Delta DVPPF02-SL

Delta DVPPF02-SL – PROFIBUS DP Slave Communication Module

The Delta DVPPF02-SL connects a compatible Delta DVP Slim PLC to a PROFIBUS DP network as a slave station. Delta lists the DVP-SV, DVP-SX2, DVP-SV3 and DVP-SX3 series. The module mounts on the CPU’s left-side expansion bus and draws power from the CPU. Delta specifies 2 W power consumption.

DB9 wiring, bit rate and termination

The module supports DP-V0 cyclic data exchange. It automatically detects the network bit rate and supports rates from 9.6 kbit/s to 12 Mbit/s. On the PROFIBUS DB9 connector, pin 3 is B (+), pin 8 is A (−), pin 5 is DGND and pin 6 is VP. VP supplies the connector’s termination circuit.

On an industrial communication network, cable length depends on the selected bit rate. Delta specifies segment lengths of 1,000 m at 187.5 kbit/s, 400 m at 500 kbit/s and 100 m at 12 Mbit/s. Use shielded twisted-pair PROFIBUS cable and enable termination at both physical ends of the segment. Route the bus cable away from power wiring. Checking the shield connection and grounding helps diagnose interruptions caused by electromagnetic interference, especially when motor drives switch on.

Station address and DELA0AFE.GSD

The two front rotary switches set the station address in hexadecimal. Valid settings are 01–7D hex (1–125). For station 26, set the high digit to 1 and the low digit to A. Set the address with power off and use the same station number in the master project.

Import DELA0AFE.GSD into the master’s hardware configuration. The module’s identification number is 0x0AFE. Delta’s AH10PFBM-5A master example uses SYCON.net. In the Siemens SIMATIC 300 example, the GSD is installed through STEP 7 HW Config. When selecting I/O lengths, allow 2 bytes per word. The module supports up to 100 words in each direction, depending on the configuration.

PLC data addresses for the first left-side slot

For DVP-SV and DVP-SX2, a DVPPF02-SL in the first left-side slot receives data from the master in D6000–D6099, sends data to the master from D6250–D6349 and reports its status in D6100.

For DVP-SV3 and DVP-SX3, the first left-side slot uses D16000–D16099 for data from the master, D16250–D16349 for data to the master and D16100 for status. Label the data direction at both ends of the project. The master’s output is data received by the slave PLC. The master’s input is data sent by the slave PLC. If the module is moved to another slot, use the address range for that position.

PLC programming software and cable

Download the PLC program to the host CPU. For a classic DVP CPU, choose a supported version of WPLSoft or ISPSoft. Configure the ISPSoft connection through COMMGR. For example, use the UC-PRG015-01A for the SX2 mini-USB port or the UC-PRG020-12A for a compatible COM1 RS-232 port. For SV3/SX3, use DIADesigner and the CPU’s supported USB or Ethernet connection.

Editor’s Note

When buying a used unit, check the DVPPF02-SL label, side expansion clip, DB9 pins and both address switches.

Before removal, photograph the address switch settings and the termination switch on the PROFIBUS plug.

If POWER is off, start with the CPU supply and side expansion connection. A red NET LED means the connection to the master is down. A displayed F4 code also indicates loss of the master connection.

For F0, check the station address. F5 indicates a parameter error and F9 indicates a configuration error. Compare the GSD identification number and the selected input and output lengths in the master project.

On the bench, trace a known test word in each direction. In the classic first-slot arrangement, verify incoming data in D6000 and outgoing data in D6250.

Related modules and topics

The DVPPF01-S and DVPPF02-H2 are related Delta PROFIBUS products. In the Slim left-side range, the DVPEN01-SL provides Ethernet and the DVPCOPM-SL provides CANopen. See the PROFIBUS FAQ for network and wiring topics.

Manual and wiring diagram

The DVP Series Module Manual, section 13.4 covers DB9 pin assignments, bit rates and distances, and the register areas for each left-side position. See Delta DVP PLC files for the series documentation.

DVPPF02-SL · DVP Slim communication modules · Delta DVP PLC series · Used Delta PLC models · Delta Automation