Delta AHRTU-DNET-5A

Delta AHRTU-DNET-5A DeviceNet Remote I/O Module

The Delta AHRTU-DNET-5A connects Delta AH500 I/O modules to a DeviceNet network. It sends remote input data to the scanner and passes received output data to the installed modules. For example, a remote station can connect the sensors and valves at the end of a conveyor while the main-panel CPU runs the PLC program.

The AHRTU-DNET-5A mounts in the CPU slot of the remote main rack. On the main PLC side, the AH10DNET-5A can serve as the DeviceNet scanner (master). The AHRTU-PFBS-5A is the remote I/O module for PROFIBUS DP installations.

Installation sheet and module manual

AHRTU-DNET-5A installation and pinout sheet (PDF) · Includes English and Turkish sections. Delta document 5012608103 · 2 pages.

Delta AH500 Module Manual (PDF) · English. Chapter 11 starts on PDF page 452 and covers installation, I/O mapping and diagnostics. All Delta AH PLC PDF files.

Specifications and wiring

Network and address. CAN-based DeviceNet supports I/O polling and explicit messaging. Two rotary switches set the node address from 00 to 63. The DR1/DR0 settings are OFF/OFF = 125 kbps, OFF/ON = 250 kbps and ON/OFF = 500 kbps. Setting both switches to ON selects extended-rate mode. Set the rate in DeviceNet Builder, up to 1 Mbps. Address and speed changes take effect after a power cycle.

DeviceNet port. Removable five-pin connector with 5.08 mm pitch. The sheet identifies pin 1 V+ (red), pin 2 CAN_H (white), pin 3 shield, pin 4 CAN_L (blue), pin 5 V− (black). The network side takes 11–25 V DC. The manual lists 60 mA. The remote rack has a dedicated power supply. Delta shows the AHPS05-5A in the main rack’s POWER slot.

Rack and I/O capacity. The station supports one main rack, up to seven expansion racks and up to 68 AH500 I/O modules in total. Delta lists a maximum of 980 bytes each for input and output. Check the scanner’s own I/O mapping limits for the project. Supported models include digital I/O, analog I/O and temperature measurement modules. If used, the AH10SCM-5A occupies an I/O slot on the remote main rack.

Software and commissioning

Open the main PLC project in ISPSoft. Configure the PC-to-PLC connection in COMMGR. Use DeviceNet Builder to check the network scan, remote rack module order and input/output byte mapping. If the scanner needs a device description, see EDS device files. Compare the PLC program addresses with the scanner’s configuration. Delta PLC software.

Editor’s Note

Before replacing the module, photograph the old nameplate, both address dials and all DIP switch settings.

On a used module, check the backplane connector and mounting clip as well as the five-pin plug. Look for bent pins and play in the connector.

If the scanner cannot see the module, check the voltage between V+ and V−, look for duplicate addresses and confirm that the bit rate matches the scanner.

MS reports module status and NS reports network status. Record both LEDs and the seven-segment code when diagnosing a fault.

On the bench, check that a test input appears at the expected PLC address. Then confirm an output with a controlled test load. Check output behavior during a network interruption with the load in a safe state.

Related topics

AH communication modules · AH expansion modules · Delta PLC accessories · Delta device description files · AH10COPM-5A CANopen module.

Delta AH PLC series · Delta PLC models · Second-hand Delta · Second-hand automation.