Delta industrial network cables
Delta Industrial Network Cables
Delta industrial network cables connect PLCs, drives and remote I/O devices on field networks. The main models covered here are UC-DN01Z-01A, UC-DN01Z-02A and UC-PF01Z-01A. The first two serve DeviceNet/CANopen applications; the third serves PROFIBUS. Select these Delta PLC accessories according to the physical requirements of the intended network.
These products are passive cables rather than communication modules or protocol converters. Match the cable, port and network protocol together. Identical connector shapes do not establish identical electrical interfaces. See Delta network connectors for related connector choices.
Main cable models and their roles
UC-DN01Z-01A: Listed as a DeviceNet/CANopen thick trunk cable. Consider conductor size, total network load and communication speed together when planning long runs and network power.
UC-DN01Z-02A: Listed as a DeviceNet/CANopen thin drop cable. Its distance limits differ from those of the thick cable. The manufacturer's selection guide allows both cables in main or branch runs, subject to the applicable network length and load limits.
UC-PF01Z-01A: A PROFIBUS DP communication cable. Do not select it as a DeviceNet/CANopen replacement based on a similar model name. When reviewing UN-03PF-01A, UN-03PF-02A and UN-03PF-03A connectors, check cable direction, service access and termination arrangement.
305-meter supply length and network distance
The catalog's 305 m figure describes supply/ordering length. It does not establish a 305-meter network limit at every baud rate. State the actual length of a cut cable and include both trunk and branch lengths in the network design.
The Delta guide's DeviceNet table lists UC-DN01Z-01A at 500 m for 125 kbit/s, 250 m for 250 kbit/s and 100 m for 500 kbit/s. UC-DN01Z-02A is listed at 100 m for all three speeds. Branch and power-distribution limits also apply. These figures must not be transferred to PROFIBUS or EtherCAT networks.
Network type, connectors and termination
Preserve the separate duties of CAN_H, CAN_L, V+, V− and shield on DeviceNet wiring. Read the exact terminal definitions in the manuals for modules such as DVPDNET-SL and AH10DNET-5A. Mixing data and network-power conductors can damage connected equipment.
Plan trunk connections, branches and termination positions together when selecting TAP-CN01, TAP-CN02 and TAP-CN03 distribution accessories. Use terminators such as TAP-TR01 only with their intended ports and network arrangement. Identify the actual network ends rather than terminating every device. Follow the PROFIBUS connector's own termination instructions.
Evaluate CANopen wiring for AH10COPM-5A separately from PROFIBUS wiring for AH10PFBM-5A and AH10PFBS-5A. RJ45 options under Delta CANopen cables and Delta EtherCAT cables must not be treated as interchangeable solely because the plugs look alike.
Installation, shielding and commissioning
Route communication wiring appropriately away from motor and drive power cables, and bond shields according to the equipment's EMC instructions. Avoid unnecessarily untwisting pairs inside connectors and prevent shield strands from contacting signal terminals. Verify continuous-flex, oil and chemical resistance separately for the intended installation.
Passive cables require no software download. Supported network devices may be configured using Delta CANopen Builder or Delta DeviceNet Builder within the appropriate hardware/project scope. Check physical wiring separately from station addresses, baud rate and device configuration.
Editor's Note
Read the complete jacket marking instead of buying by cable color or thickness alone. Inspect crushed sections, joints and connector ends. Establish the actual length of a cut piece; catalog reel length is not the length of the cable in front of you.
If a network fails after adding a device, inspect the new connection first. Incorrect terminals, loose contacts, reversed data pairs or misplaced termination can make healthy equipment appear faulty. Change one thing at a time and record the result.
A continuity test does not fully assess a communication cable. Shield contact, pair construction or movement-related faults can remain despite a normal multimeter reading. Check carefully while moving the ends and compare with a known-good cable or suitable network tester where possible.
Isolate network power before resistance measurements and follow the device instructions. Two 121-ohm DeviceNet end resistors ideally measure approximately 60.5 ohms in parallel; connected circuitry can affect the reading. This preliminary check alone does not prove reliable operation under load.
Measure network power at the remote node while devices are operating, not only beside the supply. Investigate cable size, total load and connection points if voltage drops. Check these causes before assuming a software fault.
Every repair joint can disturb shielding and pair geometry. For critical or moving installations, consider a suitable industrial connection or cable replacement rather than an improvised taped splice. If communication fails when a drive starts, examine cable routing and shield bonding closely.
Sources, PDF and software files
The document hub is Delta PLC accessories PDF and software files. Use Delta PLC/HMI Cable Selection Guide, chapter 4, together with the connected device's manual for cable selection, pinout and distance limits. Other documents are available under Delta PLC and HMI manuals and Delta user manuals.
Related topics
Delta network connectors · Delta CANopen cables · Delta EtherCAT cables · TAP-CN01 · TAP-CN02 · TAP-CN03 · TAP-TR01
Navigation: Delta PLC accessories · Delta PLC models · Second-hand Delta products
External references
Delta PLC/HMI Cable Selection Guide, 15 August 2019 (English) · External archive copy of the same manufacturer guide · Delta manufacturer catalog covering standard fieldbus cables (English)