Delta DVP-ES2
Delta DVP-ES2 Series PLC
Delta DVP-ES2 is a second-generation, block-type PLC CPU family with 16k steps of program capacity and 10k words of data-register space. Applications include machine sequencing, digital I/O, high-speed counting and pulse motion with suitable transistor models. PLC programming uses WPLSoft or ISPSoft; ladder diagrams and instruction support depend on the selected CPU and software release.
The family offers different I/O counts, AC/DC supplies and relay/transistor outputs. Standard ES2, ES2-C and ES2-E do not share the same communication hardware. Select by the complete ordering code on the label rather than the ES2 family name alone.
ES2 models and built-in I/O
16 I/O: DVP16ES200R / DVP16ES200T provide 8 inputs + 8 outputs. 24 I/O: DVP24ES200R / DVP24ES200T provide 16 inputs + 8 outputs.
32 I/O: DVP32ES200R / DVP32ES200T provide 16 inputs + 16 outputs. 40 I/O: DVP40ES200R / DVP40ES200T provide 24 inputs + 16 outputs.
60 I/O: DVP60ES200R / DVP60ES200T provide 36 inputs + 24 outputs. DVP80ES200R/T provides 40 inputs + 40 outputs. These standard 200R/T CPUs require 100–240 V AC power.
24 V DC model: DVP32ES211T is a main PLC CPU with 16 inputs + 16 NPN transistor outputs, not an expansion module. Its supply differs from 200T despite the matching I/O count. Do not apply AC mains to 211T. DVP40ES200RM is an AC model with 24 inputs + 16 relay outputs; preserve the complete code, including M, when selecting a replacement.
DVP40ES200RM has a built-in SD card slot. This feature is not provided on every ES2 model.
Relay outputs, transistor outputs and sensor wiring
R identifies relay outputs; T identifies NPN/sinking transistor outputs. Relay CPUs are unsuitable for high-speed pulse generation. Connect input common S/S for the PNP/NPN sensor circuit. An AC-powered CPU does not have AC digital inputs: the inputs use 24 V DC signals.
For an inductive sensor or photocell, check output polarity, common wiring and response time. X/Y addresses use octal numbering; X10 follows X7. Correct grounding and suitable separation between signal and power wiring help prevent false counts on high-speed inputs.
Which programming software is used?
DVP-ES2 supports WPLSoft and ISPSoft. Select the correct ES2 target and check the required instructions against CPU firmware and software release. A shared manual covering several DVP families does not mean every listed instruction works on ES2.
For ISPSoft, configure the appropriate serial connection and COM port in COMMGR. Configure WPLSoft communication settings for the port used. Back up the existing program, communication parameters and required retained data before downloading a new project.
Which programming cable is required?
For a PC with USB: use the UC-PRG020-12A USB-to-RS-232 programming cable. Its PLC end connects to the 8-pin mini-DIN COM1 socket. Install the Windows driver and select the resulting COM number. Standard ES2 has no native USB programming socket. The USB-A → Mini-B connection used by ES3 does not apply to ES2.
For a PC with a physical RS-232 port: use DVPACAB2A30 or the appropriate UC-MS020-01A RS-232 cable. If the PC lacks a serial port, this cable requires a suitable USB-to-RS-232 converter. USB-TTL uses a different electrical interface, and an arbitrary mini-DIN cable does not guarantee the correct pinout. See Delta PLC programming cables for cable selection.
RS-485, CANopen and Ethernet options
Standard ES2 models provide one RS-232 and two RS-485 ports. COM1, COM2 and COM3 can operate independently with suitable configuration. For Modbus RTU, match station addresses, baud rate, data format and master/slave roles. Do not assume this port arrangement applies to every C/E variant.
The ES2-C models DVP32ES200RC / DVP32ES200TC are CANopen variants with 16 inputs + 16 outputs and a 100–240 V AC supply. A CAN port must not be assumed on every ES2 CPU without the C suffix.
The RE/TE models in the ES2-E family have built-in Ethernet. The 20-point versions provide 12 inputs + 8 outputs; the 32/40/60-point versions provide 16+16, 24+16 and 36+24 I/O respectively. For an Ethernet connection, use a suitable RJ45 network cable and configure IP/subnet settings and the software target. Standard 200R/T models have no built-in Ethernet.
Review the differences between EtherNet/IP and Modbus TCP: an RJ45 socket alone does not establish protocol, role or instruction support. Verify the required protocol against the complete CPU model and firmware.
High-speed counters, pulse outputs and motion
ES2 is specified with high-speed input capability of 100 kHz on two points and 10 kHz on six points. Actual limits depend on the selected single/two-phase counter and hardware revision. Match encoder phases, electrical output and counter mode; the 100 kHz rating does not apply to every input.
Suitable transistor models provide high-speed pulse outputs of 100 kHz on two points + 10 kHz on two points. Match the servo or stepper motor drive’s pulse/direction format, input circuit and PLC output wiring. These ratings do not apply to relay outputs; simultaneous-channel and instruction limits also require checking.
Analog measurement and expansion modules
Standard ES2 is a digital I/O CPU; the built-in analog channels of EX2 must not be attributed to ES2. Analog signal measurement and PID control require suitable modules, channel ranges and scaling. Pt100 and thermocouple sensors cannot be measured directly by ordinary digital inputs.
When selecting DVP E2 expansion modules, check ES2 compatibility, module count, addressing and power budget together. Built-in CPU I/O and expanded-system capacity are different figures; confirm the permitted arrangement in the hardware documentation for the complete model.
Editor’s Note
Start by checking whether the label says 200 or 211. Establish AC/DC supply and R/T output type before applying power. Matching the old controller’s I/O count alone is insufficient.
A failed connection does not establish a CPU fault. Check the cable driver, COM number, mini-DIN socket and communication settings. Selecting the wrong virtual serial port is a common cause of connection failure.
Back up the program and required retained data, then test inputs individually with appropriate 24 V DC signals. Test high-speed counting at a frequency representative of the application rather than relying on input indicators alone.
An illuminated output LED does not prove that the load is being driven. Test relay contacts under a suitable load and transistor outputs with correct polarity and load supply. Check appropriate suppression components on inductive loads.
Do not implement the emergency stop solely in a standard PLC program. Preserve the machine’s appropriate safety circuit and prevent unexpected movement during testing.
For repair inspection, disconnect power and verify capacitor discharge before examining the supply, connectors and affected I/O circuit. Finish with communication, loaded I/O and controlled power-cycle checks.
Manuals and related topics
Use Delta DVP PLC files for programming, installation and cable documents. An older ES2 instruction sheet may omit later C/E and higher-I/O models; compare its coverage with the current catalogue. Supporting topics include ladder diagrams and Modbus RTU.
Navigation: Delta Automation · Delta PLC · Delta DVP PLC series · DVP-ES2 main page · DVP files
External references
Delta DVP series catalogue, English · Delta ES2 and related DVP series Programming Manual, English · Delta PLC/HMI Cable Selection Guide, English