Delta UB-10-OR16A / DVPAETB-OR16A
Delta UB-10-OR16A / DVPAETB-OR16A — 16-Relay External Terminal
Delta UB-10-OR16A / DVPAETB-OR16A is an external interface that provides 16 relay contacts driven by compatible PLC transistor outputs. Delta documents list these as alternative names for the same terminal. This external terminal uses existing output channels; it does not add 16 independently addressed outputs to the PLC.
The NPN-driven OR16A is used with DVP, AS and AH PLC systems through documented host and cable combinations. Its relay contacts provide an interface to field loads. Selection must account for load current, total common current and switching frequency together.
Electrical specifications and common current
Supply: 24 V DC auxiliary power at +24V and GND. Outputs: 16 relays. Current: 2 A per point, 5 A per common. Contact voltage: below 250 V AC or below 30 V DC. Response: approximately 10 ms.
Four loads drawing 2 A each on one common would total 8 A and exceed the 5 A/COM limit. Inductive loads require a separate contact-life assessment. Mechanical relays are unsuitable for fast pulses, PWM or motion pulse outputs. The auxiliary 24 V supply and the field voltage switched by the contacts must be considered separately.
Compatible devices and cables
DVP/AH: Manufacturer combinations include DVP32SN11TN, AH32AN02T-5C and AH64AN02T-5C. The UC-ET010-24C is a 1 m IDC 40-pin → 2 × 20-pin cable. AH documentation also lists it as DVPACAB7B10. Select DVP / AH I/O cables against the complete host model code.
AS: AS332T-A, AS32AN02T-A and AS64AN02T-A are listed OR16A combinations. AS wiring shows UC-ET010-24D (1 m), UC-ET020-24D (2 m) and UC-ET030-24D (3 m). In the illustrated OR16A connection, use branch #1. A matching connector alone does not establish cable or branch compatibility.
DVP and AS terminal markings
The board carries DVP markings. Use the manufacturer’s conversion table or AS label for AS wiring. The table shows terminal correspondence; confirm actual project addresses against module placement and hardware configuration.
| Common | DVP markings on board | AS equivalent |
|---|---|---|
| C0 | Y0, Y1, Y2, Y3 | Y0.0, Y0.1, Y0.2, Y0.3 |
| C1 | Y4, Y5, Y6, Y7 | Y0.4, Y0.5, Y0.6, Y0.7 |
| C2 | Y10, Y11, Y12, Y13 | Y0.8, Y0.9, Y0.10, Y0.11 |
| C3 | Y14, Y15, Y16, Y17 | Y0.12, Y0.13, Y0.14, Y0.15 |
Differences from related terminals
UB-10-OR16B / DVPAETB-OR16B is a separate variant for PNP output combinations and is not a direct OR16A substitute. UB-10-OT32A / DVPAETB-OT32A provides 32 transistor outputs. UB-10-ID32A / DVPAETB-ID32A is a 32-input terminal. Similar appearance or channel count does not make these products interchangeable.
Editor’s Note
A relay click is only the start of a useful check. Worn contacts may pass a no-load continuity test; use a controlled test load and check contact voltage drop and heating as well.
If a whole group fails, check its common connection before blaming four relays. With power isolated, inspect terminal tightness and cable continuity. Measure the auxiliary supply between +24V and GND.
On used units, inspect beneath the terminals, around relay solder joints and at connector latches. Burn marks, loose common connections or damaged tracks can remain after a relay has been replaced.
In an AS cabinet, do not infer the program address from a Y10 board marking. Establish the terminal correspondence and project output assignment first; an address mistake can make a healthy board appear faulty.
For relay replacement, compare coil voltage, contact arrangement, load rating and insulation as well as dimensions and pin spacing. Disconnect field loads before working on the board.
When driving a contactor or valve coil, check that suppression suits the load voltage. Disconnect the load and test channels individually with current limiting; bridging contacts can hide the original fault.
PDF, software and related topics
Find installation documents and software links on the Delta PLC accessories PDF and software files page. Select programming and communication software for the PLC CPU in use.
Delta AH I/O cables · Delta AH external terminals · Delta AS expansion modules · Delta DVP power supplies · Delta AS power supplies · Delta AH power supplies
Navigation: UB-10-OR16A / DVPAETB-OR16A main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta UB-10 installation sheet — DVP-0999830-01 · Delta AS Module Manual — 2-39 · Delta AS Hardware and Operation Manual — 1-14 · Delta AH Motion Controller Hardware Manual — 2-9