Delta AS332T-A

Delta AS332T-A PLC CPU

The Delta AS332T-A is a 24 V DC modular PLC CPU in the Delta AS300 series. It has 16 digital inputs, 16 NPN transistor outputs and a 128k-step program capacity. Typical applications include conveyors, packaging machines and pulse-controlled positioning.

Inputs, outputs and pulse control

Inputs X0.0–X0.15 accept 24 V DC signals. Match the S/S common wiring to the PNP or NPN sensor type using Delta’s wiring diagram. Outputs Y0.0–Y0.15 are NPN (sinking). The resistive load rating is 5–30 V DC, 0.1 A per output and 1.6 A per common. Built-in I/O is wired through a 40-pin MIL connector.

The CPU supports 6 high-speed counter channels at up to 200 kHz and 6 axes of pulse output at up to 200 kHz. Use X0.0–X0.11 and Y0.0–Y0.11 for high-speed functions. The last four inputs are rated at 10 kHz and the last four outputs at 100 Hz with a resistive load.

The series supports up to 32 expansion modules or 1,024 physical I/O points in total. See AS expansion modules, digital I/O, analog measurement and function cards when selecting hardware.

Programming, cables and communications

Open the AS332T-A project in ISPSoft. Select a Mini USB or RJ45 Ethernet connection in COMMGR. Check that the AS USB driver is installed for a USB session. For Ethernet, check the PC and CPU IP settings. See the Delta PLC cable guide for connection options.

The CPU has one Ethernet port, two RS-485 ports, one Mini USB port and one microSD slot. Modbus TCP can be configured over Ethernet and Modbus RTU over RS-485. Keep the machine’s IP address, station address and serial settings with the project backup.

Related CPU models

The AS332P-A has the same I/O count with PNP outputs. The AS320T-B and AS320P-B offer 8 inputs, 12 outputs and removable terminal blocks. Consider the AS324MT-A for differential pulse applications. The AS300N-A has no built-in I/O.

Editor’s Note

When buying a used unit, check that the label clearly reads AS332T-A.

Inspect the MIL connector pins and confirm that the cable and terminal board are included.

Back up the program, hardware configuration and communication settings before removal.

Monitor the inputs online during bench testing and check each output with a suitable test load.

If the application uses pulse control, test the high-speed channels separately. An output LED alone cannot confirm that the load switches.

Related topics

Delta AS PLC series · AS200 · AS500 motion controllers · Delta PLC software

Delta PLC and HMI manuals · Delta PLC home · Used Delta products

Manufacturer references

AS332T-A installation sheet (includes EN) · AS hardware manual (EN) · AS operation and programming manual (EN) · AS series catalog (EN)