Delta AH64AM10N-5C
Delta AH64AM10N-5C – 64-Point Digital Input Module
The Delta AH64AM10N-5C is an expansion module with 64 digital inputs rated at 24 V DC for the Delta AH500 PLC system. Nominal current is 3.2 mA per input. The module has two latching 40-pin MIL connectors, each carrying 32 inputs.
The module collects signals from proximity sensors, limit switches, push buttons and auxiliary contacts. It suits control panels that need a high input count within the Delta AH digital module range. PNP and NPN sensor wiring depends on the S/S common terminal for each input group.
Wiring, terminals and addressing
S/S common Connect the relevant group’s S/S terminal to 0 V for 24 V DC PNP sensors or to +24 V for NPN sensors. Group sensors that share a common by wiring type. See sink and source wiring for the current paths.
Field terminals Use two UB-10-ID32A terminal boards to bring all 64 inputs out to field terminals. Delta lists the 1 m UC-ET010-24A cable and shielded 24B cable options. See AH I/O cables, external terminals and the Delta Cable Selection Guide.
Software and addressing Check the module slot and X start address in ISPSoft HWCONFIG. The module spans four consecutive 16-bit input groups. A start address of X0.0 gives a last input of X3.15. Go online through COMMGR to monitor field signals. The hardware table lists an input response of 10 ms from OFF to ON and 15 ms from ON to OFF.
PDF manual Delta AH500 Hardware and Operation Manual (English). See section 2.6.1 for specifications, 4.7.20 for AH64AM10N-5C wiring and 5.4.1 for input addressing. Further documentation is available under Delta AH PLC PDF Files.
Editor’s Note
When buying a used module, check the full AH64AM10N-5C order code and the latches on both MIL connectors.
Confirm which cables and terminal boards are included. One board brings out 32 inputs.
On the bench, start with one input from each 16-point group. Then test all 64 points and watch the corresponding X bits in ISPSoft.
Check the front selector when using the LEDs for diagnostics. The display shows 32 points at a time.
Delta’s wiring drawing also carries a 5 mA label. Use the 3.2 mA value in the electrical specifications table for input current.
Related Topics
Other input modules The AH32AM10N-5C offers 32 inputs with a MIL connector. The AH32AM10N-5B uses DB37, and the 16-point AH16AM10N-5A uses a removable terminal block. For stand-alone panel counting, see the Derell DGC-776-RS-A.
AH expansion modules · AH analog modules · Delta PLC software · Delta PLC and HMI manuals · Delta PLC · Second-hand Delta products