Delta AH power supplies
Delta AH Power Supplies – AHPS05-5A and AHPS15-5A
Delta AH power supplies provide system power to AH-series PLC rack modules through the backplane. The two main models covered here are AHPS05-5A and AHPS15-5A. Select the supply by input power, total rack consumption and backplane configuration. See Delta AH PLC series and Delta AH500 for the system context.
AHPS modules supply the PLC's internal system; calculate power for sensors, valves and other field loads separately. In particular, VS+ / VS− are external DC supply-monitoring inputs, rather than general-purpose 24 V output terminals. Keep system power and field-power duties separate when selecting Delta PLC accessories.
Differences between AHPS05-5A and AHPS15-5A
AHPS05-5A: Uses a nominal 100–240 V AC, 50/60 Hz input and provides up to 24 V DC, 2.5 A / 60 W for the rack. Connect AC input to L and N. Distinguish these terminals from the external 24 V monitoring inputs.
AHPS15-5A: Uses a nominal 24 V DC input, with a rack output capacity of 24 V DC, 1.5 A / 36 W. Input terminals are +24V and 24G. Include the AHPS15 input demand when sizing the upstream DC supply.
Catalog dimensions for both models are 110 mm high × 50 mm wide × 103 mm deep. Matching dimensions do not establish matching input type or power capacity. Do not interpret the “-5A” model suffix as a 5-amp output rating.
Rack power budget and backplane selection
Add the documented internal consumption of the CPU, backplane and installed modules. Delta AH expansion modules, AH digital modules, AH analog modules and AH communication modules do not all consume the same power. Account separately for external field-power consumption.
Plan standard main and extension rack supplies according to the applicable backplane instructions. Special arrangements exist among Delta AH Motion backplanes; for example, the catalog specifies that AHBP00M2-5A does not require a separate AH power module. Avoid applying one power-module arrangement to every AH backplane.
Power redundancy in a Delta AH500 redundant PLC system requires a supporting backplane. The catalog identifies redundant-power support for AHBPxxMR1-5A main and AHBPxxER1-5A extension backplanes. CPU redundancy, such as that provided by AHCPU560-EN2, and power-supply redundancy are separate system functions.
Terminals, monitoring and commissioning
Connect VS+ and VS− to the positive and negative terminals of the external 24 V DC supply being monitored. A compatible CPU and program can use diagnostic/interrupt functions to respond to an abnormal supply. NC is unconnected. Follow the model-specific drawing for grounding and input wiring.
When reviewing Delta AH external terminals and Delta AH I/O cables, trace the field-load current path as well. Rack power capacity and the load rating of a digital output describe different electrical limits.
AHPS power supplies do not require a PLC program download. Use Delta ISPSoft for the CPU project and system diagnostics when needed, with Delta COMMGR for an appropriate PC connection. The POWER indicator helps show supply status; complete verification requires measurements at appropriate points under load.
Editor's Note
Read the label first: AHPS05 has an AC input, while AHPS15 has a DC input. Similar enclosures are no reason to transfer the wiring unchanged. Photograph the full label and input terminals before disconnecting anything.
A lit POWER indicator alone does not prove that the unit is healthy. A supply can appear normal without load and sag when powering the rack. Test through a suitable backplane or the manufacturer's specified test connection; do not connect a test load to VS terminals.
For intermittent CPU resets, inspect input power, rack connections and loaded supply behavior before replacing the CPU. If the problem begins when a module is added, check both the total power budget and that module's condition.
Measure the external 24 V supply and AHPS separately when field power drops. A sensor or valve supply fault can produce a system indication through the VS monitoring circuit. Also inspect loose terminals, corrosion and the common return path.
A repair assessment may include heat discoloration, damaged capacitors and rack-connector damage. Before working on the AC model's primary side, isolate power and verify that stored capacitor voltage has discharged. Do not replace a fuse with a higher rating to suppress the symptom.
In a redundant installation, one working supply does not prove that both are healthy. Check each supply and load transfer according to the system maintenance procedure. Determine whether live replacement is permitted from the exact power-module and backplane instructions.
Sources, PDF and software files
The document hub for this section is Delta PLC accessories PDF and software files. Use the power-supply section of the AH500 hardware manual for terminal drawings, rack arrangement and electrical limits. Other documents are available under Delta PLC and HMI manuals.
Related topics
Power arrangements for other PLC families: Delta DVP power supplies · Delta AS power supplies. These groups should not be treated as direct replacements for AH rack supplies. General document collection: Delta user manuals.
Navigation: Delta PLC accessories · Delta AH PLC series · Delta PLC models · Second-hand Delta products
External references
Delta AH manufacturer catalog (English) · AH500 hardware manual – power-supply specifications, external archive copy · AHPS terminal definitions, external archive copy