Delta UB-10-ID32A / DVPAETB-ID32A is an external terminal module that brings 32 digital input points from a compatible I/O module to field terminals. Manufacturer documentation pairs these codes as alternative names. It organises wiring for existing inputs rather than adding PLC input channels. See Delta external terminals and Delta PLC accessories for the related product groups.

Terminal construction and mounting

The assembly has a 40-pin IDC/MIL connector and 36 field terminal positions for input signals and S/S commons. Manufacturer drawings show body dimensions of 113 × 87 × 53.6 mm. Check the DIN rail clip and base fixing components during installation.

Input electrical limits follow the connected I/O module's specifications. The relevant wiring examples describe 24 VDC, 5 mA input circuits with sinking/sourcing arrangements. Determine S/S common wiring from both the sensor output type and the input module diagram.

Compatible input modules

The DVPAETB-ID32A instruction sheet lists Delta DVP32SM11N, Delta AH32AM10N-5C and Delta AH64AM10N-5C. Preserve the -5C suffix on AH models; -5A and -5B versions with different connections must not be treated as the same arrangement.

The AS manual also shows UB-10-ID32A with Delta AS32AM10N-A and Delta AS64AM10N-A. On a 64-input module, identify the connector serving each 32-point group. See Delta DVP Slim digital modules, Delta AH digital modules and Delta AS digital modules for the associated module families.

Cable selection

The DVPAETB instruction sheet specifies Delta DVPACAB7A10 as a 1 m, IDC 40-pin to 40-pin I/O cable. For DVP and applicable AH input modules, the cable selection guide shows UC-ET010-24A: 1 m, UC-ET010-24B: 1 m, UC-ET020-24B: 2 m and UC-ET030-24B: 3 m.

For AS32AM10N-A and AS64AM10N-A, that guide lists UC-ET…-24B cables. Verify connector orientation and cable suffix against the selected module's connection table. See Delta DVP / AH I/O cables for related options.

DVP markings and AS addressing

The AS manual states that UB-10-ID32A carries printed DVP input markings. Use the manufacturer's conversion table or AS label for AS installations. In the starting-group example, DVP markings correspond as follows: X10 → AS X0.8, X20 → AS X1.0 and X37 → AS X1.15. Determine actual project addresses from the hardware configuration and connector group in use.

ID32A is an input terminal assembly. The UB-10-OR16A / DVPAETB-OR16A relay output terminal and UB-10-OT32A / DVPAETB-OT32A transistor output terminal serve different functions. Similar housings do not establish the same signal direction or terminal function.

Editor's Note

Record the input card code as well as the terminal label when ordering. Suffixes such as -5C on an AH module and 24A/24B on a cable matter to the connection arrangement. Keep clear photographs of both connectors with the equipment record.

For a failed input, check the sensor output, field terminal and PLC end in sequence. If the correct signal reaches the terminal but the PLC does not detect it, inspect the cable and connector contacts as well. Measure voltage against the correct S/S reference rather than relying on chassis readings alone.

Remove power and disconnect both cable ends before continuity testing. Inspect ribbon cables for crushed sections, broken conductors near plugs and damaged latches. Do not test by inserting an IDC connector reversed or offset by one row.

In an AS system, reading printed terminal markings directly as program addresses can lead to the wrong input. Verify each sensor's actual bit, then update cable and terminal labels. Pay particular attention to addressing in the second group of a 64-input card.

For a used terminal assembly, check loose screws, cracked terminals, corrosion and heat damage. Compare repaired tracks or added wires with the diagram first. Where testing is available, verify every point with a suitable input module; a few working inputs do not establish the condition of the entire assembly.

PDF manuals and wiring documents

Use Delta PLC accessories files for terminal instructions and cable selection resources, and Delta PLC and HMI manuals for input module electrical specifications. Select the diagram using the complete terminal, cable and input module codes together.

Related topics

Delta AH external terminals · Delta AH I/O cables · Delta external terminals · Delta PLC accessories

Browse controllers in the Delta PLC category and available equipment under second-hand Delta products.

External references: Search the Delta Download Center using the complete model code for manufacturer documentation.