Delta DVP-ES2 CANopen
Delta DVP-ES2 CANopen PLC · DVP32ES200RC and DVP32ES200TC
The Delta DVP-ES2-C is a compact PLC family that executes the machine program and communicates with drives over its built-in CANopen interface. Both the DVP32ES200RC and DVP32ES200TC have a 100–240 V AC supply, 16 digital inputs, 16 digital outputs and an integrated CANopen port. The CPU can operate as either the network master or a slave.
DVP32ES200RC vs DVP32ES200TC
The DVP32ES200RC has mechanical relay outputs. These can control an interposing relay or contactor coil within the specified electrical ratings. The DVP32ES200TC has open-collector transistor outputs. Check the TC wiring diagram for the DC load supply, output commons and required switching speed.
Both CPUs use 24 V DC digital input signals. When connecting an inductive sensor, check its PNP or NPN output against the PLC’s S/S input common wiring.
What are COM1, COM2 and COM3 used for?
COM1 is the 8-pin mini-DIN RS-232 port for the PC connection. COM2 is the RS-485 port and can be configured for Modbus RTU. COM3 connects to the CANopen field network. The standard DVP32ES200R and DVP32ES200T use COM3 as a second RS-485 port. For built-in Ethernet, see the RE and TE models in the DVP-ES2-E family.
Programming software and cable
Use WPLSoft or ISPSoft for PLC programming and ladder logic. Check the project’s CPU target and firmware support for the instructions used. For ISPSoft, select the serial channel in COMMGR.
For a PC with USB, connect the Delta UC-PRG020-12A USB-to-RS-232 programming cable to COM1. Install the cable driver and select the COM number assigned by Windows. For a PC with a physical RS-232 port, use the Delta UC-MS020-01A serial cable.
Use CANopen Builder to configure the network. Connect the PC through COM1 and set the CPU role, node ID and CAN bit rate. Add the field devices and configure their PDO mappings in the network project. The PC’s serial baud rate and the CANopen field bus bit rate are separate settings.
CANopen network, drive connection and field wiring
The ES2-C supports the CiA DS301 V4.02 communication profile. In master mode, Delta specifies up to 16 slave nodes with IDs from 1 to 16. In this industrial communication setup, PDOs carry operating data, SDOs provide access to device parameters, and NMT manages node states. See the CAN communication guide for bus and node terminology.
Delta’s application example uses an ASD-A2-…-M CANopen model from the ASDA-A2 series. The PLC sends commands to the servo drive and reads the actual motor speed reported by the drive. The encoder remains connected to the servo system’s feedback circuit. Before adding a variable-frequency drive, check the complete drive code, CANopen support and any required communication option card.
Use shielded twisted-pair CAN cable. The COM3 terminals are marked CAN+ = CAN-H, CAN− = CAN-L and SG = signal ground. Fit one 120 Ω termination across CAN+ and CAN− at each physical end of the trunk. Higher bit rates reduce the permitted bus length. Route the bus away from motor and power wiring and check the shield connection against the panel’s grounding scheme. If drive noise affects communication, check the cable routing and the EMC filter together.
Editor’s Note
Start with the nameplate. The RC and TC models share the same I/O count, but their output commons differ. Photograph the old terminals before swapping a CPU.
When buying a used unit, check more than the POWER and RUN LEDs. Read the program through COM1 and test COM3 with a known-good CANopen node.
If COM3 shows a red indication, first check the bit rate, node IDs, CAN-H/CAN-L polarity and termination at both ends. With power off, two 120 Ω terminators in parallel read roughly 60 Ω across the bus.
If the drive is online but the speed on the HMI screen stays unchanged, compare the PDO mapping with the PLC register address. Then check the display scaling and units.
Back up the PLC program and the CANopen Builder network project separately. Keep the EDS file, node list and drive parameters together in the machine folder so the network can be restored after a CPU replacement.