Delta UC-ET020-24B 2-Metre Shielded I/O Connection Cable
Delta UC-ET020-24B is a 2-metre shielded MIL IDC40-to-IDC40 cable connecting compatible PLC I/O modules to external terminal modules. It belongs to the Delta DVP / AH I/O cable group and has a 40-pin IDC connection at each end.
It carries the module's I/O connections to an external terminal module inside the cabinet. Plan the cable route, connector clearance and maintenance access together.
Compatible module and terminal combinations
Input connection: DVP32SM11N to UB-10-ID32A / DVPAETB-ID32A. Output connection: DVP32SN11TN to UB-10-OT32A / DVPAETB-OT32A.
Delta's selection guide also shows the relevant 40-pin connections of AH32AN02P-5C and AH64AN02T-5C to UB-10-OT32A. Select by the complete module code and the particular connector being used.
When selecting within the DVP PLC series, check the module's input/output type and the terminal board's function. A connector fitting mechanically does not establish that signal and common connections match.
Connector orientation and cabinet wiring
Before connecting, inspect the pin 1 mark, connector key and locking parts. Read channel, common and supply assignments from the module's own diagram. Do not adapt the cable to another board based on pin count alone.
Arrange shield connections according to the equipment's installation and grounding instructions. Route the I/O cable separately from motor and drive power wiring, avoiding sharp bends that strain the connector entries.
Disconnect the PLC supply and external I/O supplies before installation or replacement. Before restarting, check terminal wiring and ensure that the machine cannot make an unexpected movement.
Similar cables and selection differences
The same shielded 40-to-40-pin family includes UC-ET010-24B at 1 metre and UC-ET030-24B at 3 metres. Choose the length that suits the route.
UC-ET010-24A is 1 metre, unshielded, 40-to-40-pin; UC-ET010-24C is 1 metre, unshielded, 40-pin to two 20-pin connectors.
UC-ET010-24D, UC-ET020-24D and UC-ET030-24D are shielded 40-pin to two 20-pin cables, 1, 2 and 3 metres respectively. Check this distinction particularly when the wiring plan includes UB-10-OR16A / DVPAETB-OR16A.
When ordering, specify the complete UC-ET020-24B code, module codes at both ends and required length. If using an existing cable as a reference, include photographs of the connector interiors as well as its label.
Editor's Note
Inspect both ends first. A used cable may have broken locks, bent contacts or a replacement connector. Even with the correct label, inspect the plugs and look for crushed sections near the cable entries.
Check shared connections when an entire channel group fails. Verify connector seating, terminal power and the commons shown in the module diagram. Several signals disappearing together is a useful diagnostic clue.
Disconnect both ends before continuity measurements. Match the connector viewing direction in the manufacturer's drawing, then check continuity and shorts between adjacent contacts. Do not perform insulation-resistance testing through a cable connected to the PLC.
Investigate intermittent faults near the plugs. Gently flex the disconnected cable during measurement. An interrupted reading suggests a broken conductor or IDC contact problem. Do not force a connector into place.
Begin functional checks with one channel. Secure machine movements, apply a suitable input test signal and verify its PLC indication. For outputs, establish what the actual load will do before issuing a command.
Leave sensible maintenance slack. Avoid stretching the cable, using connectors to support its weight or trapping it against power wiring. Label both ends with their module and terminal identities to simplify later fault finding.
PDF diagrams and software files
Use our Delta PLC accessories PDF and software files page for documentation. Consult Chapter 2 and Figure 1B in Section 2.5 of the Delta PLC/HMI Cable Selection Guide, together with the accessory table on printed page 46 of the DVP/TP catalogue.
Related subjects
For other options, see Delta PLC accessories, DVP / AH I/O cables, external terminals and used Delta PLC models.
Navigation: Used Delta products | Delta PLC models | PLC accessories | I/O cables | PDF and software files
External references
Delta PLC/HMI Cable Selection Guide, manufacturer document | Delta DVP/TP catalogue, 2024