Delta DVP12SA10R
Delta DVP12SA10R – Slim PLC with 8 Inputs and 4 Relay Outputs
The Delta DVP12SA10R is a Delta DVP-SA PLC base unit with 8 digital inputs, 4 relay outputs and a DC supply. Delta’s DVP Slim declaration of conformity lists the DVP12SA10R and DVP12SA11R on separate lines. The declaration confirms the I/O configuration. Use the nameplate and the model-specific wiring diagram to check nominal supply voltage, terminal assignments, contact ratings and hardware revision.
I/O and panel checks
An eight-input layout suits small machines that monitor on/off signals from sensors, pushbuttons and limit switches. The PNP and NPN wiring guide explains how sensor outputs relate to the input common. For relay outputs, check the type of load, terminal common groups and switching frequency. Use the panel drawing to check coil suppression and interposing relay requirements for valves and contactors.
When planning a replacement, record the part numbers of the Delta DVP expansion modules, digital I/O modules and analog modules. Compare the expansion layout, addresses in the ladder program and operator panel communications with the existing panel, even if the input and output counts match.
Programming software and cable
Delta uses WPLSoft for the DVP family. The DVP12SA11R/T instruction sheet lists the COM1 RS-232 programming port and the DVPACAB2A30 and DVPACAB230 PC-to-PLC cables. The same sheet identifies COM2 as the RS-485 communications port. Confirm the DVP12SA10R software model selection, port and programming cable against its hardware revision. The legacy ISPSoft 1.01 manual lists DVP-SA/SX support from firmware V1.6. Check the CPU firmware when choosing the PLC programming software release.
Editor’s Note
Ask for a close-up of the nameplate when buying a used unit. 10R and 11R are easy to mix up in a quotation.
With the panel de-energized, inspect the terminal cover, terminal screws and expansion connector. Photograph any corrosion or heat damage.
If you can read the program before removing a working unit, save a backup. Keep the panel drawing, relay common assignments and communications settings with it.
On the bench, test each relay contact separately with a suitable test load. The output LED shows the command. A measurement across the load confirms switching.
For a spare, compare the program, field wiring, expansion arrangement and mounting dimensions as well as the number of I/O points.
Related models and topics
The DVP12SA11R and DVP12SA11T are the relay and transistor models of the DVP-SA series. The DVP12SA211R and DVP12SA211T belong to the DVP-SA2 series. For a new panel, the Derell Series B PLCs can also be assessed against the project’s I/O and software requirements.
Used Delta automation equipment · Delta PLC · Delta DVP PLC series · Delta DVP PLC files · DVP12SA11R/T instruction sheet (PDF)
External references
Delta DVP Slim declaration of conformity, DVP12SA10R entry (2024) · Delta cUL listing, E206327 · Delta ISPSoft 1.01 compatibility table (2011)