Delta DVP communication cables

Delta DVP communication cables

Delta DVP communication cables provide an RS-232 serial connection between a suitable DVP PLC port and a computer or operator panel. The UC-MS models in this group differ principally in length, mini-DIN connector construction and male or female DB9 termination. Check the PLC model, the selected port and the wiring diagram of the other device together.

UC-MS and DVPACAB230 model differences

Delta UC-MS010-02A is 1 metre long, with a right-angle 8-pin male mini-DIN at the PLC end and a female DB9 at the other end. Delta UC-MS020-01A is the 2-metre option and Delta UC-MS030-01A is the 3-metre option with 8-pin male mini-DIN and female DB9 ends. The catalogue illustrates computer connections for these models; use with a panel also depends on that HMI's port diagram.

Delta UC-MS020-06A is 2 metres long and Delta UC-MS030-06A is 3 metres long. Both have 8-pin male mini-DIN and male DB9 ends and are illustrated with HMI connections. The same cable does not suit every HMI: verify its COM port, connector gender and pin assignment.

Delta DVPACAB230 is listed as a 3-metre cable between a PLC and a PC with 9-pin and 25-pin D-Sub connections. When replacing one on an existing machine, check the PLC-side port drawing and the complete cable code.

Port, converter and software selection

A UC-MS cable is not a protocol converter. Adding a gender changer does not guarantee the required pin connections. If a computer uses a separate USB-to-RS-232 converter, its driver and virtual COM port belong to that converter. For USB connections, Delta UC-PRG020-12A and Delta UC-PRG030-01A serve different arrangements: the former connects to mini-DIN RS-232, while the latter connects to a suitable device's mini-USB port. Select from Delta DVP programming cables according to the actual CPU port.

For computer communication, the selected COM port, baud rate, data format and device address must match the PLC configuration. Choose programming software for the CPU generation; compare Delta WPLSoft and Delta ISPSoft through Delta PLC software. The cable code alone does not establish one baud rate or software version.

For panel communication, also check the HMI project's PLC driver, port number and serial settings. Delta HMI Programming and HMC Cables and Delta HMI Communication Auxiliary Units help distinguish the panel's computer connection from its PLC connection.

Start document selection at Delta PLC accessories files. Sections 1.21 Cable Models and 1.22 Descriptions of Cable Models in the Delta PLC/HMI Cable Selection Guide cover connector arrangements and cable drawings. Read the general model list alongside the connection section for the exact CPU and HMI.

Editor's Note

Ask for photographs of both ends before buying. A similar label is not enough: check DB9 gender, mini-DIN pins and whether an angled connector will fit the available cabinet space.

Check the connection before condemning the PLC port. Try a known-good cable, then a known-good USB-to-RS-232 converter if one is used. A converter appearing on the computer does not prove that data reaches the PLC.

If movement causes interruptions, inspect the cable. Disconnect both ends and check continuity and unintended shorts against the manufacturer's drawing. A reading that changes when the cable is gently flexed near a connector suggests a broken conductor.

Record the working machine's settings first. Save the existing project before changing baud rate, parity, address or HMI driver. Separating a wrong port selection from a damaged cable saves troubleshooting time.

Inspect the cable route as well. Review serial wiring running beside contactors or drive motor cables, and follow the device drawing for shielding and grounding. For used cables, crushed insulation, loose DB9 screws and bent mini-DIN pins deserve close attention.

Related topics

See Delta DVP interfaces for additional port hardware, Delta PLC accessories for accessory selection and Delta PLC to identify the CPU and module family.

External references: Delta PLC/HMI Cable Selection Guide — 2019 · Delta DVP/TP catalogue — 2024.


Refine Search