Delta DVPACAB7A10
Delta DVPACAB7A10
Delta DVPACAB7A10 is a 1-metre ribbon-style I/O connection cable with 40-pin IDC connectors at both ends. It carries signals between a suitable digital I/O module and an external terminal board. Verify the complete module code, connector arrangement and terminal board together.
UC-ET010-24A designation and connections
The manufacturer hardware manual identifies DVPACAB7A10 together with Delta UC-ET010-24A. Its connection arrangement is IDC40-to-IDC40. Distinguish it from branching cables with two connectors at one end. Provide the old cable marking and both connected-device codes when ordering.
AH32 and AH64 input modules
For Delta AH32AM10N-5C, the manufacturer shows connection through the cable to UB-10-ID32A / DVPAETB-ID32A. Using both input groups on Delta AH64AM10N-5C requires two separate cables and two ID32A terminal boards. Each connection serves one group of 32 inputs.
40 contacts do not mean 40 independent channels. Read channel and common-connection arrangements from the module drawing. Label which input group each cable serves in an AH64 installation; the two boards do not connect as branches of one cable.
DVP application and terminal function
The cable guide also shows the Delta DVP32SM11N input module with UC-ET010-24A and ID32A. In the same IDC40 connection family, the DVP32SN11TN output module uses an UB-10-OT32A terminal board. The connected module and terminal determine input or output function.
AH32AM10N-5B instead uses a DB37 connection and is paired with UB-10-ID32B / DVPAETB-ID32B. Check the 5B and 5C suffixes carefully during replacement. Similar module names do not establish the same connector or cable requirement.
7B10, 7C10 and shielded options
Delta DVPACAB7B10 and Delta UC-ET010-24C use an IDC40-to-two-IDC20 arrangement. Delta DVPACAB7C10 uses DB37; Delta DVPACAB7D10 is a 36-pin connection; and Delta DVPACAB7E10 is a 50-pin connection. Do not select these instead of 7A10 by appearance alone.
Delta UC-ET010-24B is shown separately as a 1-metre shielded IDC40-to-IDC40 option. Assess ribbon construction, shielding and the terminal-side connector arrangement together. Do not assume conductor size, current limits or suitability for moving cable carriers.
Installation and field connections
Include duct turns, connector exits and maintenance access in the 1-metre route. Avoid trapping the ribbon under covers or folding it sharply beside a connector. Install with module and field supplies disconnected, checking pin-one orientation and retainer seating.
Review Delta AH digital modules together with Delta AH external terminals. For inputs, check S/S and field power; for outputs, check common connections, loads and terminal function against the module documentation. Start testing with one channel and complete every group used by the application.
PDF and connection drawings
Start document selection at Delta PLC accessories files. In the 2019 PLC/HMI Cable Selection Guide, printed pages 2-3–2-4 / PDF pages 102–103 show AH input connections, and Figure 1A, printed page 2-28 / PDF page 127 shows the IDC40 ribbon arrangement. Printed page 3-65 / PDF page 97 of the 2016 AH Motion Hardware Manual gives both cable codes together.
Editor's Note
Confirm cable quantity for an AH64 installation first. If both input groups are required, plan two cables and two terminal boards together. Establish the complete connection requirement before ordering.
Photograph both ends before removal. Record the module suffix, terminal code and group label together. Take particular care to distinguish DB37-connected 5B models from MIL-connected 5C models.
Inspect folds and pinch points in the ribbon. Look for cut insulation, separated IDC housings and broken retainers. Disconnect using the housing and retainer rather than pulling on the ribbon.
Measure continuity with both ends disconnected from equipment. Follow pin numbering from the correct viewing direction. If an input group disappears together, check common connections, field power and plug seating alongside the cable.
Use a known field signal for the final check. Verify that a signal applied through the terminal appears at the intended input address. LEDs or a continuity beep alone do not prove every connection; record the result by input group.
Related topics
Browse parent groups under Delta AH I/O cables and Delta PLC accessories, and device documentation under Delta PLC and HMI manuals.
External references: Delta PLC/HMI Cable Selection Guide — 2019, English · Delta AH Motion Controller Hardware Manual — English.