Delta DVP24ES200T
Delta DVP24ES200T 24-Point Transistor Output PLC
The Delta DVP24ES200T is a 100–240 V AC main unit in the Delta DVP-ES2 series. This PLC CPU provides 16 digital inputs and 8 transistor outputs on removable terminal blocks. It has a 16K-step program capacity and supports up to 256 total I/O points with compatible ES2/EX2 expansion modules. It suits conveyors, sorting equipment and feeders that use more sensor inputs than control outputs.
Power supply and digital I/O wiring
L and N supply AC power to the CPU. The X0–X17 inputs accept 24 V DC signals. Wire S/S according to the sensor type and the sink or source diagram. Y0–Y7 are open-collector transistor outputs. The load circuit is rated for 5–30 V DC. Delta specifies 0.5 A per output and 4 A per common for resistive loads. The output circuit requires a 24 V DC auxiliary supply at UP and ZP. The instruction sheet identifies ZP as the NPN common and UP as the PNP common.
High-speed inputs and pulse outputs
The input limits are 100 kHz at X0 and X2, 10 kHz at X1 and X3–X7, and 60 Hz at X10–X17. The output switching limits are 100 kHz at Y0 and Y2, 10 kHz at Y1 and Y3, and 1 kHz at Y4–Y7. When commanding a servo drive or stepper drive with pulses, check the drive input levels and common terminals. For a line-driver encoder, check how to interface its differential output with the PLC input.
Programming software and cable
Use Delta WPLSoft or Delta ISPSoft for PLC programming. Select the DVP-ES2 CPU family in the project. The PC connects through COM1 RS-232. Use the UC-PRG020-12A converter cable for a USB port or the UC-MS020-01A cable for a native RS-232 port. Both have an 8-pin mini-DIN connection at the PLC end. After installing the USB cable driver, select the assigned COM port in WPLSoft or in COMMGR for ISPSoft.
RS-485 field communication
COM2 and COM3 are separate RS-485 ports. They can communicate with HMIs, drives and meters using Modbus ASCII/RTU. Set matching baud rates, parity and stop bits, and assign a distinct station address to each device on the same bus. See the industrial communication and Delta HMI files pages for panel integration.
Editor’s Note
Read the DVP24ES200T nameplate first. Check the panel’s L/N supply and the 24 V DC signal circuit separately.
If an input LED stays off, check the S/S common and the sensor output before replacing the sensor.
If the output LED is on and the load stays off, measure the UP/ZP supply and the load circuit against the wiring diagram.
For a pulse-controlled axis, match the program’s Y address to the physical terminal. Check the drive settings and pulse frequency as well.
Back up the program and serial port settings before removing the unit. On the bench, check POWER, RUN, ERROR and I/O status separately. See the PLC troubleshooting guide for these checks.
Related models and topics
For 16 inputs and 8 relay outputs, see the DVP24ES200R. Transistor-output options include the DVP16ES200T, DVP32ES200T, DVP40ES200T and the 24 V DC DVP32ES211T. For Ethernet projects, see the DVP-ES2 Ethernet models.
See the DIN rail and grounding guides for panel mounting and noise control.