Delta DVP60ES200T
Delta DVP60ES200T – PLC with 36 Inputs and 24 NPN Transistor Outputs
Delta DVP60ES200T is a 100–240 V AC powered main PLC unit in the DVP-ES2 family, incorporating 36 digital inputs and 24 NPN transistor outputs. Its 60 built-in I/O points suit automation applications with multiple sensors, pushbuttons and actuators. The standard T model must be distinguished from the Ethernet-equipped TE version.
Program memory is in the 16K class; the manufacturer's programming manual specifies 15,872 usable steps. The onboard channels are digital. Select suitable expansion modules where analog I/O is required for measurement or control.
Inputs and addressing
The 36 inputs use X0–X43 and the 24 outputs use Y0–Y27. X/Y addresses follow octal numbering: X10 follows X7, and Y10 follows Y7. Consequently, X43 does not mean that the CPU has 44 physical inputs.
Inputs support 24 V DC sink/source wiring. Configure the S/S common to match the NPN/PNP arrangement, then check sensor and limit switch signals accordingly. For high-speed counting, check the encoder output type, channel assignment and input filter together. A line driver encoder output is not electrically identical to an ordinary 24 V input signal.
Transistor outputs and pulse frequencies
Outputs are NPN open collector. The instruction sheet specifies a resistive-load limit of 0.5 A per point and 4 A per common group. Wire the field supplies for UP0/ZP0, UP1/ZP1 and UP2/ZP2 according to the manufacturer's NPN circuit. Powering the CPU alone does not establish the output load supply.
The manufacturer's output table distinguishes Y0 and Y2: 100 kHz; Y1 and Y3: 10 kHz. The remaining Y outputs have a specified switching limit of 1 kHz; they are not positioning channels with the same performance. Check channel pairing and instruction support for pulse/direction or CW/CCW operation. A transistor output is not electrically equivalent to a 5 V differential line-driver output.
DC valves and interposing relay coils require a load current calculation, suitable fuse protection and suppression. Check voltage and load type before connecting a contactor coil. Observe the polarity of a diode across a DC coil. Do not connect an AC load directly to these outputs.
Power supply and panel wiring
Connect 100–240 V AC to L/N. The instruction sheet lists 30 VA consumption and a 24 V DC / 500 mA auxiliary output. This 500 mA is a shared budget for input circuits and external loads, rather than an additional unrestricted load allowance. Do not arbitrarily parallel an external 24 V power supply with the PLC's auxiliary output.
Check grounding, terminal tightness and possible load-side short circuits. The normal PLC program does not replace the emergency stop and safety relay circuit.
Programming software and cable
WPLSoft and ISPSoft are programming tools for DVP-ES2. Select the ES2 CPU target in the PLC programming project and assess the existing Ladder program, instructions and CPU firmware together. Firmware conditions for the older ES family must not be transferred unchanged to ES2.
Programming uses COM1 RS-232 with an 8-pin mini-DIN connector. The manufacturer's ES2/EX2 cable table lists the UC-PRG020-12A USB programming cable and the UC-MS020-01A RS-232 cable. The latter requires a suitable PC serial port or USB-to-RS-232 converter. Install the USB cable driver and select the correct COM number. For ISPSoft, configure the COMMGR serial driver and port settings.
Communication and expansion
The standard CPU has one RS-232 and two RS-485 ports: COM1 is RS-232, while COM2/COM3 are RS-485. Match station, baud rate, parity and protocol settings for Modbus ASCII or Modbus RTU. There is no native Ethernet or USB port.
Assess the ES2 expansion interface, module supply and address allocation together. A physically similar DVP module is not automatically compatible. Where Ethernet is required, assess a suitable network-equipped model such as DVP60ES200TE.
Editor's Note
Check the complete model ending first. 60ES200T and 60ES200R use different output circuits, while the TE version has different communication hardware. A matching total of 60 points does not establish equivalence.
For a used unit, test every input and all three output groups separately. If an output LED lights but the load remains off, measure the UP/ZP supplies and common return before concluding that the CPU is faulty.
Check pulse operation on Y0 and Y2 with a suitable receiver or oscilloscope. An average voltage reading on a multimeter does not establish pulse frequency or edge quality.
Back up the project, necessary retained data and serial-port settings before making changes. Downloading a program or forcing outputs can affect machine movement.
Review loose terminals, corrosion, burn marks and previous repairs using photographs. Check power-restoration behaviour under controlled conditions. These notes are not completed test results for a particular unit.
Related models
DVP60ES200R provides the same 36-input/24-output count with relay outputs; it does not replace high-speed transistor pulse outputs. DVP40ES200T offers 24 inputs/16 transistor outputs, and DVP32ES200T offers 16 inputs/16 transistor outputs. Compare DVP60ES200TE for projects requiring Ethernet. These are project candidates, not assumed plug-in equivalents; check programs, terminals and supplies.
PDF documents and related topics
Visit our Delta DVP PLC files page. The existing Turkish DVP-ES2 installation and wiring sheet and English/Chinese DVP-ES2 instruction sheet cover this model. EX2 analog tables within the shared document do not establish onboard analog channels on DVP60ES200T.
Related topics: NPN/PNP wiring principles, evaluating encoder signals and RS-485 field communication.