Delta UC-ET010-24A

Delta UC-ET010-24A 1-Metre Flat I/O Terminal Cable

Delta UC-ET010-24A is a 1-metre unshielded flat cable connecting compatible PLC I/O modules to external terminal boards. It has a MIL IDC40, 40-pin connection at each end and belongs to the Delta DVP / AH I/O cable group.

The cable carries I/O signals from the module to an external terminal board inside the cabinet. Plan the distance, connector orientation and maintenance slack together.

Module and terminal compatibility

The manufacturer's DVP combinations are DVP32SM11N ↔ UB-10-ID32A / DVPAETB-ID32A for inputs and DVP32SN11TN ↔ UB-10-OT32A / DVPAETB-OT32A for outputs.

The cable selection guide also lists the relevant IDC40 connections of AH32AN02P-5C and AH64AN02T-5C to UB-10-OT32A. Verify the complete module code and the particular connector being used.

When selecting terminals for the Delta DVP PLC series, follow the module diagram for channel functions, commons and field supplies. A 40-pin connector does not represent 40 independent I/O channels.

Flat cable routing and connection checks

Check the pin 1 mark, connector key and locks before connecting. Establish whether the drawing shows the contact face or cable side. Check socket and board markings together rather than relying solely on a coloured cable edge.

Keep the flat cable clear of cabinet doors, sharp sheet-metal edges and wiring-duct lids. Route it separately from motor and drive power wiring, avoiding hard folds immediately behind the IDC connectors.

Disconnect the PLC and external I/O supplies before installation or removal. Release the appropriate locks and hold the connector body when unplugging.

Similar models and selection differences

Shielded IDC40-to-IDC40 options: UC-ET010-24B is 1 metre, UC-ET020-24B is 2 metres, and UC-ET030-24B is 3 metres. Assess shielding requirements as well as length when replacing a cable.

UC-ET010-24C is a 1-metre unshielded IDC40-to-two-IDC20 cable. UC-ET010-24D, UC-ET020-24D and UC-ET030-24D provide the same branching arrangement in shielded 1, 2 and 3-metre versions.

When changing an arrangement using UB-10-OR16A / DVPAETB-OR16A, check the number of terminal-side connectors. Specify the complete UC-ET010-24A code and the equipment codes at both ends when ordering.

Editor's Note

Inspect folds in the flat cable carefully. Conductors can break inside an apparently intact ribbon. Pay particular attention to hard bends near connectors, crushed sections and areas covered with repair tape.

Inspect both contact rows before connecting. Look for bent pins, recessed contacts and damaged locks. A plug seated on only one side can produce intermittent channel faults.

Disconnect both ends before measuring. Check continuity and shorts between neighbouring conductors against the manufacturer's drawing. Gently flex the cable during measurement and investigate any changing reading.

Check commons when a whole channel group disappears. Terminal power, a shared connection or an incompletely seated connector may be responsible. Complete these physical checks before changing the PLC program.

Check routing if faults begin when a drive runs. Separate the cable from power wiring and repeat the test under the same conditions. If a shielded cable is needed, verify the module-to-terminal combination and follow the manufacturer's shield connection instructions.

Commission one channel at a time. Secure the machine, use an appropriate input test signal and account for load movement before testing outputs. Finish by labelling both ends with their module and terminal identities.

PDF diagrams and software files

Use our Delta PLC accessories PDF and software files page for documentation. Consult Chapter 2 and Figure 1A in Section 2.5 of the Delta PLC/HMI Cable Selection Guide, together with the accessory table on printed page 46 of the DVP/TP catalogue.

Related subjects

For other options, see Delta PLC accessories, DVP / AH I/O cables, external terminals and used Delta PLC models.

Navigation: Used Delta products | Delta PLC models | PLC accessories | I/O cables | PDF and software files

External references

Delta PLC/HMI Cable Selection Guide, manufacturer document | Delta DVP/TP catalogue, 2024