Delta AH10COPM-5A
Delta AH10COPM-5A CANopen communication module
The Delta AH10COPM-5A is a rack-mounted module that connects a Delta AH500 PLC to a CANopen network. It can operate as a master or slave and exchange data with CANopen drives and remote I/O stations. It supports PDO, SDO, SYNC, EMCY and NMT messages.
Bit rate, node address and terminals
Use the DR2, DR1 and DR0 switches to select 10, 20, 50, 125, 250, 500 or 800 kbit/s, or 1 Mbit/s. Delta specifies maximum bus lengths of 100 m at 500 kbit/s and 25 m at 1 Mbit/s. The two rotary switches set the node address from 01 to 7F hex (1 to 127). Cycle power to the module after changing the address or bit rate.
The removable five-position connector is wired 1 GND · 2 CAN− (CAN_L) · 3 SHLD · 4 CAN+ (CAN_H) · 5 reserved. The module receives 24 V DC from the rack’s internal bus.
ISPSoft and CANopen Builder
Set the module slot and master/slave role in HWCONFIG in ISPSoft. In master mode, configure the network with CANopen Builder. Check the device’s EDS file and PDO mapping, then compare the PLC D-register addresses with the project. For the PC connection, use the PLC cable and COMMGR settings that match the CPU programming port.
Manuals
AH500 Module Manual, Chapter 15 (English, master/slave, CANopen Builder and PDO) · AH500 Hardware & Operation Manual, section 4.11.6 (English, terminal and switch diagrams).
Editor’s Note
When buying a used module, check that the removable five-position plug is included.
Before replacing the card, record the old node address and DIP switch settings, and save the network project.
Start with a known CANopen device. Check the bit rate, node address and termination at both ends of the bus.
If the node appears but the PLC data does not change, check the NMT state, PDO length and D-register mapping.
If the ERROR LED comes on, look up the error code. 16#A0B1 indicates that the received PDO length differs from the configured length.
Related topics
Within the AH family, the AH10DNET-5A supports DeviceNet, the AH10PFBM-5A and AH10PFBS-5A support PROFIBUS, and the AH15SCM-5A handles serial communication. Ethernet options include the AH10EN-5A and AH15EN-5A. For CANopen on the AS series, see the AS-FCOPM.
AH communication modules · AH expansion modules · Delta AH PLC series · Delta PLC accessories · Delta PLC · Second-hand Delta models
External reference · Delta AH10COPM-5A Module Manual, Chapter 15