Delta TAP-CN02

Delta TAP-CN02

Delta TAP-CN02 is a passive distribution box joining trunk and drop cables in a DeviceNet or CANopen network. Delta catalogues describe it as “1 in / 4 out”. The manufacturer's wiring diagram assigns TB1 and TB2 to the trunk and TB3, TB4 and TB5 to three drops. The box includes a switch-selectable 121 Ω terminating resistor.

The input/output description does not mean separate PLC channels or independent network ports. Corresponding conductors share the same network connections; TAP-CN02 does not act as an active repeater, Ethernet switch or protocol converter. It belongs to Delta DVP other accessories and should be considered alongside CANopen cables and industrial network cables.

Trunk, drop and terminal arrangement

TB1: incoming trunk. TB2: continuing trunk. TB3–TB5: three drop connections. The catalogue's 1/4 arrangement therefore includes the continuing trunk and three drops. CAN communication is bidirectional; these terminals do not operate as a one-way electronic fan-out.

The manufacturer's cable guide shows removable terminal blocks with 5.08 mm pitch. Signal labels are V−: 0 V, L: CAN_L, S: shield, H: CAN_H and V+: network power. Terminal groups have different physical orientations. Follow the printed signal labels rather than counting positions from the left or right.

DeviceNet colours are black for V−, blue for CAN_L, white for CAN_H and red for V+, with the shield conductor connected to S. Check the end device's pin assignment separately. Similar housings among network connectors do not establish identical pinouts.

121 Ω termination switch

ON: the internal 121 Ω resistor is connected. OFF: the internal resistor is disconnected. The manufacturer's instructions specify ON when the box provides termination at the start or end of the network, and OFF when it is in the middle of the trunk. The resistor connects between CAN_H and CAN_L.

Plan termination at the trunk's two physical ends, rather than at every drop or device. Do not leave an additional terminator in parallel with the internal resistor at the same end. TAP-TR01 is a separate termination accessory; it does not provide TAP-CN02's distribution function, and connector compatibility must be checked.

Power, mounting and cable selection

The common TAP-CN01/02/03 instruction sheet specifies 11…25 VDC DeviceNet network power, supplied through the network cable. TAP-CN02 is not a power supply. It mounts on a 35 mm DIN rail; specified operating temperature is 0…55 °C, with storage at −25…70 °C. Protect the box inside the cabinet and support cables so they do not strain the removable terminals.

The manufacturer's diagram shows thick trunk cables and thin drops. When selecting UC-DN01Z-01A and UC-DN01Z-02A, consider conductor size, distance, network current and voltage drop. The TAP instruction sheet limits drop cables to 6 m. DeviceNet cumulative drop budgets at 125/250/500 kbit/s are respectively 156/78/39 m. CANopen may require shorter drops depending on its data rate and topology. The distribution box does not extend permissible network distance.

Differences from other TAP models

TAP-CN01 is listed as 1 in / 2 out with fewer connections. TAP-CN03 belongs to the 1 in / 4 out group and uses RJ45 drop connections. TAP-CN02 provides terminal-block drop connections. The RJ45 connections on CN03 must not be treated as Ethernet switch ports either.

Editor's Note

When buying a used box, inspect more than its green housing. Check that all removable terminals, the DIN rail clip and termination switch are present. An incomplete box should be assessed differently from a complete assembly.

For intermittent faults, draw the box's position in the network first. A TAP-CN02 in the middle of the trunk with termination left ON adds an unwanted resistor. Establish the number and location of terminators before replacing cables.

Measure resistance with network power removed. Two correctly connected 121 Ω terminators in parallel give approximately 60 Ω between CAN_H and CAN_L. This alone does not prove the entire network is healthy; it helps investigate missing or excessive termination.

Follow the printed H, L, S, V+ and V− labels. Viewing a plug from the opposite side can make the order misleading. Connecting power to a data terminal can affect attached devices as well as the distribution box.

If faults begin after adding a drop, check its length and the end device's current consumption and supply voltage. Having three physical drop connections does not permit three cables of any desired length.

Isolate power before correcting darkened terminals, loose screws or oxidised contacts. With cables disconnected, continuity checks can help identify open wiring; do not apply an insulation tester while device electronics remain connected. Check contacts, wiring and the switch first on this passive box.

Related network devices and software

With appropriate CANopen interfaces and wiring, related devices include DVPCOPM-SL, AS-FCOPM and AH10COPM-5A. DeviceNet examples include DVPDNET-SL, AS01DNET-A, AH10DNET-5A, RTU-DNET and AHRTU-DNET-5A. No node address or IP address is assigned to TAP-CN02 itself. CANopen Builder and DeviceNet Builder configure connected network devices; software is not installed in the box.

PDF manuals and wiring diagrams

Use our Delta PLC accessories PDF and software files page for installation and cable documentation. General documents are available under Delta PLC and HMI manuals. Read the TAP-CN01/02/03 Instruction Sheet alongside the distribution box circuit diagrams in the Delta PLC/HMI Cable Selection Guide.

Related subjects

TAP-CN01 · TAP-CN03 · TAP-TR01 · UC-DN01Z-01A · UC-DN01Z-02A · CANopen cables · Industrial network cables · Network connectors

Navigation: Delta DVP other accessories · Delta PLC accessories · Delta DVP PLC series · Delta AS PLC series · Delta AH PLC series · Delta PLC models · Used Delta products · PDF and software files

External references

Delta TAP-CN01/02/03 installation instructions – archived manufacturer document · Delta PLC/HMI Cable Selection Guide – TAP-CN02 circuit diagram · Delta AH catalogue – distribution boxes · ODVA DeviceNet Technology Overview – drop lengths and topology