Delta DVP40ES200R

Delta DVP40ES200R DVP-ES2 Relay Output PLC

The Delta DVP40ES200R is a compact PLC CPU from the DVP-ES2 series with 24 digital inputs and 16 relay outputs. It runs on 100–240 V AC and has a program capacity of 16k steps. It reads sensors and push buttons and controls contactors and valves in industrial automation applications such as conveyors, filling and packaging.

24 V DC inputs and C0–C3 relay groups

The X0–X27 inputs accept 24 V DC signals. For an inductive sensor or photoelectric sensor, wire the S/S common according to the PNP/NPN wiring diagram. Addresses are octal, so X10 follows X7. Identify analog and digital inputs at the start of the project. Use a compatible DVP expansion module to measure analog signals.

C0 → Y0–Y3, C1 → Y4–Y7, C2 → Y10–Y13, C3 → Y14–Y17. Delta rates the relay contacts at 2 A per point and 5 A per common for resistive loads. The maximum relay switching frequency is 1 Hz. Select the interposing relay, coil suppression and fuse for the actual coil or valve load when designing the control panel.

For counting pulses from an encoder or sensor, check the encoder output type and high-speed counter mode. The instruction sheet specifies up to 100 kHz for inputs X0 and X2. The limit for X1 and X3 varies by production date. For pulse-output positioning, see the transistor-output DVP40ES200T, which has the same I/O count.

Programming software, cable and communications

Use WPLSoft or ISPSoft for PLC programming and select the DVP-ES2 CPU type. Connect the computer’s USB port to the CPU’s 8-pin Mini-DIN COM1 (RS-232) port using the Delta UC-PRG020-12A programming cable. For a computer with a DB9 serial port, use the UC-MS020-01A cable. Configure ISPSoft through COMMGR and select the COM number assigned by Windows when using the USB cable.

COM2 and COM3 are RS-485 communication ports. Use Modbus RTU over RS-485 to connect an HMI, SCADA system or drive. Match the station address, baud rate and parity when setting up industrial communications. Route serial wiring separately from power cables to reduce electromagnetic interference.

Editor’s Note

On a used CPU, check the DVP40ES200R label first. Inspect the C0–C3 terminals for discoloration, looseness or cracks.

When an output LED lights, verify the contact with a suitable test load. Check contact resistance on outputs that have regularly driven valves or contactors.

Back up the program and parameters from the running CPU. Record the station address, baud rate and parity for COM2 and COM3.

On the bench, verify the X0–X27 inputs with an appropriate 24 V DC signal and test the relays by common group.

Before putting the panel back into service, check the L/N supply, S/S wiring and grounding against the wiring diagram.

Related models and documents

For the same 24 inputs and 16 relay outputs with a memory card slot, see the DVP40ES200RM. For built-in Ethernet, see the DVP40ES200RE. Compare the DVP32ES200R and DVP32ES200T for 16 inputs and 16 outputs, or the DVP60ES200R and DVP60ES200T for 36 inputs and 24 outputs.

For smaller panels, the DVP24ES200R and DVP24ES200T provide 16 inputs and 8 outputs. The DVP16ES200R and DVP16ES200T provide 8 inputs and 8 outputs.