Delta UC-MS020-06A
Delta UC-MS020-06A
Delta UC-MS020-06A is a 2-metre RS-232 communication cable with an 8-pin male Mini-DIN connector and a male DB9 connector. The manufacturer lists it for linking a suitable DVP PLC RS-232 port to an HMI. Selection depends on the 06A suffix and male DB9 end as well as length.
PLC and HMI port compatibility
Identify the PLC under Delta DVP PLC series and the panel under Delta HMI files. For a family such as Delta DOP-B, check the complete model's COM port and RS-232 support. A series name alone does not establish identical ports and pin assignments across every panel.
Configure the correct PLC driver, COM selection, speed, parity and station address in the panel project. A physically connected cable does not verify these settings. Review ports and supporting hardware under Delta HMI communication peripheral units.
Figure 4 wiring
The manufacturer's principal data connections are Mini-DIN pin 4 Rx ↔ DB9 pin 3 Tx, Mini-DIN pin 5 Tx ↔ DB9 pin 2 Rx, and Mini-DIN pin 8 GND ↔ DB9 pin 5 GND. The DB9 side also shows links between 7–8 and 1–4–6.
Read pin numbers using the connector orientation shown in the manual. Do not rely on conductor colours alone when repairing a cable. UC-MS020-06A carries the serial connection; the PLC and panel still require their specified power supplies.
Differences from similar UC-MS codes
Delta UC-MS030-06A is the 3-metre option in the same connection family. Delta UC-MS020-01A is 2 metres, Delta UC-MS030-01A is 3 metres, and Delta UC-MS010-02A is 1 metre; these are listed with a female DB9 end. Connector gender is a separate selection factor from length.
Review Delta UC-PRG020-12A for a serial connection from a computer's USB side; it should not be assumed to replace UC-MS020-06A directly. If serial conversion is required, select suitable hardware under Delta DVP interfaces.
Cabinet layout with a 2-metre cable
Allow for cable ducts, turns, door movement and maintenance access when assessing the 2-metre length. Secure a door-mounted HMI cable so hinge movement does not pull it tight. Avoid sharp bends at connector exits and continuous tension on the DB9 housing.
Check the DB9 retaining screws and Mini-DIN alignment. Do not force connector pins, and avoid long parallel routes beside motor and drive power cables. Photograph the working installation before replacement.
Software, backups and documents
No firmware or project is downloaded to the cable itself. Select Delta WPLSoft or Delta ISPSoft according to CPU support and review tools under Delta PLC software. Use Delta HMI programming and HMC cables for panel backups and PC connection information.
Start document selection at Delta PLC accessories files. Figure 4 in the PLC/HMI Cable Selection Guide shows the wiring on printed page 1-82 / PDF page 91. Printed page 48 / PDF page 49 of the 2023 DVP/TP catalogue confirms the model, length and HMI connection description.
Editor's Note
Inspect the complete code and both ends first. A used item described only as a “Delta serial cable” is insufficient. Check the Mini-DIN pins, male DB9 end and cable label together.
Do not immediately change settings when communication stops. Back up the working project and record COM selection, driver, speed and device address. Preserve known-good settings while checking the cable.
If communication drops when the door moves, inspect connector exits. Examine the Mini-DIN outlet, DB9 housing and trapped duct sections. Conductors can fracture inside an intact outer jacket.
Test continuity with both ends disconnected from equipment. Check the three data lines and DB9 links separately against Figure 4. Front and rear views of a plug can reverse the apparent pin order.
Complete testing with the actual PLC and panel. First read one known value, then observe the connection during normal door movement and operation. A continuity beep alone does not complete the application test.
Related topics
Browse parent groups under Delta DVP communication cables and Delta PLC accessories, and device documents under Delta PLC and HMI manuals and Delta manuals.
External references: Delta PLC/HMI Cable Selection Guide — 2019, English · Delta DVP/TP manufacturer catalogue — 2023, English.