Delta UC-ET010-24D
Delta UC-ET010-24D Shielded I/O Terminal Cable
Delta UC-ET010-24D is a 1-metre shielded cable connecting a PLC I/O module to external terminal units. It has one MIL IDC40 connector and two separate IDC20 connectors. It belongs to Delta DVP / AH I/O cables and Delta PLC accessories. Select it by terminal arrangement and the complete module code as well as length.
DVP module and relay terminal pairing
The manufacturer's catalogue lists it for DVP32SN11TN with UB-10-OR16A. The cable guide shows the 40-pin module connector feeding two 16-channel relay terminal units. The cable carries output signals; relay contacts and field-load connections are provided by the external terminal units.
Consult Delta DVP Slim digital modules, Delta DVP expansion modules and Delta external terminals when selecting the assembly. Match the Delta DVP PLC project's output addresses to the channel groups on both terminals.
Routing the 1-metre cable and identifying branches
The manufacturer identifies UC-ET010-24D under Figure 4B as a shielded IDC40-to-two-IDC20 cable. Record which terminal group each IDC20 branch serves before removal. Interchanging identical connector types can redirect outputs to different field channels.
Allow for the cable-duct route, bends and connector access when checking whether one metre is sufficient. Avoid a layout that strains the plugs. Connect the shield according to the applicable equipment and cabinet wiring design.
UC-ET010-24A, 24B and 24C differences
UC-ET010-24C has the same 1-metre IDC40-to-two-IDC20 arrangement but is not identified as shielded in the catalogue. UC-ET010-24D is the shielded option. Connector count alone does not establish the shielding arrangement.
UC-ET010-24A and UC-ET010-24B use IDC40-to-IDC40 connections; 24B is listed as shielded. That group serves different terminal arrangements involving UB-10-OT32A and UB-10-ID32A. Do not choose 24A or 24B solely because its length matches a project requiring two IDC20 branches.
For a longer shielded connection with two branches, consider UC-ET020-24D at 2 metres or UC-ET030-24D at 3 metres. Confirm module-to-terminal compatibility and channel mapping before selecting length.
Terminal selection for AH modules
The guide lists UC-ET010-24D for AH32AN02T-5C → UB-10-OR16A and AH32AN02P-5C → UB-10-OR16B. Although the cable code is shared, select the terminal for the module's output arrangement. See Delta AH external terminals for related options.
No software or driver is installed in UC-ET010-24D. Commissioning checks concern pin orientation, channel mapping, common connections, terminal power and field loads. The cable does not create additional I/O points in the PLC program.
Editor's Note
These four variants are all one metre long, but their connectors and shielding differ. Order by the complete UC-ET010-24D code and record the module and both terminal models.
Label both branches and terminal groups before removing the old cable. After fitting the replacement, check channels individually to confirm that each reaches the intended relay.
Disconnect every end from the equipment before continuity testing. Follow pin 1 orientation and the manufacturer's diagram. Inspect IDC housings for broken latches, bent contacts and cable-entry damage.
If one relay group does not operate, check its terminal supply and 20-pin plug first. A working branch does not establish that the other branch's conductors and common connections are healthy.
If one metre is insufficient for the route, select a suitable length rather than straining the plugs. Keep the cable away from motor power wiring. If a relay operates but the load does not, inspect the contacts and load circuit separately.
PDF and wiring documentation
Use Delta PLC accessories files for manufacturer cable drawings and Delta PLC and HMI manuals for module and terminal connections. The guide shows the DVP arrangement on printed pages 2-2 and 2-17, and Figure 4B on page 2-32.
Related topics
Delta UC-ET010-24C · Delta UC-ET010-24B · Delta UC-ET010-24A · Delta UC-ET020-24D · Delta UC-ET030-24D
Return to Delta DVP / AH I/O cables. Browse controllers in the Delta PLC category and available devices under second-hand Delta products.