Delta UC-ET020-24D — 2 m Shielded IDC40 / 2 × IDC20 I/O Cable

Delta UC-ET020-24D is a 2-metre shielded I/O cable connecting a PLC or I/O module’s 40-pin IDC/MIL interface to two 20-pin terminal connections. It routes existing input/output signals to external terminal modules. It belongs to the Delta DVP / AH I/O cables range and is also documented for suitable AS applications.

Main construction

Item Description
ModelUC-ET020-24D
Nominal length2 m
Main connectorIDC40 / 40 pins
Branch connectors2 × IDC20 / two 20-pin connectors
Cable constructionShielded, two-branch I/O connection
Conductor specification28 AWG in AS wiring diagrams

DVP and AS applications

The cable selection guide lists IDC40 → 2 × IDC20 and UC-ET020-24D for connecting DVP32SN11TN to UB-10-OR16A / DVPAETB-OR16A external relay terminal modules. The branches route the respective output groups to the terminal side.

The AS hardware manual shows AS332T-A, AS332P-A and AS324MT-A connections with the UB-10-ID16A terminal module. In Delta AS PLC applications, the cable branches can serve separate input and output groups. Read branch functions and pin assignments from the exact CPU’s wiring table.

For DVP and AH installations, assess the exact module, output type and external terminal board together. A 40-pin connector does not establish a common signal assignment across every module.

Branch numbers, common terminals and channel mapping

AS wiring drawings identify #1 / #2 as separate groups. In some CPU arrangements #1 serves outputs and #2 serves inputs; an output-only module can use both branches for output groups. Check X/Y addresses, C0, S/S and supply references against the actual equipment.

The AS module manual states that the markings printed on UB-10-OR16A are for DVP applications and that the AS table or label must be used for AS wiring. Compare the correct model diagram before equating terminal-board markings with PLC addresses.

Differences from related UC-ET models

Model Length Connection
UC-ET010-24D1 mShielded IDC40 → 2 × IDC20
UC-ET020-24D2 mShielded IDC40 → 2 × IDC20
UC-ET030-24D3 mShielded IDC40 → 2 × IDC20
UC-ET020-24B2 mShielded IDC40 → IDC40

UC-ET010-24B and UC-ET030-24B also provide IDC40 → IDC40 connections. The selection guide shows UC-ET010-24A as 1 m IDC40 → IDC40 and UC-ET010-24C as 1 m IDC40 → 2 × IDC20. Check the suffix as carefully as length: one 40-pin connector and two 20-pin connectors represent different arrangements.

Compare the cable arrangement specified for 40-pin terminal boards such as UB-10-OT32A / DVPAETB-OT32A with the two-branch 24D arrangement. Select the cable and terminal module together.

Installation and load assessment

Seat connector locks fully and arrange the cable so that the branching point carries no pulling force. Apply shield connections according to the PLC/module manual. Routing away from motor and drive power cables helps maintain signal integrity.

The 28 AWG specification alone does not determine allowable load current. Check the PLC output, common group, cable and terminal-module limits together. Do not treat the relay board’s contact rating as the current that the thin PLC-side conductors can directly carry.

Editor’s Note

Read the exact PLC or module code, then the terminal-board code. Connector appearance alone is insufficient. Label both branches before removal so that input and output groups are not exchanged during reconnection.

With power off and the cable disconnected at both ends, check continuity and unintended shorts between adjacent pins against the model diagram. Verify how the 40 contacts are distributed before assuming straight-through wiring throughout.

If a fault affects one branch, inspect that connector and the branching point separately. Gently moving the cable near its connector during measurement can reveal an intermittent break. Do not leave a broken latch or loose contact in service.

If an output LED operates but the field device does not, check the common terminal, field supply, terminal board and actual load in sequence. Use a suitable test load in an arrangement that cannot cause unexpected movement.

When moving a terminal board between AS and DVP installations, compare the printed address markings separately. Incorrect labels can make healthy hardware appear faulty. Keep a cable and channel-mapping record in the cabinet.

For used cables, inspect the shield, outer jacket, IDC housings and signs of pulling. Follow continuity checks with channel-by-channel tests using a suitable module. Switch off power and photograph the existing wiring before removal or reconnection on a working machine.

PDF and related topics

Use the Delta PLC accessories PDF and software files page for cable selection and wiring documents. Further sources are available under Delta PLC and HMI manuals and Delta user manuals.