Delta DVPDNET-SL is a DeviceNet scanner for the left expansion bus of a compatible Delta DVP PLC. In master mode it scans drives and remote I/O. In slave mode it exchanges data with another DeviceNet master. Delta documents DVP-SV, DVP-SV2 and EH2-L hosts. For SA2, SX2 and newer CPUs, check left-side expansion support and the D-register map for the exact model.
Network wiring, node address and speed
The removable DeviceNet communication port uses 1 V− (black), 2 CAN_L (blue), 3 shield, 4 CAN_H (white), 5 V+ (red). The CPU powers the module electronics. The DeviceNet network takes separate 24 V DC power through V+/V−. Size the power supply for the combined network load. Fit one 121 Ω terminator between CAN_H and CAN_L at each physical end of the trunk. Follow the network design for shield grounding. Keep the trunk away from motor wiring to reduce electromagnetic interference.
Two rotary switches set MAC ID 00–63. Each node needs a unique address. Standard rates are 125, 250 and 500 kbit/s. The DR1/DR0 settings are OFF/OFF = 125, OFF/ON = 250, ON/OFF = 500. Check the hardware revision and other network devices before using extended rates. Set the switches with power off. Changes take effect after power is restored. The module mounts with the CPU on a 35 mm DIN rail.
DeviceNet Builder, PLC program and cable
Use DeviceNet Builder to set the master/slave mode, Scan List and I/O connection type. Use the input and output tables to check which PLC registers carry each device’s bytes. Master mode supports Polled, Bit-Strobe, Change of State and Cyclic connections. The data limit is 380 bytes per direction in master mode and 255 bytes per direction in slave mode.
Load the PLC program into a supported CPU using WPLSoft or ISPSoft. DeviceNet Builder connects through the CPU. For the SV2 models in Delta’s cable guide, CPU COM1 RS-232 uses UC-PRG020-12A from PC USB or UC-MS020-01A from a serial port. For other hosts, select the programming cable from the CPU guide. RS-232 and RS-485 are PC-to-PLC connection options. The five-pin connector serves the DeviceNet network.
Example master registers for the first module. On DVP-SV, process inputs use D6037–D6226, process outputs use D6287–D6476, and module status uses D6036. On SV3/SX3, the corresponding registers are D16037–D16226, D16287–D16476 and D16036. Confirm the CPU model, module order and Builder byte mapping before using these addresses in the ladder program.
Field application and protocol selection
Commissioning a drive and remote I/O. Scan a DeviceNet-equipped inverter or remote I/O unit and add it to the Scan List. Read drive status and input words first. Then verify the output words against the drive’s data map. Show the network fault separately on the SCADA system or operator panel. Verify the emergency stop and run enable circuits before testing motor movement.
Choosing a communication module. A plant may use several industrial communication networks. DVPCOPM-SL serves CANopen, DVPPF02-SL serves PROFIBUS DP, DVPEN01-SL serves Ethernet, and DVPSCM12-SL serves serial applications. For EtherNet/IP or Modbus/RS-485, verify both the field device protocol and the supported module. For new panel designs, also see Derell PLCs and smart relays.
Editor’s Note
On a used module, check the left-bus connector, DeviceNet plug and both address switches.
If the module powers up but nodes do not appear, check network voltage at V+/V− with a multimeter. Then compare the DR1/DR0 setting with the other nodes.
Check the terminators at both ends of the trunk and look for duplicate MAC IDs.
A node can appear in a scan before exchanging real-time data. Check its Scan List entry and I/O lengths.
When diagnosing a fault, read the MS/NS LEDs, numeric display and PLC status word together.
Back up the Builder project before replacing the module. In a controlled test, verify how the PLC program handles buffered data when a node drops offline.
PDF documents and series links
See our Delta DVP PLC files page for the manuals. Section 13.2 of the 2026 Module Manual covers DVPDNET-SL. See PDF page 400 for terminals and switches, 407–409 for register mapping and 434–435 for diagnostics.
DVPDNET-SL · DVP Slim communication modules · DVP expansion modules · DVP PLC series · Used Delta PLCs · Delta Automation
External references
Delta DVPDNET-SL Operation Manual, 2023 · Delta DVP Series Module Manual, 2026 · Delta DVPDNET-SL Instruction Sheet · Delta PLC/HMI Cable Selection Guide