Delta DVP-SV

Delta DVP-SV Series PLC

Delta DVP-SV is an earlier generation of expandable main PLCs in the Delta DVP family. It provides a 24 V DC supply, 16 digital inputs, 12 digital outputs and 16K steps of program memory. DVP28SV11R has relay outputs, while DVP28SV11T has NPN transistor outputs. The SV executes its own control program; it is not an expansion module.

Keep the distinction between SV and SV2 when selecting a replacement. DVP28SV11R/T belongs to the original SV generation; codes such as DVP28SV11R2/T2 identify SV2 units. Do not assign the SV2's 30K-step memory or other generation-specific features to an original SV. Compare the full nameplate code with the existing project and field wiring.

Inputs, outputs and motion applications

The R relay model suits control duties requiring contact outputs. The T transistor model is the option to assess for fast switching and suitable pulse applications. Its designated high-speed outputs can generate pulses at up to 200 kHz. This rating does not apply to every output or to the relay model. Check the receiving servo or step drive's signal type, pulse/direction arrangement and input wiring.

With suitable expansion modules, an SV system can reach 512 digital I/O points in total. This ceiling does not make every module combination valid. Select Slim digital, analog and temperature modules by exact code, mounting side, power budget and addressing. Analog measurement signals must not be connected directly to the main unit's digital inputs.

Which software programs the DVP-SV?

WPLSoft is an option for creating ladder programs, transferring programs and monitoring a DVP-SV online. Preserve the original .dvp file when maintaining an existing WPLSoft project. Select the correct SV CPU family when creating a project; matching the number of I/O points alone is insufficient.

ISPSoft also supports DVP-SV programming. Delta's ISPSoft manual includes SV project examples. ISPSoft 2.0 and later use a COMMGR communication channel. WPLSoft files can be imported into ISPSoft; keep a separate original copy and check the compilation results after conversion. Do not assume every ISPSoft language or function is available on every CPU. The Delta PLC software section explains the roles of the different tools.

Programming cable and PC connection

The basic PC connection uses the PLC's COM1 RS-232 port. DVPACAB2A30 is a serial programming cable with a 9-pin D-sub connector at the PC end and an 8-pin mini-DIN connector at the PLC end. When choosing a Delta PLC cable, check the RS-232 electrical standard and pin assignments as well as the connector shape.

A computer without a serial port can use a USB-to-RS-232 converter plus DVPACAB2A30. Install the converter's Windows driver and select its assigned COM port number. This arrangement does not mean the SV has a built-in USB port; an ordinary USB printer cable cannot replace this serial connection.

For ISPSoft, create and start the appropriate serial driver in COMMGR, then select that channel in ISPSoft. The baud rate, data bits, parity, stop bits and station address must match the PLC's existing settings. If connection fails, first check the COM selection, cable and other programs using the port. Avoid changing a working machine's communication settings by trial and error.

RS-485 and network expansion

The SV also has a COM2 RS-485 communication port. Check the protocol, station addresses and line wiring against the existing HMI or field-device project. For Ethernet requirements, assess Slim communication modules and, where the project supports it, DVPEN01-SL. Ethernet must not be described as a built-in port of the SV main unit.

Editor's Note

Start with a clear nameplate when buying a used SV: R or T, SV or SV2? Similar housings can hide differences that leave you reworking the wiring and project later.

Before making changes, back up the accessible program, parameters and retained data. Uploading the program does not prove that every machine setting has been recovered; check recipes and initial values as well.

Take the BAT.LOW indicator seriously, particularly on a unit stored without power. Check data retention before testing. Do not perform a power-cycle experiment or memory operation before making a backup; consult the manual about the battery and Flash backup.

An input LED is only part of the test. Monitor inputs in software and test each output with a suitable load. Look for unreliable contacts on relay units and leakage or incomplete switching on transistor units.

For pulse applications, the RUN indicator alone proves little. Measure the signal at the correct output and confirm that the drive accepts it. Make the mechanical area safe before allowing movement.

When communication fails, first verify the 24 V supply, cable, converter and COM settings. Comparing the same connection with a known working unit can help separate a cable problem from a PLC fault.

Manuals and related topics

Use Delta DVP PLC files for installation, connection and programming documents. Read the model table in a shared SV/SV2 document rather than applying a later generation's ratings to the original unit.

Related topics: DVP-SV2 · DVP-SS2 · DVP-SA2 · DVP-SX2 · Slim positioning modules. These links support comparison; they do not establish direct equivalence or a drop-in replacement.

Navigation: DVP PLC series · Delta PLC main category · Used Delta equipment · PLC software · DVP files

External references

Delta DVP-SV/SV2 instruction sheet, 2012 (English and Chinese; manufacturer's document hosted in a distributor archive) · Delta ISPSoft user manual, 2021 (English, archive view).


Refine Search