Delta AH32AM10N-5C
Delta AH32AM10N-5C 32-Point Digital Input Module
The Delta AH32AM10N-5C adds 32 digital inputs at 24 V DC to a Delta AH500 PLC system. It uses a locking MIL connector and reads on/off signals from devices such as photoelectric sensors, inductive sensors, limit switches and pushbuttons. An external terminal block can collect the field wiring and connect to the module through a preassembled cable. Delta AH digital modules.
5A, 5B and 5C connectors. The AH32AM10N-5A has a removable terminal block, the AH32AM10N-5B has a DB37 connector, and the AH32AM10N-5C has a MIL connector. For 16 or 64 inputs, see the AH16AM10N-5A and AH64AM10N-5C.
Manual and wiring diagram
AH32AM10N-5C wiring diagram (PDF) · English. PDF page 214, printed page 4-44. It shows the MIL input layout, S/S terminals and UB-10-ID32A wiring. All Delta AH PLC PDF files.
Specifications and field wiring
Input signal. Nominal rating per point is 24 V DC, 5 mA. Input impedance is 4.7 kΩ. Delta specifies an ON threshold above 15 V DC and an OFF threshold below 5 V DC. Response time is 10 ms from OFF to ON and 15 ms from ON to OFF, both with a ±10% tolerance. The specified maximum input frequency is 50 Hz.
PNP and NPN wiring. The module accepts sinking and sourcing DC signals. Check the wiring diagram for the S/S common connection that matches the field output type. Sensors sharing a common must have compatible output types and supply wiring. The front-panel LEDs indicate the state of each input.
MIL cable and external terminal. Delta shows the UB-10-ID32A with the UC-ET010-24A cable. Shielded options include the UC-ET010-24B (1 m), UC-ET020-24B (2 m) and UC-ET030-24B (3 m). AH I/O cables · AH external terminals.
ISPSoft input addresses
Check the rack slot and input start address in HWCONFIG in ISPSoft. The module uses two 16-bit input groups. For example, a start address of X2.0 gives input ranges of X2.0–X2.15 and X3.0–X3.15. For the PC-to-CPU connection, see COMMGR and Delta PLC software.
Editor’s Note
When buying a used module, check the full nameplate. Confirm the 5C suffix and inspect the MIL socket and latch.
Ask for the exact cable and external terminal part numbers, too. A cable for another connector version can complicate an otherwise straightforward replacement.
If a whole group of inputs drops out together, start with the S/S common and the 24 V field supply.
On the bench, test the first and last input of each 16-point group. Watch the front LED and the X bit in ISPSoft together to catch wiring order or address shifts.
If the input LED lights and the program reads the wrong bit, compare the HWCONFIG start address with the electrical drawings.