Delta DVP / AH I/O cables
Delta DVP / AH I/O Cables
Delta DVP / AH I/O cables connect the multipin interface of a suitable PLC input/output module to an external terminal module, helping organise field wiring inside the control cabinet. The UC-ET…-24A, -24B, -24C and -24D options differ in connector arrangement, length and shielding. Selection requires the complete I/O module code, cable code and external terminal code to be checked together.
These cables carry I/O signals to external terminals. For other connection duties, see DVP programming cables, DVP communication cables and industrial network cables. A cable appearing among both DVP and AH accessories does not establish compatibility with every module in either series.
40-pin to 40-pin connections: A and B options
UC-ET010-24A is the standard 1 m MIL IDC40–IDC40 option. UC-ET010-24B provides the same connector arrangement with shielding at 1 m. The shielded B group also includes UC-ET020-24B at 2 m and UC-ET030-24B at 3 m.
40-pin to two 20-pin connections: C and D options
UC-ET010-24C is the standard 1 m MIL IDC40–IDC20 × 2 option. UC-ET010-24D has this connector arrangement with shielding at 1 m. UC-ET020-24D at 2 m and UC-ET030-24D at 3 m are the longer shielded options.
The two terminal ends in the C/D group separate channel groups according to the wiring diagram; they should not be treated as a Y lead that duplicates each signal. Likewise, 40 pins do not mean 40 I/O channels: common and supply connections also form part of the pin assignment.
Matching DVP and AH modules
Delta's cable selection guide shows the A/B group with the UB-10-ID32A terminal for the DVP32SM11N input module. For the DVP32SN11TN output module, the 40-pin terminal arrangement and the arrangement split between two 20-pin relay terminals are separate options. Similar connector housings alone do not make input and output terminals interchangeable.
For AH modules, AH32AM10N-5C is shown with the A/B group and UB-10-ID32A. For the AH32AN02T-5C output module, A/B cables connect to UB-10-OT32A, while C/D cables connect to UB-10-OR16A relay terminals. The relay terminal selection changes to UB-10-OR16B for the PNP output AH32AN02P-5C.
The module suffix matters. For example, AH32AM10N-5C uses MIL connections, whereas AH32AM10N-5B uses DB37, requiring a different cable selection. With a 64-point module, check the channel group at each connector and the required number of cables and terminals separately. Related information is available under AH digital modules, AH external terminals and AH I/O cables.
Cable selection and cabinet installation
Verify pin 1 orientation, connector keying, latches and the pin assignment at both ends. A passive cable does not convert NPN to PNP or turn a transistor output into a relay output. Where relay outputs are required, the appropriate external terminal module provides that function. Use the module and terminal manuals to establish permitted load and common-terminal currents.
Select a length that allows routing without tension or strain on the connector. For shielded B/D cables, follow the manufacturer's EMC and earthing arrangement; shielding does not make routing alongside motor or drive power cables acceptable. Do not place a cabinet cable in a moving cable carrier unless its suitability for that duty is documented.
Editor's Note
When buying a cable, look beyond the label in the middle. Ask for photographs of both ends and check 40-to-40 versus 40-to-two-20, latch condition and bent contacts. A different final letter can mean a different terminal connection.
Before troubleshooting, safely isolate the PLC, field supplies and connected loads. Disconnect both cable ends before checking continuity and shorts against the wiring diagram. Do not apply an insulation tester while PLC electronics or terminal modules remain connected.
Label the channel groups before removing two 20-pin ends. Swapped groups can leave the wiring looking tidy while operating the wrong machine output. A deliberate channel-by-channel check saves a great deal of fault-finding later.
An illuminated PLC output LED does not prove the cable is sound. With machine movement prevented, compare the module and terminal ends using a suitable test load. An open common, loose connector or damaged conductor can produce similar symptoms.
Pull on the connector housing when disconnecting, rather than the cable bundle. Replace crushed, overheated or broken-latch cables. For intermittent faults, comparison with a known-good cable of the correct code often gives a quick answer.
When assembling a used set, photograph the PLC module, terminal and cable codes together. A seller's general compatibility claim is insufficient; keep the three matching codes and the correct pin diagram with the cabinet documentation.
PDF manuals, wiring diagrams and software
Use our Delta PLC accessories PDF and software files page for supporting documents. Check the “Extension Cables for I/O Modules” chapter of the Delta PLC/HMI Cable Selection Guide together with the connected terminal's wiring diagram. General documents are available under Delta PLC and HMI manuals. These passive I/O cables do not require their own software or USB driver.
Related subjects
UC-ET010-24A · UC-ET010-24B · UC-ET010-24C · UC-ET010-24D · UC-ET020-24B · UC-ET020-24D · UC-ET030-24B · UC-ET030-24D
DVP32SM11N input module · DVP32SN11TN output module · AH32AM10N-5C · AH32AN02T-5C · UB-10-ID32A · UB-10-OT32A · UB-10-OR16A · AH external terminals
Navigation: Delta PLC accessories · Delta DVP PLC series · Delta AH PLC series · Delta PLC models · Used Delta products · PDF and software files
External references
Delta DVP/TP catalogue – accessory ordering table · Delta AH catalogue – module and terminal selection · Delta PLC/HMI Cable Selection Guide – archived manufacturer document · Delta UB-10 external terminal instruction sheet