Delta DVP02DA-E2
Delta DVP02DA-E2 — 2-Channel Analog Output Module
Delta DVP02DA-E2 adds two analog outputs to a compatible DVP PLC. Each channel can provide −10…+10 V, 0–20 mA or 4–20 mA. Hardware resolution is 14 bits; data exchange uses 16-bit words. The module converts digital commands into analog signals and has no analog measurement inputs.
See our Delta DVP PLC files page for wiring, channel settings and conversion curves. The manufacturer's combined sheet covers DVP02DA-E2 and DVP04DA-E2; the channel count and registers below refer to the two-output DVP02DA-E2.
Applications and CPU compatibility
The module can supply a speed reference to a variable frequency drive, a setpoint to an analog controller, or a reference to a servo system accepting analog commands. Match the receiver's 0–10 V / 4–20 mA selection to the channel mode. Do not issue negative voltage commands to a receiver accepting only 0–10 V.
Feedback from a pressure sensor or temperature sensor requires a separate, suitable input module. Consider DVP04AD-E2 for analog inputs, DVP04DA-E2 for four outputs, or DVP06XA-E2 for four inputs plus two outputs.
Within the DVP E2 module family, this module serves ES2/EX2 and supported ES3 configurations. Check the exact CPU model and hardware revision. The ES2 sheet numbers special modules 0–7, starting closest to the CPU; other special modules count towards the eight-module limit. The module does not occupy digital X/Y points.
Output ranges and raw commands
Mode 0 — −10…+10 V: K−32000 = −10 V; K−16000 = −5 V; K0 = 0 V; K16000 = +5 V; K32000 = +10 V. Use the K0–K32000 portion of this mode for a 0–10 V reference.
Mode 1 — 0–20 mA: K0 = 0 mA; K16000 = 10 mA; K32000 = 20 mA. Mode 2 — 4–20 mA: K0 = 4 mA; K16000 = 12 mA; K32000 = 20 mA. These examples assume the standard conversion curve; check existing channel and calibration settings first.
Data uses 16-bit two's complement. The specified response time is 400 µs per channel; this does not specify a 400 µs update for the entire PLC application or communication link.
Current-output load must be within 0–500 Ω. For voltage output, the sheet specifies a 1 kΩ–2 MΩ load and separately a 5 mA maximum output current. Calculating 10 V / 5 mA gives 2 kΩ minimum to remain within that current limit at the full 10 V level. This minimum is calculated from the stated current limit.
Power, terminals and isolation
An external 24 V DC supply is required, with an allowable range of 20.4–28.8 V DC and maximum consumption of 1.5 W. Include other system loads separately when selecting a power supply or DIN rail supply, and provide suitable fuse protection.
CH1 voltage: VO1–AG; CH1 current: IO1–AG. CH2 voltage: VO2–AG; CH2 current: IO2–AG. Match the terminals to the selected channel mode. Terminal order is 1:24V, 2:0V, 3:ground, 4–6:FE, 7:VO1, 8:IO1, 9:AG, 10:VO2, 11:IO2, 12:AG. Do not apply an analog input module's V+–I+ bridge to these outputs.
AG is analog common; FE serves shielding/functional earth. The analog and digital circuits are isolated, but the analog channels are not isolated from one another. Route analog cables away from contactor and relay power wiring; consider shields and grounding together with the control panel layout. These signal outputs must not directly power motors or coils.
Programming software and cable
DVP02DA-E2 does not receive a standalone PLC application. Its parameters are managed through the host CPU program. For ES2/EX2, use WPLSoft or ISPSoft. For ISPSoft, configure the appropriate driver and communication settings for the CPU port in COMMGR.
A suitable ES2/EX2 RS232 programming port can use the DVPACAB2A30 cable. If the PC has no serial port, use a suitable USB-to-RS232 converter, its driver and the correct COM port. The PLC programming cable connects to the CPU; check the pinout and port type when selecting Delta PLC cables.
For a supported ES3 installation, select software and cable by CPU model. Check ISPSoft/DIADesigner support for standard ES3 CPUs; models such as ES300TEC require DIADesigner. WPLSoft is not supported for ES3. When using the CPU's USB port, select the appropriate data cable and USB driver.
Control registers and ES2 addressing example
CR#0 = H0041 identifies the model; CR#1 reports firmware. CR#2 selects CH1 mode and CR#3 selects CH2 mode: 0 = ±10 V, 1 = 0–20 mA, 2 = 4–20 mA. CR#16 and CR#17 hold the two output commands. CR#18–CR#19 are reserved on DVP02DA-E2; it has no third or fourth output.
For module K0, FROM K0 K0 D90 K1 reads the model code. TO K0 K16 D100 K2 writes D100 and D101 to CH1 and CH2. Configure both channel modes first; these lines alone are not a complete commissioning program.
On DVP-ES2, module 0 maps D9900 = CH1 and D9901 = CH2; module 1 uses D9910/D9911. For example, MOV D100 D9900 writes the CH1 output command. Do not copy DVP06XA-E2's D9904/D9905 output addresses to this model. Verify the address map separately for another CPU family.
CR#28/29 adjust offset; CR#34/35 adjust gain. Mode 2 does not allow offset/gain adjustment; changing mode restores the default calibration settings. CR#43 reports errors and can be read with FROM K0 K43 D120 K1. Write H5678 to CR#41 to save eligible parameters; do not repeat this every scan. Output commands and retained configuration parameters have different retention behaviour.
Commands can be managed through an HMI panel or SCADA system. Modbus ASCII or Modbus RTU communication runs through the CPU; this module has no standalone RS485 port. Our Modbus communication guide explains the distinction between CR numbers, D addresses and protocol addresses.
Editor's Note
Check the DVP02DA-E2 label first. The four-channel drawing in the combined sheet belongs to the other model; this unit has two outputs.
For a used module, inspect the terminals, side connector, burn marks and POWER/ERROR indicators under a 24 V supply. An illuminated power LED does not prove that both analog channels work.
Disconnect the actuator for initial testing. Check 0, 5 and 10 V, then 4, 12 and 20 mA, on both channels using suitable loads and instruments. Record existing settings before changing calibration.
If voltage is correct unloaded but drops under load, check the receiver's input impedance first. For current output, check total load, cable resistance and IO/VO terminal selection before recalibrating.
K0 still produces 4 mA in 4–20 mA mode. Test output behaviour during CPU STOP, power restoration and communication loss with the installed CPU/module settings.
If one channel affects the other, investigate AG common wiring and shielding. Back up CR#43 status and the existing parameters; save deliberately and verify retention after a power cycle.
Related topics and files
Delta DVP PLC series · DVP expansion modules · DVP04DA-E2 · DVP06XA-E2 · Delta DVP PLC manuals and PDF files.
External references
Delta DVP02DA-E2/DVP04DA-E2 manufacturer sheet, 2021 edition, distributor archive · Delta DVP module manual · ES3 family programming manual.