Delta UC-MS010-02A
Delta UC-MS010-02A — 1 m RS-232 Communication Cable
Delta UC-MS010-02A is a 1-metre RS-232 cable with a right-angle, 8-pin male mini-DIN connector and a female DB9 connector. It belongs to the Delta DVP communication cables range. The catalogue lists PLC-to-PC use, while suitable panel-to-PLC applications are also documented.
Applications and connection selection
Delta’s TP02G-AS1 and TP04G-AS2 instruction sheets show UC-MS010-02A between a DVP PLC and the panel’s COM1 RS-232 port. Verify the exact PLC, panel interface and communication settings together. Review DVP PLC series and TP panels and remote I/O to distinguish the different hardware within these ranges.
Main signal connections
| 8-pin male mini-DIN | Female DB9 | Function |
|---|---|---|
| 4 — Rx | 3 — Tx | Data from DB9 to mini-DIN |
| 5 — Tx | 2 — Rx | Data from mini-DIN to DB9 |
| 8 — GND | 5 — GND | Signal reference |
The manufacturer drawing also shows DB9 links between 7–8 and 1–4–6. Mini-DIN pins 1 and 2 are labelled +5 V; those labels do not establish that the cable powers the PLC or panel. Use the complete drawing when preparing a cable, including the connector links.
Differences from related UC-MS cables
| Model | Length | DB9 end | Mini-DIN end |
|---|---|---|---|
| UC-MS010-02A | 1 m | Female | Right-angle male |
| UC-MS020-01A | 2 m | Female | Straight male |
| UC-MS030-01A | 3 m | Female | Straight male |
| UC-MS020-06A | 2 m | Male | Straight male |
| UC-MS030-06A | 3 m | Male | Straight male |
Check DB9 connector gender and cable exit direction as well as length. A right-angle connector can help with cabinet clearance, but verify that it does not press against adjacent terminals or covers. Adding a gender adapter alone does not establish full electrical compatibility.
Computer connection and software
The computer requires a suitable RS-232 serial port. If a USB-only computer uses a USB/RS-232 converter, the driver and COM-port settings belong to that converter. USB programming options such as UC-PRG020-12A can be reviewed separately under DVP programming cables.
For a supported PLC application, check WPLSoft, ISPSoft and COMMGR settings as applicable. Match the interface, baud rate, parity, data/stop bits and device address to the target hardware. Connecting the cable does not automatically match these settings.
For a TP panel, also verify the device driver, selected port and register addresses in the TPEditor project. Transferring a project from the computer and reading PLC data from the panel are separate connection steps. Identify the two devices the cable will connect before selecting it.
Editor’s Note
Check both equipment ports first. An eight-pin socket that looks suitable is not enough. Verify the model code, RS-232 interface and female DB9 end together before connecting the cable.
A right-angle mini-DIN helps in confined spaces, but the wrong cable direction can place constant strain on the socket. Check the fitted connector together with the cover and neighbouring cables. Disconnect by holding the connector body rather than pulling the cable.
With the cable disconnected, check continuity for 4–3, 5–2 and 8–5 first. Then check the DB9 links and unintended shorts. Gently moving the cable near each connector during measurement can help reveal an intermittent break.
Confirm whether pin numbers are shown from the connector face or solder side. A mirrored view can lead to incorrect wiring. Do not test the data pins by applying an external 5 V or 24 V supply.
If communication fails, change one item at a time. Check the COM port first, then the serial format and device address. Reading a known register from suitable test equipment gives a clearer result than changing settings at random.
For a used cable, inspect bent mini-DIN pins, loose DB9 screws and damage near the connector entries. Request a real data-reading test after continuity checks. Begin with reading values on an operating machine rather than clearing programs or writing data in bulk.
PDF, software and related topics
Use the Delta PLC accessories PDF and software files page for the cable selection guide and software links. Panel documentation is under Delta TP panel files. Further sources are available under PLC and HMI manuals and Delta user manuals.
Navigation: UC-MS010-02A main page · Delta PLC accessories · Delta PLC models · Used Delta products
External references
Delta PLC/HMI Cable Selection Guide — 1-80, Figure 1 · Delta DVP / TP Catalogue — Accessories · Delta TP02G-AS1 Instruction Sheet — Communication Connection · Delta TP04G-AS2 Instruction Sheet — Communication Connection