Delta DVP04PT-E2
Delta DVP04PT-E2 — Four-Channel RTD Temperature Measurement Module
Delta DVP04PT-E2 adds four individually configurable RTD/resistance measurement channels to compatible DVP PLC systems. Among PLC input and output modules, it performs temperature measurement, converting sensor readings into signed 16-bit data. It is not a standalone CPU.
Supported resistance sensors are Pt100, Pt1000, Ni100 and Ni1000. Select the temperature sensor type together with its wiring arrangement. Pt100 and thermocouples require different input circuits; consider DVP04TC-E2 for J/K and other supported thermocouples.
Power, CPU compatibility and module numbering
Use an external 24 V DC supply; the permitted range is 20.4–28.8 V DC. The 2022 instruction sheet specifies maximum consumption of 1.5 W. Connect the DC supply to 24V/0V. An AC-powered host CPU does not permit applying AC to this module’s power or sensor terminals.
This is an E2 expansion module for the DVP-ES2/DVP-EX2 group; the 2023 DVP catalogue presents the expansion group under ES3/ES2/EX2. Check the exact PLC CPU, firmware and expansion budget. Special modules are numbered 0–7 from the CPU outward; the supported arrangement permits up to eight and consumes no digital X/Y points.
Sensor modes, ranges and resolution
CR#2–#5 select the CH1–CH4 input modes. Mode 0: Pt100, −180 to +800 °C; mode 1: Ni100, −80 to +170 °C; mode 2: Pt1000, −180 to +800 °C; mode 3: Ni1000, −80 to +170 °C; mode 4: 0–300 Ω; mode 5: 0–3000 Ω. Mode 5 requires firmware V1.11 or later. Mode −1/HFFFF disables a channel. DVP04PT-E2 does not support modes 6–9 for JPt100, Cu50, Cu100 or LG-Ni1000.
The Pt100 curve uses 100 Ω at 0 °C and 3850 ppm/°C; Pt1000 uses 1000 Ω at 0 °C. A matching resistance value alone is insufficient: the sensor curve must also match. Resistance mode returns ohms rather than temperature.
Celsius resolution is 0.1 °C; specified hardware steps are 0.18 °F and 0.1 Ω. The resolution obtained when converting an analog signal is different from overall measurement accuracy. The instruction sheet specifies ±0.3% of full scale at 25 °C ambient and ±0.6% over 0–55 °C ambient. Conversion takes 200 ms per channel. Averaging is configurable from 1 to 100 samples, default 10.
Three-wire and two-wire sensor connections
Each channel has On+, In+, In− and FE terminals, where n is the channel number. For a three-wire RTD, connect the two leads from the same sensor end to In+ and In−, and the opposite-end lead to On+. Comparable lead lengths and resistances are important for lead-resistance compensation.
For two-wire operation, bridge In+ and In− and connect the sensor between On+ and that common point. Lead resistance can add measurement error. Connect shielding to FE according to the manufacturer’s grounding diagram. Correct grounding, shield continuity and separation from power wiring help reduce electromagnetic interference. Do not apply external 24 V to sensor terminals.
Programming software and cable
Program an ES2/EX2 CPU using WPLSoft or an ISPSoft release supporting that CPU. During PLC programming, use TO for module settings and FROM for readings and status. For ES3 projects, select the software and instruction support from the ES3 CPU manual; the example below uses ES2/EX2 instruction syntax.
Use a DVPACAB2A30 PC-to-PLC cable for the ES2/EX2 CPU’s RS-232 programming port. A USB-only computer needs a suitable USB-to-RS-232 converter, its driver and the correct COM port. The cable connects to the CPU; the DVP04PT-E2 sensor terminals are not a programming port.
Control registers and four-channel reading example
CR#0 = H0082 identifies the model; CR#1 reports firmware. CR#7 selects units, with H0000 for °C. CR#8–#11 set averaging counts, CR#12–#15 contain averaged readings and CR#20–#23 contain present readings. In Celsius mode, analog input data is in tenths of a degree: 253 = 25.3 °C; −50 = −5.0 °C.
For a bench example with special module number 0, TO K0 K2 H0000 K1 selects Pt100 for CH1; configure CR#3, #4 and #5 separately for CH2–CH4. TO K0 K7 H0000 K1 selects Celsius. FROM K0 K12 D100 K4 reads four averages into D100–D103; FROM K0 K20 D110 K4 reads present values into D110–D113. Replace K0 with the actual module number and allocate free D-register storage.
CR#43 is the error bit field; read it with FROM K0 K43 D120 K1. Distinguish power, channel-conversion, input-mode and averaging errors. During PLC debugging, monitor status together with data. The 2026 manual states that a disabled DVP04PT-E2 channel returns 32767/H7FFF; do not interpret this as valid temperature.
Offset, retained settings, alarms and PID
CR#28–#31 contain channel offsets: measured value = raw value − offset. Verify the sensor and wiring before applying correction. Save retentive settings by writing H5678 to CR#41. Trigger this once after configuration changes rather than every scan, then verify retention by cycling power.
CR#100 enables limit detection; CR#101 reports status; CR#102–#105 set upper limits and CR#108–#111 lower limits. PID control registers occupy CR#120–#136 for CH1, with subsequent channels starting at intervals of 20 registers. For CH1, #120 is setpoint, #121 sampling time, #131 output percentage, #135 RUN/STOP and #136 auto-tuning.
When using PID for temperature control, apply the calculated command through the CPU and appropriate output hardware; this four-input module does not switch heater power directly. An HMI should show setpoint, measured temperature and sensor faults together. Preserve scaling, signed data and quality status when transferring readings to SCADA; configure the PLC-to-SCADA data relationship accordingly.
Editor’s Note
Test all four channels when buying a used module. Check the E2 label, expansion connector, terminals and CR#0 identity. Apply the same reference to every channel in turn and record the differences.
In Pt100 mode, a precision 100 Ω reference checks approximately 0 °C and 138.5 Ω checks approximately 100 °C. Account for reference tolerance. Use proper three-wire connections, or the required I+/I− bridge for a two-wire bench test. Disconnect power before changing connections.
For drifting readings, inspect Pt100/Pt1000 selection, mode settings, loose terminals and lead resistances first. If readings jump when a motor starts, investigate cable routing and shielding. Increasing averaging does not repair an intermittent connection.
Compare a lower and an upper reference point. A correct room-temperature reading does not establish accuracy across the range. Back up the program and settings before changing offsets, and verify startup after saving parameters.
Test sensor disconnection, channel disabling and module power loss in an isolated bench arrangement. Verify that invalid or stale temperatures cannot keep heating active. Before running PID auto-tuning on the process, establish output limits and independent overtemperature protection.
PDF manuals
Start with our Delta DVP PLC files page. Chapter 4 of DVP Series Module Manual, DVP-0399820-05, dated 6 January 2026, covers DVP04PT-E2/DVP06PT-E2 specifications, control registers, PID and wiring. The package also includes the English DVP catalogue dated 23 October 2023.
Related topics
DVP04TC-E2 measures thermocouples; DVP04AD-E2 handles general analog inputs; DVP04DA-E2 provides analog outputs; DVP06XA-E2 combines analog inputs and outputs. Check sensors, channels and wiring before considering any replacement.
DVP E2 modules | DVP expansion modules | Delta DVP PLC series | DVP04PT-E2 model page | DVP file archive
External references
Delta DVP module manual — 2026 English archive copy | Delta DVP catalogue — English archive copy | Delta 2022 DVP04PT/06PT-E2 instruction sheet | Delta programming cable explanation | Delta WPLSoft/ISPSoft explanation