Delta UB-10-OT32A is a 40-pin MIL/IDC external terminal module that brings 32 transistor output points from a suitable PLC output module to field wiring terminals inside the control cabinet. Delta documents list UB-10-OT32A or DVPAETB-OT32A as alternative names. A multipin I/O cable connects it to the PLC module, while wiring to valves, relay interfaces and other suitable DC loads terminates at the terminal module.

OT32A makes existing outputs accessible; it does not add 32 independent output addresses to the PLC. NPN/PNP operation, permissible load current and protection requirements depend on the connected PLC module. For relay contacts, consider UB-10-OR16A / DVPAETB-OR16A; for input connections, see UB-10-ID32A / DVPAETB-ID32A. These products perform different duties within the Delta external terminals group.

Terminal arrangement, supply and dimensions

Connections: a latching 40-pin MIL/IDC connector and 36 field connection terminals. Channel count: 32 outputs. The common UB-10/DVPAETB instruction sheet specifies a 24 VDC auxiliary supply with −15% / +20% tolerance and 1 mA consumption per point for OT32A. This 1 mA figure is not the permissible load current.

Mechanical arrangement: DIN rail mounting, approximately 113 × 87 × 53.6 mm body dimensions and 166 g weight. The common terminal instruction sheet gives an operating temperature of 0…55 °C and a storage temperature of −25…70 °C. Allow additional cabinet space for the connector and cable routing.

Compatible DVP, AH and AS output modules

DVP: The manufacturer's terminal instructions and cable selection guide show OT32A connected to DVP32SN11TN. This documented pairing does not establish compatibility with every DVP output module.

AH: Listed models include AH32AN02T-5C, AH32AN02P-5C, AH64AN02T-5C and AH64AN02P-5C. T and P modules have different output directions; OT32A does not convert between them. On 64-point modules, trace the connector, cable and terminal for each 32-channel group separately. Preserve the complete -5C suffix when selecting hardware; other suffixes may use DB37 connections.

AS: OT32A connections for AS32AN02T-A and AS64AN02T-A appear in the AS module manual. Printed DVP markings on the terminal are not automatically the PLC addresses in an AS installation. Follow the applicable diagram for AS address correspondence and the C0 common connection. Do not copy the DVP/AH supply connections into an AS application without checking its diagram.

Suitable I/O cables

OT32A requires a 40-pin to 40-pin connection. UC-ET010-24A is the standard 1 m option. Shielded choices are UC-ET010-24B at 1 m, UC-ET020-24B at 2 m and UC-ET030-24B at 3 m. Older DVPAETB documents also use the name DVPACAB7A10. Cables split into two 20-pin ends should not be confused with OT32A's 40-pin terminal connection. See Delta DVP / AH I/O cables for further details.

Addressing and load limits

The DVP terminal arrangement places outputs Y0, Y2, Y4… in the upper row and Y1, Y3, Y5… in the lower row. With DVP octal numbering, Y0…Y37 represents 32 points. The common DVP/AH terminal instruction sheet shows +24V and GND connections at the row ends; AS assignments must be checked separately. Verify terminal markings against the PLC project's starting address and the cable's channel group.

OT32A transistor output connections must not be treated as relay contacts. The 2 A relay contact rating given for OR16A/B does not apply to OT32A. Obtain load current, group limits, inductive load protection and output voltage requirements from the connected module's manual. The terminal itself does not require a program, firmware download or USB driver.

Editor's Note

When buying a used terminal, ask for a close photograph of the 40-pin socket as well as the OT32A label. Bent contacts, broken latches and darkened terminals deserve attention even if the assembly appears to work briefly.

If the PLC output LED is on but the load does not operate, check the auxiliary supply, common connection, I/O cable and load return path in sequence. One loose common can make several healthy outputs appear faulty.

Safely isolate power and disconnect both cable ends before continuity testing. Do not use an insulation tester with PLC electronics connected, or bridge unknown pins to see what happens.

When moving from DVP to AS, review the old cable labels. Compare terminal markings with actual program addresses one channel at a time. Swapping the two groups on a 64-output module can produce unintended machine operation.

When an output collapses under load, check load current and coil suppression first. Replacing OT32A does not repair an overloaded PLC output. Assess the load, cable and PLC output separately.

Keep the complete terminal, cable and PLC module codes together when assembling a used set. A correctly matched assembly with sound contacts is far more useful than three parts selected by appearance.

PDF manuals and wiring documents

Use our Delta PLC accessories PDF and software files page for installation instructions, cable selection and related PLC documents. General documents are available under Delta PLC and HMI manuals. Read the connected module's output wiring diagram alongside the terminal instructions.

Related subjects

DVP32SN11TN · AH32AN02T-5C · AH32AN02P-5C · AH64AN02T-5C · AH64AN02P-5C · AS32AN02T-A · AS64AN02T-A

UC-ET010-24A · UC-ET010-24B · UC-ET020-24B · UC-ET030-24B · UB-10-OR16A / DVPAETB-OR16A · UB-10-ID32A / DVPAETB-ID32A · AH external terminals · AH I/O cables · AH digital modules

Navigation: Delta external terminals · Delta PLC accessories · Delta DVP PLC series · Delta AS PLC series · Delta AH PLC series · Delta PLC models · Used Delta products

External references

Delta UB-10 external terminal installation and wiring instructions · Delta AH Motion hardware manual – UB-10 / DVPAETB alternative names · Delta AS module manual – terminal and address assignments · Delta PLC/HMI cable selection guide