Delta AH10SCM-5A

Delta AH10SCM-5A Dual-Port Serial Communication Module

The Delta AH10SCM-5A is a communication module that adds two RS-485/RS-422 serial ports to the Delta AH500 PLC system. COM1 and COM2 can exchange serial data with drives, power meters and measuring instruments. The specified maximum line rate is 460.8 kbit/s, with 1.2 W internal power consumption.

Ports, protocols and model selection

The module supports Modbus RTU/ASCII master and slave operation, Delta PLC Link and UD Link for user-defined message formats. The AH10SCM-5A uses removable terminals for differential serial links. For RS-232 applications with DB9 connectors, see the AH15SCM-5A. Check rack compatibility alongside the AH expansion modules and AH power supplies.

Terminal wiring and software

RS-485 uses the D+ and D− terminals. RS-422 uses separate TX+/TX− and RX+/RX− pairs. Each port has its own termination switch. TR1 serves COM1 and TR2 serves COM2. Set each switch according to the physical layout of its serial line.

Add the module to the rack in HWCONFIG in ISPSoft. Match baud rate, data bits, parity, stop bits and the Modbus station address to the connected device. Use SCMSoft for custom UD Link messages. See Delta PLC software for engineering tools.

Instruction sheet and PDF files

AH10SCM-5A instruction sheet and terminal pinout · Includes English and Turkish text. Page 2 shows the COM1/COM2 terminals and the TR1/TR2 switches. Browse the series documentation under Delta AH PLC PDF files.

Editor’s Note

When buying used, verify the AH10SCM-5A nameplate and check that both removable terminal blocks are present.
Inspect the TR1 and TR2 switches and the rear backplane connector.
On the bench, start by testing COM1 with a Modbus device whose address and serial settings you know.
Use the same device to test COM2 and confirm a valid response on both ports.
If TX flashes without an RX response, check D+/D− polarity, the station address and parity before removing the module.