Delta DVP E2 modules

Delta DVP E2 Modules

Delta DVP E2 modules add analogue inputs and outputs, RTD and thermocouple measurement, or resolver feedback to compatible Delta DVP PLC systems. On the DVP-ES2 and DVP-EX2, they use the right-side expansion bus. For replacements, check the full part number, the signal type and the module order in the PLC program.

E2 module selection guide

Select a model number to open its device page. AI means analogue input, AO means analogue output and the hex ID is the code the ES2/EX2 uses to identify the module.

ModelI/OApplicationHex ID
DVP04AD-E24 AIVoltage or current measurementH0080
DVP02DA-E22 AOTwo analogue reference outputsH0041
DVP04DA-E24 AOFour analogue reference outputsH0081
DVP06XA-E24 AI + 2 AOMeasurement and analogue control in one moduleH00C4
DVP04PT-E24 RTDPt100 and other supported RTDsH0082
DVP04TC-E24 TCJ, K, R, S, T, E and N thermocouplesH0083
DVP10RC-E2ResolverAngle measurement and position-based outputsH0026

Selecting analogue inputs and outputs

Choose AD to read sensors, DA to send commands, or XA for both. For example, the DVP06XA-E2 can read a pressure transmitter and send a speed reference to a variable-frequency drive from one module. Match the input channel mode to the transmitter and the output voltage or current mode to the receiving device.

Scaling example. With standard 4–20 mA scaling on the DVP04AD-E2, 4, 12 and 20 mA correspond to raw values of 0, 16,000 and 32,000. A 0–10 bar transmitter should display 0, 5 and 10 bar. A DA output in the same current mode produces a nominal 12 mA for a raw command of 16,000. Verify the analogue signal direction and scale before enabling PID pressure control.

RTD, thermocouple and resolver connections

The DVP04PT-E2 reads two- or three-wire RTDs such as Pt100, Pt1000, Ni100 and Ni1000. Use the manufacturer’s three-wire diagram where lead resistance affects the reading. The DVP04TC-E2 supports type J, type K, R, S, T, E and N thermocouples. Match the probe label, channel settings, polarity and extension wire type. In PID temperature control, these modules measure temperature. A separate output and a suitable SSR or power stage drive the heater.

The DVP10RC-E2 reads shaft angle from a resolver and provides angle comparison outputs. Delta specifies 12-bit resolver input resolution. Check the resolver excitation and signal ratings before installation. Our resolver and encoder comparison can help identify existing feedback hardware. On machines with brake control, check the output wiring against the machine circuit diagram.

CPU compatibility, software and module registers

Use WPLSoft or ISPSoft for ES2/EX2 PLC programming. Configure COMMGR for ISPSoft. Connect the PC to the CPU. The UC-PRG020-12A suits compatible COM1 RS-232 ports. Check the port and pinout in the Delta PLC cable guide and review the differences between RS-232 and RS-485.

On the ES2/EX2, D1320–D1327 show the special module IDs in connection order. If a DVP04AD-E2 is the first special module, D1320 = H0080 is expected. In ladder logic, TO writes settings and FROM reads data from the model-specific control registers. If the module order changes, check the module numbers in these instructions and verify the HMI and SCADA tags.

When moving to a DVP-ES3 or EX3, check each E2 part number against the new CPU’s hardware list. Delta’s ES3/EX3 documentation lists several E2 analogue and temperature models. Check DVP10RC-E2 separately because that document does not confirm its compatibility.

Editor’s Notes

Read the suffix on the nameplate first. The DVP04PT-E2 and DVP04PT-S serve similar measurement duties. Choose the spare from the expansion family supported by the CPU and check the wiring diagram.

Measure the 24 V DC supply under load. If the CPU cannot see the module, check external power, the side connector and the IDs in D1320–D1327. When buying used, check that the removable terminal block comes with the module.

Test every channel. Apply a known signal to the input with a calibrator. Disconnect the field device before measuring an output with a suitable test load. In 4–20 mA mode, a raw command of 0 produces 4 mA.

Trace interference before changing settings. If the reading jumps when a drive runs, check the signal cable routing, shield termination and cabinet grounding. Check EMC filters and their placement where relevant.

Record the settings before replacement. Save the channel modes, scaling, module order and any mechanical angle reference for the resolver. Verify angle and analogue values before reconnecting the actual load.

Related modules and PDF files

See DVP ES2 / EX2 modules for digital I/O, and DVP Slim analogue modules and DVP Slim temperature modules for Slim CPUs. Delta documentation also covers the six-channel RTD module DVP06PT-E2, positioning module DVP02PU-E2 and expansion cable kit DVPAEXT01-E2.

OtomasyonAVM PDF archive · Delta DVP PLC files · Delta PLC and HMI manuals. Chapters 3 and 4 of the DVP Module Manual cover analogue I/O and temperature. Chapters 5 and 6 cover positioning and cable expansion. For resolver details, use the dedicated DVP10RC-E2 manual.

Delta categories · Used Delta products · Delta PLC · DVP PLC series · DVP expansion modules

External references

Delta DVP Module Manual · ES2/EX2 programming manual · DVP10RC-E2 resolver manual · ES3/EX3 programming manual · Delta PLC/HMI Cable Selection Guide