Delta DVPSCM12-SL
Delta DVPSCM12-SL – Dual-Port RS-485 / RS-422 Communication Module
Delta DVPSCM12-SL is a serial communication expansion module installed on the left side of a compatible DVP PLC CPU. It provides two independent RS-485/RS-422 ports, COM1 and COM2. Part of the DVP Slim communication module family, it supports field-device data exchange and an additional connection for CPU programming and monitoring.
The module supports Modbus ASCII, Modbus RTU and UD Link user-defined serial communication. Matching physical communication ports alone does not establish interoperability; the protocol and data format must also match. BACnet MS/TP slave functionality belongs to DVPSCM52-SL.
Specifications and CPU compatibility
Interface: RS-485 or RS-422 selectable for each port. Supported rates range from 1,200 to 460,800 bit/s, with 7/8 data bits, None/Odd/Even parity and 1/2 stop bits. The manufacturer specifies up to 32 devices per port. Assess achievable distance and reliable speed against the cable and connected equipment.
Supply: 24 V DC from the CPU's internal expansion bus; consumption 1.5 W. The serial interface is isolated from the supply; the specified insulation test voltage is 2,500 V DC. Operating temperature is 0–55 °C and approximate weight 95 g. Each port has a switchable built-in 120 Ω termination resistor.
The 2026 manufacturer manual lists DVP-SA2 V1.0, DVP-SX2 V1.2, DVP-SV V2.2, DVP-SE V1.0, EH2-L V2.20 and EH3-L V1.00 CPUs. It specifies module firmware V1.10 or later for DVP-SV3/SX3 support. Verify the full CPU code, version and left-side expansion support before selecting the module.
RS-485 and RS-422 terminal connections
RS-485: Pin 3 = D+, pin 4 = D− and pin 5 = SG. Pins 1, 2 and 6 are unused in this mode. Compare D+/D− definitions when wiring an RS-485 network; A/B labels may indicate different polarities between manufacturers.
RS-422: Pin 1 = TX+, pin 2 = TX−, pin 3 = RX+, pin 4 = RX−; pins 5 and 6 = SG. Connect each transmit pair to the other device's receive pair. The physical interface must match the SCMSoft selection. SG is a signal reference, not a protective-earth terminal.
Arrange an RS-485 network as a main line with short branches. Apply termination at its two physical ends; leave the module's resistor disabled when its position does not require termination. Consider resistance, shielding and grounding together. Route industrial communication cables separately from motor and drive power cables.
Configuration software and connection cables
SCMSoft is the module's configuration software and is included in DCISoft. COM PORT Setting defines interface type, baud rate, parity and station address. MODBUS Advance sets up bit/word read and write mappings. UD Link handles custom packets, including headers, data fields, checksums and execution sequences.
Develop the host PLC program using WPLSoft or ISPSoft as supported by the CPU; ISPSoft communication uses COMMGR. For SV3/SX3 systems, the 2026 manual also shows opening SCMSoft from DIADesigner hardware configuration. Distinguish CPU application programming from module configuration.
Connection through the CPU: For a suitable CPU with an 8-pin mini-DIN RS-232 port, match UC-MS020-01A / UC-MS030-01A or the USB-connected UC-PRG020-12A to the exact CPU. Direct connection to an SCM port requires a suitable USB-to-RS-485/RS-422 converter and terminal wiring. The module itself has no RS-232 or USB socket.
The WPLSoft example for CPU access through SCM COM1 uses defaults of 9600 bit/s, 7E1 and station 247. COM2 defaults to station 246. A used module may have different settings; distinguish the SCM port's station address from the CPU's own address.
Control registers and data exchange
Left-side special modules are numbered K100–K107, starting with the module closest to the CPU. For the first module, FROM K100 K0 D200 K2 reads its model code and firmware into D200–D201. The DVPSCM12-SL model code is H4041. Ensure that D200–D201 are available in the actual application.
CR#31–CR#34 control MODBUS Advance exchange: COM1 reading, COM2 reading, COM1 writing and COM2 writing. For a first-position module with its SCMSoft read mapping already configured, TO K100 K31 K2 K1 enables continuous COM1 word reading. Verify the actual module position; this instruction does not create the port or slave configuration. Monitor CR#11 error status in the Ladder application as well.
Applications and commissioning
In an automation cabinet, one port can serve drives/servos while the other serves meters or temperature controllers. Obtain each servo drive's or other device's register addresses, data types and scaling from its own manual. Increasing baud rate does not make all transactions simultaneous; response delays, polling count and retries determine the total update cycle.
For values transferred to SCADA or an operator panel, monitor the last successful communication time. When defining the PLC–SCADA connection, distinguish stale data from current measurements. Check station addresses, function codes, zero/one-based address notation and multiword ordering in the Modbus configuration.
Related communication modules
Consider DVPSCM52-SL for BACnet MS/TP slave requirements. DVPEN01-SL provides Ethernet connectivity, DVPCOPM-SL serves CANopen master applications and DVPDNET-SL serves DeviceNet master applications. These address different networks and are not direct replacements. Compare CPU support and application protocol together.
Editor's Note
A POWER light alone is insufficient when buying a used communication card. Inspect its label, firmware, left-side connector and both port terminal blocks.
Test COM1 and COM2 separately with a known-good device and verify both reading and writing. A flashing TX LED does not establish that a valid reply arrived; inspect RX activity and the received values.
For a communication fault, check baud rate, parity, protocol, address and D+/D− wiring first. Two masters attempting to control the same RS-485 line can also cause failures.
Inspect the CPU's 24 V power supply and the module supply status. Low voltage and poor contacts can resemble a port fault. Check the supply current budget and relevant fuse as well.
Perform short-circuit and resistance checks with power isolated and field wiring disconnected. Back up the settings before a factory reset; losing working communication mappings can prolong the repair.
For a used-unit sale, state quantity, label photographs, working/faulty condition and test results for both ports. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.
PDF documents and related topics
For wiring, control registers and SCMSoft examples, visit our Delta DVP PLC files page first. The 18-page manufacturer sheet dated 2 July 2014 includes a Turkish section. Use section 13.5 of the 2026 module manual for the newer CPU support information.
Related topics and navigation: Delta and used models | Delta PLC | DVP series | Expansion modules | Slim communication modules | DVPSCM12-SL model page
External references
Delta DVPSCM12-SL manufacturer sheet – 2014, multilingual including Turkish
Delta DVP Series Module Manual – 2026, section 13.5
Delta DVPSCM12/52-SL Operation Manual – Rev.02, historical English manual
Delta PLC/HMI Cable Selection Guide