Delta DVP04TC-E2
Delta DVP04TC-E2 — 4-Channel Thermocouple Temperature Input Module
Delta DVP04TC-E2 is a 4-channel thermocouple temperature input module for compatible DVP-E series PLC systems. It accepts J, K, R, S, T, E and N temperature sensors or −80 to +80 mV signals. It transfers measurements to the host CPU; it is not an independently programmed CPU or a heater power output.
Do not connect Pt100/RTD sensors directly to this module. The difference between Pt100 and thermocouples determines the correct module. For resistance temperature sensors, consider an appropriate RTD module such as DVP04PT-E2. E2, H2 and Slim modules do not share one universal expansion interface.
Sensor types and temperature ranges
Supported thermocouple types and rated ranges are J: −100 to +1150°C; K: −100 to +1350°C; R and S: 0 to +1750°C; T: −150 to +390°C; E: −150 to +980°C; N: −150 to +1280°C. Match each channel mode to its probe. Check thermocouple standards, sheath limits and cable temperature ratings separately; the module range does not establish the probe’s suitability for every environment.
Resolution, accuracy and conversion time
Data uses a signed 16-bit two’s-complement format. The Celsius scale is 0.1°C, so a value of 253 means 25.3°C when Celsius mode is selected. This increment is not measurement accuracy: the manual specifies ±0.3% of full scale at 25°C ambient and ±0.6% of full scale over 0–55°C ambient. The ±80 mV mode uses a 0.01 mV scale rather than the temperature scale.
Conversion time is 200 ms per channel; do not assume all four channels refresh within 200 ms. CR#8–CR#11 allow 1–100 samples for averaging each channel, with a default of 10. More averaging reduces fluctuations but slows response to changing temperatures. The manufacturer wiring section requires a 30-minute warm-up before temperature measurement.
Power supply, terminals and field cable
The external supply is 24 V DC, with an allowed range of 20.4–28.8 V DC. Connect the DC supply to 24V/0V and the thermocouple positive/negative conductors to the corresponding I1+/I1− through I4+/I4− terminals. The removable terminal block has a 5 mm pitch. Do not apply mains power, a 24 V digital signal or a 0–10 V transmitter output to these inputs.
Use thermocouple extension/compensation cable matched to the probe for the analog input. Maintain polarity and connect the shield/FE according to the manufacturer grounding diagram. Route the cable separately from drive, motor and heater power conductors to reduce electromagnetic interference. Avoid local thermal gradients around the terminals that could disturb cold-junction compensation.
Compatible CPUs and module addressing
DVP04TC-E2 belongs to the DVP-E expansion group for DVP-ES2/EX2 and DVP-ES3/EX3 block-type systems. Select it against the exact DVP-ES2 or DVP-ES3 CPU code, firmware, module count and power budget. Up to eight special modules are numbered 0–7 from the nearest to the CPU. They do not occupy digital X/Y points.
Read analog I/O data through control registers. The difference between analog and digital inputs means this is not the same as reading an X contact. Do not copy a DVP04TC-H2 or DVP04TC-S register map into an E2 application; sensor-mode and error-register locations differ.
Programming software and cable
DVP04TC-E2 does not receive a separate PLC program. Configure and read it from the host CPU’s PLC programming project. Use WPLSoft for ES2/EX2 systems, or ISPSoft where supported by the exact CPU/release. Standard ES3 CPUs require ISPSoft 3.08 or later; CPUs such as ES300TEC/EX3 require DIADesigner 1.30 or later. Use FROM/TO in the ladder program and configure COMMGR where required for the connection.
For USB access to an ES2/EX2 CPU’s 8-pin mini-DIN RS-232 port, use the UC-PRG020-12A programming cable. Alternatively, connect a UC-MS020-01A serial cable to the PC RS-232 port or a suitable USB-to-RS-232 converter. Check the USB cable/converter driver and assigned COM number. The programming cable connects to the CPU; thermocouple wiring connects to the module I+/I− terminals. Select ES3/EX3 connections according to that CPU’s supported ports and connection method.
Control registers and a reading example
CR#0: model ID H’0083; CR#1: firmware; CR#2–CR#5: CH1–CH4 sensor modes; CR#7: temperature unit; CR#8–CR#11: averaging sample counts; CR#12–CR#15: averaged measurements; CR#20–CR#23: present measurements; CR#43: error status. Each channel uses its own mode register: 0=J, 1=K, 2=R, 3=S, 4=T, 5=E, 6=N, 7=±80 mV; −1=channel disabled. The default sensor mode is J.
Check legacy wizard examples: some CR numbers in section 5.8.2 of the 2013 ES2 manual conflict with that document’s DVP04TC-E2 register table. For this model, use CR#2–CR#5 for sensor modes and CR#12–CR#15 for averaged readings.
With the sensor modes and Celsius unit already configured correctly, FROM K0 K12 D100 K4 reads the four averaged measurements into D100–D103 for special module number 0. Replace K0 with the actual module index. ES2 also provides module values in D9900–D9999; use the table for the exact CPU and module order. Avoid saving settings to EEPROM every scan; handle initialisation, measurement reading and error checks separately.
Communication and temperature control
The module communicates with the CPU through its side expansion connection; do not wire it as an independent RS-485 station or direct Modbus RTU terminal. To pass temperatures to an HMI/SCADA, use the CPU communication port and data addresses. The manual’s PID registers contain calculated control values; they do not establish physical heater power outputs on the module. SSR/contactor control requires appropriate external output hardware.
Editor’s Note
Check the E2 suffix on the label first. Do not order an H2 or Slim module merely because it looks similar. Identify whether the installed sensor is a thermocouple or Pt100 before removal; a software setting cannot turn one physical sensor type into another.
On a used module, inspect the complete terminal block, I+/I− contacts, side expansion connector and clips for corrosion or damage. A loose expansion connection can interrupt communication even when the supply is correct.
Allow a 30-minute warm-up before testing. Check every channel with a suitable thermocouple calibrator at two or more temperatures. A plausible room-temperature reading alone is insufficient. Record the actual sensor mode and temperature unit.
Do not expect zero degrees when shorting a thermocouple input: cold-junction compensation can produce a reading near terminal temperature. Check reversed polarity, incorrect compensation cable and leakage from the probe sheath. Observe measurements while power electronics are operating.
If ERR is active, do not hide the problem with arbitrary offset adjustments. Read CR#43, then check the 24 V supply, channel mode and sensor continuity. Move the same calibrator and cable to a healthy channel to separate field-wiring faults from module faults.
Provide independent overtemperature protection for a broken probe, stopped CPU or failed output device in heating machinery. Assess the emergency-stop and safety-relay arrangement against the machine risks; a temperature displayed on screen is not proof of a safe control chain.
PDF files
Use our Delta DVP PLC files page for documentation. The DVP04TC-E2 chapter in the DVP Series Module Manual covers specifications and registers; the DVP-ES2 Module Manual covers legacy ES2 applications; the cable guide covers CPU-to-PC connections. The 2009 DVP04TC-E2 sheet is an archive reference; compare its edition with the installed firmware.
Related topics and navigation
DVP04PT-E2 measures RTD sensors. DVP04AD-E2 provides general analog inputs, while DVP06XA-E2 combines analog inputs and outputs and DVP04DA-E2 provides four analog outputs; they are not direct thermocouple-module equivalents. Explore DVP E2 modules and DVP expansion modules for other system components.