Delta TAP-CN03

Delta TAP-CN03

Delta TAP-CN03 is a DeviceNet/CANopen distribution box connecting a trunk to RJ45 drops. It provides physical connections between terminal-block trunk wiring and suitable RJ45 CAN connections, with a switchable 121 Ω terminating resistor. See Delta DVP other accessories and Delta PLC accessories for the associated product groups.

Two trunk connections and three RJ45 drops

TB1 and TB2 connect the two trunk sections. TB3, TB4 and TB5 provide three RJ45 drop connections. These share the CAN bus rather than forming separate Ethernet channels. Delta's cable guide identifies a 5.08 mm removable terminal block for trunk wiring.

TAP-CN03 is not an Ethernet switch or a DeviceNet-to-CANopen protocol converter. An RJ45 socket does not establish Ethernet compatibility. Verify the equipment port and cable pin assignments before connection; do not connect it to a computer or Ethernet switch based on connector appearance.

Terminal and RJ45 pin assignments

Trunk terminal labels identify V−: 0 V, L: CAN_L, S: shield, H: CAN_H and V+: network power. Follow these labels and the manufacturer's wiring diagram.

The instruction sheet assigns RJ45 pins as 1: CAN_H, 2: CAN_L, 3 and 7: CAN_GND, 4 and 5: reserved, 6: CAN_SHLD, and 8: CAN_V+ / 24 VDC. Pay particular attention to pin 8 and verify which conductors the cable carries between the box and the connected device.

The series instruction sheet specifies 11–25 VDC DeviceNet network power and a 0–55 °C operating range, with mounting on a 35 mm DIN rail. Network power is carried through V+ and V−; check connected device voltage and current requirements separately.

121 Ω termination and drop length

Set internal termination ON when TAP-CN03 occupies a physical end of the trunk, and OFF at an intermediate position. Account for all termination at the two trunk ends. Do not add Delta TAP-TR01 at an end already terminated by the enabled internal resistor.

The box instruction sheet specifies a 6 m maximum drop cable length. The selected protocol, rate and overall network arrangement may require shorter drops. Three RJ45 sockets do not permit unrestricted star or tree networks.

Trunk and drop cables

Review UC-DN01Z-01A thick cable and UC-DN01Z-02A thin cable under Delta industrial network cables for applicable trunk and drop arrangements. Consider conductor sizes, communication distance and network voltage drop together.

Ready-made options for suitable RJ45 CAN connections include UC-CMC003-01A: 0.3 m, UC-CMC010-01A: 1 m, UC-CMC030-01A: 3 m and UC-CMC050-01A: 5 m. When selecting from Delta CANopen cables, check device pin assignments and the complete drop route.

Match network roles and port arrangements against documentation for CANopen modules such as DVPCOPM-SL and AH10COPM-5A, or DeviceNet modules such as DVPDNET-SL and AH10DNET-5A. TAP-CN03 does not change the protocol or parameter compatibility of connected equipment.

Differences from TAP-CN01 and TAP-CN02

Delta TAP-CN01 provides one terminal-block drop, while Delta TAP-CN02 provides three terminal-block drops. TAP-CN03 is distinguished by its three RJ45 drop connections. Select the box according to cable termination style as well as distribution requirements.

Editor's Note

Before inserting an available network cable, check the port label and wiring diagram. Pin 8 is defined as a power connection on this box. Confusing it with Ethernet can damage connected equipment as well as prevent communication.

Sketch where the trunk enters and continues before troubleshooting. Establish whether the box is at an end or an intermediate position before changing termination. Photograph existing settings and record the result of each change.

Remove power before resistance or continuity testing. With the box disconnected from the network, approximately 121 Ω should be present between CAN_H and CAN_L when termination is ON. Prevent other connected terminators from influencing an OFF-position check.

For a fault affecting one drop, start with its cable, plug latch and socket contacts. If the entire network fails, investigate trunk terminals, common power and termination as well. Check for stray shield strands shorting a signal terminal.

For a used box, inspect removable terminals, the DIN rail clip and termination switch. Investigate heat damage and added wire bridges. Where possible, test all three drops in turn using the correct cables and operating equipment.

PDF manuals and network configuration

Use Delta PLC accessories files for instructions and cable selection resources, and Delta PLC and HMI manuals for connected equipment documentation. TAP-CN03 itself does not require software loading. Use of Delta CANopen Builder or Delta DeviceNet Builder depends on the controller and modules in the network.

Related topics

Delta network connectors · Delta CANopen cables · Delta TAP-TR01 · Delta DVP other accessories

Return to Delta PLC accessories. Browse controllers in the Delta PLC category and available equipment under second-hand Delta products.

External references: Search the Delta Download Center using TAP-CN03 or TAP-CN01/02/03 for manufacturer documentation.