Delta AH15SCM-5A dual RS-232 serial communication module

The Delta AH15SCM-5A is a backplane-mounted, two-port serial communication module for the Delta AH500 PLC family. COM1 and COM2 provide RS-232 connections through 9-pin DB9 connectors. Typical applications include data exchange with serial measuring instruments, barcode readers or existing control devices. Check the remote device’s protocol and cable pinout for each application.

Ports, protocols and DB9 pinout

Serial rate and framing. Selectable rates range from 1,200 to 115,200 bit/s. The module supports 7 or 8 data bits, 1 or 2 stop bits, and no, odd or even parity. Protocols include Modbus RTU, Modbus ASCII and UD Link.

On both DB9 ports, pin 2 is TX, pin 3 is RX and pin 5 is GND. The instruction sheet marks the remaining pins N/C. Check TX and RX on the remote device before selecting the cable. The AH10SCM-5A model uses RS-485/RS-422 ports.

Backplane and power. The module is rated for 5 V DC, with a documented 500 V AC isolation rating and a weight of 150 g. Verify the CPU, firmware, backplane and slot before replacing a module. See Delta AH power supplies and Delta PLC accessories for system components.

Commissioning in ISPSoft

Check the physical slot and port in HWCONFIG within Delta ISPSoft. For Modbus, match the rate, data bits, parity and stop bits at both ends. Check UD Link settings in SCMSoft. For 16#A804 port communication errors or 16#A808 Modbus errors, start with the cable and HWCONFIG settings.

Installation and pinout PDF

Delta AH15SCM-5A instruction sheet and DB9 pinout (PDF) · English and Turkish sections · 24 October 2016 · 2 pages. For family manuals, see Delta AH PLC PDF files.

Editor’s Note

When buying a used unit, check the full AH15SCM-5A label and inspect both DB9 connectors.
Bench-test COM1 and COM2 separately with a cable whose pinout you know.
Start with a read request to a single device so you can see which port actually receives a reply.
If TX is active and RX stays quiet, check the remote device settings and the cable’s TX/RX routing.
Before replacing the module, back up the ISPSoft project and record the working port settings.

Related topics

Ethernet options include AH10EN-5A and AH15EN-5A. Fieldbus modules include AH10DNET-5A, AH10PFBM-5A, AH10PFBS-5A and AH10COPM-5A.

For remote I/O, see AHRTU-DNET-5A and AHRTU-ETHN-5A. For serial communications, see the Modbus FAQ.

AH expansion modules · Delta PLC software · Delta PLC · Second-hand Delta automation equipment

External references · Delta AH15SCM-5A instruction sheet · Delta AH500 hardware and operation manual