Delta DVP32ES200R
Delta DVP32ES200R PLC with 16 inputs and 16 relay outputs
The Delta DVP32ES200R is a 100–240 V AC PLC CPU in the DVP-ES2 series. It has 16 digital inputs, 16 relay outputs and a 16K-step program capacity. Its digital input and output layout suits sensor monitoring, sequencing and on/off control in a panel.
24 V DC digital inputs and high-speed counting
X0–X17 are octal addresses. The S/S input common allows sink or source wiring. The +24V/24G auxiliary supply output is rated at 500 mA. Check for an NPN or PNP output when selecting an inductive sensor, and confirm the contact function for a limit switch. Use a suitable expansion module for a transmitter that needs an analog input.
For single-phase hardware counting, Delta specifies up to 100 kHz on X0 (C243) and X2 (C244). When connecting an encoder, verify the A/B phase assignments, high-speed counter number and pulse frequency limits for the selected mode.
Relay outputs and C0–C3 commons
C0 serves Y0–Y3, C1 serves Y4–Y7, C2 serves Y10–Y13 and C3 serves Y14–Y17. Delta specifies 2 A per point and 5 A per common for resistive loads and a contact response time of approximately 10 ms. The 2024 instruction sheet specifies a maximum relay switching frequency of 1 Hz. For coils, use the load limits and relay contact life curves in the manual. Verify each output group's fuse and load circuit against its terminal diagram.
Programming software and cables
Use WPLSoft or ISPSoft for ladder programming. For ISPSoft, select the PC COM port in COMMGR. COM1 is the 8-pin mini-DIN RS-232 port. Use UC-PRG020-12A for USB or UC-MS020-01A for DB9 RS-232. Delta’s programming manual also shows the UC-MS030-01A pinout.
COM2 and COM3 are RS-485 ports. Match the Modbus ASCII or Modbus RTU settings to the connected HMI or drive. Choose the cable and converter for the RS-232 or RS-485 interface in use.
Editor’s Note
On a used unit, check the 200R suffix, terminal covers and L/N supply markings. Wire sensors for the 24 V DC input circuit.
Back up the existing project and serial settings when you connect. Before removing the PLC, label the load group served by each of the C0–C3 commons.
Even if a relay clicks, check the contact. With the load circuit disconnected, use a multimeter to confirm that it opens and closes.
If the count is unstable, verify the input assignment and the signal reaching the digital input. Cable shielding and grounding can also affect the reading.
For intermittent input or communication faults, check whether sensor wiring runs near motor cables and whether electromagnetic interference could be affecting the signal.
PDF manuals
Delta DVP PLC files · ES2 instruction sheet (EN/Chinese) · ES2 hardware guide (Turkish)
Related topics and models
The DVP32ES200T has the same I/O count with transistor outputs. The DVP24ES200R has 16 inputs and 8 relay outputs. The DVP40ES200R has 24 inputs and 16 relay outputs. For built-in Ethernet, see the DVP32ES200RE.
DVP32ES200R · Delta DVP-ES2 · Delta DVP PLC series · Delta PLC · Used Delta automation
External references
Delta programming manual (EN) · 2024 ES2 instruction sheet (EN/Chinese) · Delta PLC/HMI cable selection guide (EN)