Delta DVP-SA
Delta DVP-SA Series Slim PLC
Delta DVP-SA is a legacy slim PLC CPU series within the Delta DVP PLC family. It reads field inputs and executes the machine control program. The DVP12SA11R and DVP12SA11T models provide a 24 V DC supply, 8 digital inputs and 4 digital outputs. Maintenance and replacement work requires a clear distinction between SA and SA2, including output technology and CPU firmware.
Possible applications include conveyor sequencing, pump and valve control, part counting, timing and small machine automation. For an existing machine, matching the enclosure dimensions is insufficient: review the program, field wiring, retained data and communication settings together.
DVP-SA models and ordering-code differences
DVP12SA11R is the CPU with 8 inputs + 4 relay outputs. DVP12SA11T provides 8 inputs + 4 transistor outputs. Relay outputs switch suitable loads within their ratings; pulse applications require the transistor model and the designated Y output.
DVP12SA10R is separately listed in the manufacturer’s slim PLC conformity appendix as an 8-input / 4-relay-output controller. Do not treat 10R and 11R as the same ordering code. The detailed memory and wiring values on this page come from DVP12SA11R/T installation documents; match the 10R nameplate to its own hardware documentation.
Program memory, battery and retained data
The DVP12SA11R/T instruction sheet specifies 7,920 program steps, commonly described as the 8k class. It also lists 5,000 D registers and a separate 1,600-word file-register area. The D range includes special and retained areas, so these figures should not all be interpreted as unrestricted user data.
These legacy SA models use SRAM with battery backup. Battery condition matters for the program, real-time clock and retained data. Check the BAT.LOW indicator. Read and back up the program and required data before battery replacement or extended unpowered storage. The short replacement interval stated in the manual is not a guarantee against data loss in aged equipment.
Which programming software is supported?
WPLSoft is the Windows ladder programming tool explicitly listed in the SA instruction sheet. Select the correct SA target CPU for program editing, readback and maintenance. The same document also lists the DVPHPP02 handheld programming panel as a legacy programming option.
ISPSoft has a CPU firmware requirement: the manufacturer’s archived compatibility table specifies V1.6 or later for DVP-SA/SX. This refers to the PLC firmware, not the ISPSoft installation version. Do not assume support on an earlier CPU; read its firmware and match the programming tool and target model accordingly.
For ISPSoft versions using COMMGR, configure the serial communication driver with the correct COM port. WPLSoft also requires the correct COM number and serial settings. The cable driver, communication manager and PLC programming editor are separate components. Preserve the original program and device data when converting a WPLSoft project, then check instructions and addressing in the converted project.
Which programming cable is required?
The legacy SA instruction sheet explicitly lists DVPACAB2A30 for connecting a PC. This connects the PC DB9 RS-232 port to the PLC COM1 8-pin mini-DIN RS-232 port. DVPACAB215 and DVPACAB230 are also listed as earlier serial cable options.
A USB-equipped PC can use a suitable USB-to-RS-232 converter plus the correct PLC cable. Review UC-PRG020-12A as an integrated option and the DVP programming cable information. For DB9-to-mini-DIN cables such as UC-MS020-01A, verify the pinout and any PC-side converter. A USB-TTL adapter cannot replace RS-232; the SA CPU has no native USB port.
Power supply and I/O wiring
DVP12SA11R/T requires 24 V DC, with a documented operating range of 20.4–28.8 V DC. Built-in inputs are X0–X7 and outputs are Y0–Y3. Wire the S/S input common for the sensor’s sink/source circuit. Sensor PNP/NPN technology is a separate issue from the CPU’s relay/transistor output type.
On DVP12SA11R, Y0 uses common C0, Y1 uses C1, and Y2/Y3 share C2. Assuming a single common for all outputs can cause wiring errors. For the transistor model, check load supply, common terminals, polarity and permissible current against its own wiring diagram.
Pulse outputs, communication and built-in adjustments
The reviewed legacy DVP12SA11T installation sheet specifies 32 kHz for Y0 and 10 kHz for Y1. These pulse ratings do not apply to the relay model. Do not transfer SA2’s 100 kHz-class specifications to an older SA; check the instruction, output current and hardware revision against the applicable document.
COM1 RS-232 and COM2 RS-485 serve programming and suitable serial communication applications. Match the protocol, station address, speed and data format when connecting an HMI or drive. The standard legacy SA CPU has no built-in Ethernet port. DVP12SA11R/T also has an RTC and two adjustment potentiometers; these are not general-purpose external analog input channels.
Expansion and other DVP series
Explore DVP Slim digital modules, DVP Slim analog modules and DVP Slim temperature modules for additional field signals. When selecting DVP expansion modules, verify legacy SA support, module order, power requirements and any FROM/TO operations in the program. A newer module’s slim enclosure does not establish compatibility with an older SA CPU.
DVP-SS, DVP-SX and DVP-SV are distinct CPU families. Migration to DVP-SA2, DVP-SS2, DVP-SX2, DVP-SV2 or DVP-SE requires a fresh comparison of memory, instructions, ports and terminal layout. Adding a “2” to a related series name does not imply a drop-in replacement.
Editor’s Note
On an older SA, battery condition deserves an early check. A POWER indicator does not prove that the program is intact. Connect the PC, read the program and check BAT.LOW and clock information.
Back up before disconnecting the battery. If a controller has spent years on a shelf or its battery has failed, fitting a new battery cannot restore an already lost program. Preserve the project and the machine’s retained settings together.
Before condemning the CPU, measure the 24 V supply at its terminals while loads operate. Supply drop, corroded connectors and loose commons can resemble processor faults.
A clicking relay and an output LED are not sufficient tests. Check relay contacts under a suitable load and transistor outputs with the correct supply and polarity. Pay particular attention to the separate commons for Y0, Y1 and Y2/Y3.
For connection problems, verify the mini-DIN cable, USB-to-RS-232 driver and COM number in order. With ISPSoft, check CPU firmware rather than confusing the V1.6 requirement with the editor version.
Locate the faulty circuit by measurement before replacing parts. With power disconnected, inspect the supply, battery connector, affected input optocoupler or output driver as appropriate. Finish with program readback, loaded I/O tests and a power-cycle test on a backed-up controller.
Manuals and related topics
Use Delta DVP PLC files as the series document hub. The DVP-SA installation and wiring sheet hosted on this site is in Turkish and covers the legacy DVP12SA11R/T. It is not an SA2 manual; match the model and document edition.
Navigation: Delta Automation · Delta PLC · Delta DVP PLC series · DVP-SA main page · DVP files
External references
Delta DVP12SA11R/T instruction sheet, English, 2006 · Delta DVP-PLC programming manual, English, 2017 · Delta ISPSoft software information