Delta TAP-TR01 — RJ45 CANopen / DeviceNet Terminating Resistor

Delta TAP-TR01 is an RJ45 terminator for compatible CANopen and DeviceNet connections. Delta’s cable selection guide specifies 121 Ω. This passive component in the Delta DVP other accessories range helps match the data line at its ends and reduce signal reflections.

TAP-TR01 is not a communication card or signal repeater and needs no station address or software installation. Its RJ45 housing does not make it suitable for Ethernet, PROFINET or EtherCAT ports. Verify the network protocol and pin assignment in the connected device’s documentation.

Where to install termination

Fit one termination at each physical end of the CAN trunk. Do not terminate every station or unused socket. DeviceNet also requires termination at both trunk ends, with no additional termination at drop-line ends. The logical master is not necessarily located at a physical end.

In Delta’s example, the starting end can use a distribution box’s internal termination switched ON, with TAP-TR01 at the other end. When using TAP-CN01, TAP-CN02 or TAP-CN03, do not add a second terminator at a point where internal termination is already enabled.

RJ45 pins and connection checks

The CANopen RJ45 assignment in Delta’s DVP-MC manual identifies pin 1 as CAN_H and pin 2 as CAN_L. Assess termination between these data lines. Do not assume this assignment for a different device or adapter; follow its manufacturer’s pin diagram and connector viewing direction.

UN-03EN-04A is an RJ45 adapter, whereas TAP-TR01 provides termination. When selecting Delta network connectors, distinguish mechanical connection from electrical termination. Delta documents list TAP-TR02 as a different, 150 Ω terminator; similar appearance does not make it a TAP-TR01 replacement.

The approximate 60 Ω multimeter check

Disconnect network and device power before resistance testing. A measurement between CAN_H and CAN_L includes the parallel effect of connected terminators. The values below are calculated for an ideal circuit containing only the stated resistors; cable resistance and connected electronics can affect actual readings.

Measurement arrangement Ideal resistance Meaning
One TAP-TR01 disconnected from the network 121 Ω Individual terminator check
Two 121 Ω terminators on the line 60.5 Ω Two terminators in parallel
Three 121 Ω terminators on the line About 40.3 Ω Example of excessive termination

About 120–121 Ω on the line can suggest one termination or a cable break. About 60 Ω does not prove that the complete network is healthy. Treat resistance measurement as an initial check; investigate cable continuity, shielding, topology and signal quality if communication faults remain.

Related cables and network components

The Delta CANopen cable range includes RJ45 options such as UC-CMC003-01A, UC-CMC010-01A, UC-CMC030-01A and UC-CMC050-01A. Field cables such as UC-DN01Z-01A and UC-DN01Z-02A can be reviewed under industrial network cables. Select cable against the physical network design.

Related controller-side pages include DVPCOPM-SL for DVP PLCs, AS-FCOPM for AS PLCs and AH10COPM-5A for AH PLCs. These links do not imply direct TAP-TR01 connection to every module; verify its terminal or RJ45 arrangement separately.

Editor’s Note

An intermittent network fault can come down to this small component. Identify the actual start and finish of the cable first; the last device physically arranged in a cabinet may not be the end of the trunk.

A 60 Ω reading is not a complete health certificate. It indicates a parallel resistance condition; loose connectors, poor shield contact or an incorrect baud rate can still disrupt communication.

Do not measure resistance on a powered network. Disconnect a suspect TAP-TR01 and test it individually to avoid confusing its value with other terminations on the line.

If trouble started after a distribution box was added, check its internal termination switch. An unintended third terminator creates loading that replacing a healthy cable will not fix.

Do not keep using a terminator with a broken RJ45 latch or corroded contacts merely because its resistance is correct. A plug that passes a stationary bench check can disconnect under vibration.

Adding a resistor to unidentified pins or bridging the data lines is not a repair. Establish the pin assignment, then check the cable and terminator separately. Correct termination cannot resolve duplicate addresses or poor cable routing.