Delta DVP10RC-E2

Delta DVP10RC-E2 Resolver Input Module

Delta DVP10RC-E2 is a single-channel, 12-bit resolver module for DVP-ES2 and DVP-EX2 systems. It transfers resolver angle information to the PLC and provides electronic cam, angle-dependent output and brake-control functions.

When monitoring a press shaft or rotary mechanism, identify the feedback interface first. The difference between a resolver and an encoder matters here: incremental encoder A/B pulses cannot be connected to the resolver input. Other encoder types, including absolute encoders, also require their electrical interfaces to be checked before connection.

Specifications and output arrangement

Resolver input: One channel; raw value 0–4095. Angle registers use 0–3599 in 0.1° units. Display units do not establish the overall mechanical accuracy. The manual specifies limits of 500 rpm and 50 m resolver cable distance.

Supply: External 24 VDC, permitted range 20.4–28.8 VDC; specified maximum module consumption 1 W. Calculate external load consumption separately when selecting the control-panel power supply.

Ten transistor outputs: Y0–Y1 provide comparison/high-speed output functions, Y2–Y7 general control and Y10–Y11 synchronous brake commands. The manufacturer's wiring drawing identifies the outputs as NPN. These are module terminal names, separate from normal CPU Y addresses. The module is numbered 0–7 in special-module order and does not consume ordinary digital X/Y addresses.

Resolver cable and field wiring

R1–R2 are the resolver excitation terminals, specified at 7 Vrms / 10 kHz. Connect the S1–S3 and S2–S4 signal pairs according to the manufacturer's diagram; the specified input is 3.5 ±0.175 Vrms / 10 kHz. Frequency, transformation ratio and winding specifications must match. These signals are different from a standard 0–10 V analog input.

Use a shielded resolver cable with the signal pairs preserved, routed away from motor and brake power wiring. Check shielding and grounding as part of the complete panel arrangement. The resolver lead and the PC's PLC programming cable serve different purposes; matching connector shapes do not establish compatibility.

Programming software, cable and driver

Create the CPU application with WPLSoft or ISPSoft supporting the actual ES2/EX2 CPU. ISPSoft uses a communication driver selected through COMMGR. Configure module registers through the CPU's FROM/TO instructions; DVP10RC-E2 is not selected as a separate CPU project. Record the module number, register and engineering units clearly in the ladder program.

CPU COM1 connection: For an ES2/EX2 CPU with RS-232, use the DVPACAB2A30 cable: 9-pin female D-Sub at the PC end, 8-pin mini-DIN at the PLC end, 3 m long. A PC without a serial port needs a suitable USB-to-RS-232 adapter and its driver. Select the COM number assigned by Windows in the software. A TTL-level USB serial lead is electrically different.

The module's D+ / D− / SG terminals are for RS-485 communication. Observe the differences between RS-232 and RS-485; the CPU programming cable does not connect to these terminals. The 2014 module manual specifies function 03 for RS-485 reading and the TO instruction for register writing. Match communication mode and station settings to the actual unit.

Reading angle, speed and revolutions

CR#3: status/error flags; CR#4: raw resolver value; CR#5: resolver angle; CR#6: offset-adjusted angle; CR#7: speed; CR#8: revolutions; CR#9: output states. In a 0.1° angle register, 900 represents 90.0°.

Read example: If this is special module number 0, FROM K0 K4 D100 K5 reads CR#4–CR#8 into D100–D104. D100 contains the raw value, D101 the resolver angle, D102 the adjusted angle, D103 speed and D104 revolutions. Change K0 when the module's position changes.

ES2 automatic mapping: With M1183 OFF, the first special module maps D9900 to angle, D9901 to speed, D9902 to revolutions and D9903 to output states. For example, MOV D9900 D200 copies the angle to D200. The second special module's group starts at D9910. Check the CPU mapping before using these registers as general application memory.

The documented revolution counter increases on complete forward turns; it does not automatically decrease during reverse rotation. This differs from a conventional high-speed counter assumption. Display angle, speed, revolutions and fault status separately on the HMI to make diagnosis easier.

Editor's Note

For a used module, the POWER LED alone is insufficient evidence of condition. Check smooth angle changes with a connected resolver, inspect error flags and verify the outputs under a suitable load. Bent expansion-connector pins can interrupt communication on an otherwise clean-looking unit.

Ask for the resolver nameplate as well. A servo motor using resolver feedback does not establish that its excitation and transformation ratio suit this module. Match winding terminals to documentation instead of guessing from cable colours.

Isolate power and disconnect the resolver from electronics before checking winding continuity and resistance against its own documentation. Do not apply a high-voltage insulation test with the module connected. Applying 24 V to R/S signal terminals is not a valid test.

Observe angle readings at fixed shaft positions, then during slow rotation. The mechanical reference position and the displayed angle can differ; check mounting direction, coupling and stored offset together. Back up existing settings before replacement.

An illuminated output LED does not prove that the load is powered. Check UP/ZP and the load return against this model's drawing. Verify the output current rating before connecting a contactor or brake coil; start with a suitable test load and an interface stage where required.

Because Y10/Y11 command a brake, keep mechanical movement controlled during testing. Two simultaneous outputs do not establish a safety certification or permission to drive a power brake directly. Verify angle acquisition first, cam ranges second and the actual braking response last.