Delta DVP28SV11T

Delta DVP28SV11T – DVP-SV PLC with 16 Inputs and 12 NPN Outputs

Delta DVP28SV11T is a DVP-SV main processing unit with 16 digital inputs and 12 NPN transistor outputs. This PLC CPU executes its own application. Its 16K-step program memory and four high-speed pulse-output groups support sequencing, counting and positioning applications.

Check the complete label: DVP28SV11T and DVP28SV11T2 are different models. The suffix-2 product belongs to the SV2 generation and has 30K-step memory. The original SV model covered here has no built-in analog inputs; analog measurements require a suitable extension.

Power supply and digital inputs

Supply: 24 V DC, permitted range 20.4–28.8 V DC; CPU consumption is 6 W. External sensors and output loads are additional. Size the power supply for the complete installation and measure supply voltage while the machine is under load.

Input addresses are X0–X17; outputs are Y0–Y13. X/Y numbering is octal, so X10 follows X7. When connecting a sensor, match its NPN/PNP arrangement to the S/S common: S/S connects to 0 V for PNP sensors, or +24 V for NPN sensors. Check the manufacturer's terminal drawing for the common groups.

An inductive sensor, photoelectric sensor or limit switch may provide the required input indication, but wiring and response time must suit the application. An illuminated input LED does not prove that the application captures every short pulse.

High-speed counters and 200 kHz pulse outputs

The hardware table specifies 200 kHz for X0, X1, X4 and X5, and 20 kHz for X10, X11, X14 and X15. The remaining inputs are in the 10 kHz class. For an encoder, check counter mode, A/B-phase evaluation, input filtering and permitted pulse widths. These ratings do not establish identical counting performance on every input.

Four high-speed pulse groups: CH0 uses Y0/Y1, CH1 Y2/Y3, CH2 Y4 and CH3 Y6. Pulse and direction assignments depend on the instruction. Hardware outputs Y0–Y4 and Y6 are in the 200 kHz class; Y5, Y7 and Y10–Y13 are in the 10 kHz class. Six fast terminals do not mean six independent 200 kHz axes.

The series also supports two-axis interpolation instructions. When commanding a servo drive, verify its NPN open-collector input compatibility, signal voltage and wiring. Do not apply a 24 V field signal directly to a 5 V differential receiver. In feeding, cut-to-length and packaging automation, clean pulse waveforms and reliable homing matter alongside frequency.

NPN output wiring and load selection

Outputs are NPN open collector. Connect the load between +DC and Y, and the corresponding C common to 0 V. C0: Y0/Y1; C1: Y2/Y3; C2: Y4/Y5; C3: Y6/Y7; C4: Y10–Y13. Check the output-load supply as well as the CPU supply.

The 2014 instruction sheet specifies 5–30 V DC output operating voltage and a 0.3 A/point resistive-load limit at 40 °C. Assess load current, temperature and high-frequency switching conditions together. This load rating does not justify attaching an arbitrary load to a high-speed pulse circuit.

A transistor output is not a dry contact. A suitable interposing relay can separate a load; check contactor coil voltage and inrush current. Appropriate diode/suppression circuitry for DC inductive loads, a correctly selected fuse and proper grounding help protect the outputs.

Programming software and cable

WPLSoft and ISPSoft can program this PLC. WPLSoft supports existing DVP Ladder projects and service work; ISPSoft can be used with its supported DVP-SV target. Select SV, rather than SV2, when creating the project. Check the software release's CPU/firmware support and validate an existing project before transferring it to replacement hardware.

A PC can connect through COM1 RS-232. The PLC connector is an 8-pin mini-DIN. For a USB computer, use the UC-PRG020-12A USB-to-RS-232 programming cable. A physical RS-232 port can use a correctly wired serial cable such as UC-MS020-01A; a suitable USB-to-RS-232 converter can also be used with that serial cable. The mini-DIN socket is not a native USB interface.

For ISPSoft, configure the appropriate serial driver in COMMGR. Match the Windows COM number, serial format and PLC station. Before PLC programming, back up the running application and important retained registers. Uploading a CPU program may not recover every comment and symbol from the original engineering project.

Communication and expansion

The CPU provides COM1 RS-232 and COM2 RS-485. RS-232 can serve the engineering connection, while RS-485 supports a multi-device field network. Match Modbus ASCII/RTU, master/slave role, station and serial format to the application. There is no built-in Ethernet port.

Compatible DVP Slim extension modules add digital, analog and temperature functions; the series supports up to 512 digital I/O points. Check module compatibility, CPU version, module count and power capacity for the actual assembly. Left-side special modules and standard right-side extensions use different connection arrangements.

Related models and differences

DVP28SV11R: The same SV generation with 16 inputs and 12 relay outputs. Relay outputs cannot replace the transistor model's high-speed pulse function.

DVP28SV11T2: SV2 generation, 16 inputs, 12 NPN outputs and 30K-step memory. Assess the software target and application before replacement.

DVP28SV11R2: The SV2 option with 16 inputs and 12 relay outputs. Load type and switching frequency determine its suitability.

DVP28SV11S2: SV2 generation with 16 inputs and 12 PNP transistor outputs. The NPN/PNP difference changes field wiring; transferring the existing wires is not sufficient for replacement.

Editor's Note

Read the full label first. Similar housings do not make SV and SV2 identical. For a used PLC, record the complete model, firmware and attached modules, then back up the application and important machine settings before making changes.

Take a BAT.LOW indication seriously. Check the manufacturer's battery procedure and the available backup first; preserving the program file alone may not preserve production counters and recipe values.

An output LED does not prove a healthy transistor. Test every output with an appropriate load and check fast pulse channels with a suitable receiver or oscilloscope. For missed motion pulses, inspect cables, commons and the drive input too.

For communication faults, check the cable, driver, COM number and serial settings before replacing the CPU. Inspect for a short circuit and loose terminals with power isolated, and measure supply sag during operation.

Do not rely solely on the standard PLC application for emergency stopping. Design the required safety relay and independent stopping arrangement for the machine. Make initial movement tests with the hazardous area clear and the machine in a safe state.

For a used-unit sale, state quantity, label photographs, working/faulty condition and completed tests. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.

PDF documents and related topics

For terminal diagrams and detailed tables, visit our Delta DVP PLC files page first. In the shared SV/SV2 instruction sheet, use the DVP28SV11T row. The analog-input section applies only to DVP24SV11T2.

Related topics and navigation: Delta and used models | Delta PLC | DVP PLC series | DVP-SV | DVP28SV11T model page

External references

Delta DVP-SV/SV2 instruction sheet – 30 April 2014, 5011669007-SV08
Delta DVP programming manual – 2017 edition
Delta ISPSoft User Manual – 29 March 2021
Delta support: UC-PRG020-12A USB-to-RS-232 cable