Delta UB-10-OR16B / DVPAETB-OR16B

Delta UB-10-OR16B / DVPAETB-OR16B

Delta UB-10-OR16B / DVPAETB-OR16B is a 24 V DC-powered external terminal board with 16 relay outputs. It interfaces compatible PNP/source module outputs to field loads through relay contacts. It completes the connection and switching interface for existing outputs rather than adding independently addressable PLC channels.

P-type modules and board quantity

The manufacturer shows OR16B connections for Delta AH32AN02P-5C and Delta AH64AN02P-5C. Converting every output to a relay interface requires two OR16B boards and one branching cable for 32 outputs, or four OR16B boards and two branching cables for 64 outputs.

Preserve the module's P and -5C suffixes. Assess the board, cable and output groups together under Delta AH digital modules and Delta AH expansion modules. The control-side PNP signal and field-side relay contact perform different functions.

20-pin connection and suitable cables

The board uses a 20-pin MIL/IDC control connection. UC-ET010-24C is a 1-metre ribbon option; shielded options are UC-ET010-24D at 1 metre, UC-ET020-24D at 2 metres and UC-ET030-24D at 3 metres. The module-side IDC40 connector branches into two IDC20 ends.

Delta DVPACAB7B10 is shown in the same branching connection group in manufacturer documentation. Each branch connects one 16-output terminal board. Review cables under Delta AH I/O cables and label which output group each branch serves.

Contact current and common-terminal limit

The DVPAETB instruction sheet specifies 2 A per output and 5 A per COM, with contact voltage below 250 V AC and below 30 V DC. Assess simultaneous outputs in each group against its common-terminal limit. Loading all four channels at 2 A simultaneously exceeds the 5 A group limit.

Do not interpret these ratings as equal switching life for every load type. Assess inductive loads and starting current separately. The manufacturer requires external protection for relay loads; choose a suitable diode for DC coils or surge suppression for AC loads according to the load and electrical design.

C0–C3 groups and board power

Each of the C0, C1, C2 and C3 common terminals serves four outputs. +24V and GND are auxiliary board-power terminals and perform a different function from load commons. Assess power together with Delta AH power supplies and the machine's field wiring.

Compare the board's Y labels with addresses in the PLC project. Read addressing according to the connected module and cable group. Follow the existing electrical drawings when arranging common-terminal bridges or different load supplies.

Differences from OR16A, OR32B and transistor terminals

UB-10-OR16A / DVPAETB-OR16A has different control-output combinations; do not exchange A/B suffixes based on appearance alone. UB-10-OR32B / DVPAETB-OR32B belongs to the 32-relay DB37 group. UB-10-OT32A / DVPAETB-OT32A and UB-10-OT32B / DVPAETB-OT32B belong to the transistor-output connection group.

The manufacturer drawing gives 113 × 87 × 55.3 mm for OR16B. Check DIN-rail retention, terminal access and cable-turning space during installation. Do not treat mechanical relay contacts as high-speed transistor outputs.

PDF and connection documentation

Start document selection at Delta PLC accessories files. In the 2019 PLC/HMI Cable Selection Guide, printed pages 2-6 and 2-8 / PDF pages 105 and 107 show board quantities, and Figure 11, printed page 2-37 / PDF page 136 shows terminal arrangement. For contact limits, match the DVPAETB-ID32A/OR16A/OR16B/OT32A instruction sheet to the board label and revision.

Editor's Note

Do not overlook the A/B suffix. Photograph the module's P/T code, complete board name and connected cable together. Similar housings do not establish the same control-side requirements.

A lit LED or relay click does not prove healthy contacts. Before contact measurements, disconnect all board and load supplies and verify absence of voltage. Then test the correct common-to-output pair under controlled conditions.

Investigate the load when contacts repeatedly weld. Coil current, starting current and missing surge suppression can damage the replacement relay too. Address the cause alongside the failed component.

Do not select a replacement relay by housing shape alone. Compare coil voltage, contact capacity and pin arrangement. Inspect burnt terminals, damaged copper tracks and loose common connections as well.

Complete testing by common-terminal group. Test individual outputs and simultaneous loads, observing COM current and heating. Confirm that the load releases when its control command is removed, and record the result.

Related topics

Browse parent groups under Delta AH external terminals and Delta PLC accessories, and device documentation under Delta PLC and HMI manuals.