Delta AS power supplies
Delta AS Power Supplies
Delta AS power supplies provide 24 V DC for CPUs and modules in Delta AS PLC systems. The principal models on this page under Delta PLC accessories are AS-PS02 and AS-PS02A. Both accept AC mains; their main difference is the current allocated to internal and external loads.
Do not treat AS-PS02 and AS-PS02A as interchangeable supplies differing only by a suffix. Calculate CPU/module consumption separately from field-device consumption. A shared 24 V rating does not mean that every output provides the same current.
AS-PS02 versus AS-PS02A
| Model | 24 V DC for CPU and modules | External 24 V DC output | Power allocation |
|---|---|---|---|
| AS-PS02 | 2 A | Not allocated for external use | 48 W internal |
| AS-PS02A | 1.5 A | 0.5 A | 36 W internal + 12 W external |
AS-PS02: its 24 V DC, 2 A capacity is allocated to the CPU and internal modules. AS-PS02A: its limits are 1.5 A for the CPU/modules and 0.5 A for external use. The AS-PS02A’s combined 48 W rating does not establish a 2 A internal output.
For example, a CPU/module load of 1.7 A exceeds the AS-PS02A’s 1.5 A internal limit. Leaving the external output unused does not automatically increase that limit to 2 A. Calculate each output against its own rating.
AC input and external output terminals
The nominal input is 100–240 V AC, 50/60 Hz. L is line, N neutral and LG protective earth. The AS-PS02A external DC output uses +24V and 24G terminals. Treat DC return and protective earth according to their respective functions.
Read terminal functions from the drawing for the complete model. Confusing AC mains input with the external DC output causes serious damage. Do not interchange internal-system and external-field supply connections without checking their terminals and current ratings.
Calculating CPU, module and field loads
For an AS200 or AS300 system, add the CPU consumption to the internal requirements of connected AS expansion modules. Other controllers, including AS500 motion controllers, require assessment against their own hardware and power-distribution specifications; family names alone do not establish supply suitability.
Before connecting sensors or auxiliary circuits to the external 0.5 A output, consider their combined continuous and starting currents. If a panel such as TP04P or TP70P is to use that output, include its own consumption alongside the other loads. Provide an appropriate separate supply arrangement when capacity is insufficient.
Field power for PLC inputs, output loads and analogue circuits is a separate part of the budget from internal module consumption. Allocate valve and contactor coil currents to the correct supply. Do not combine outputs from separate sources without a manufacturer-approved arrangement.
Protection and cabinet installation
The manufacturer specifies short-circuit and overcurrent protection for the 24 V DC outputs. Protection does not permit continuous overload. Design input protection, field-branch fusing, conductor sizes and grounding separately.
Secure the module according to the system mounting arrangement and check the DIN-rail latch, connections and cooling clearances. Consider terminal access, cable strain and airflow when reviewing external terminals and HMI mounting and power connections. Assess loaded voltage and cabinet temperature together.
Other AS power products
The manufacturer’s catalogue also lists AS-PS03C as a different product with 24 V DC/3 A for external I/O and RS-485 power-monitoring functions. AS-ATXB is an adapter that facilitates external-supply connections; it is not independently an AC/DC power supply equivalent to AS-PS02.
Select Delta DVP power supplies and Delta AH power supplies against their own power-distribution systems. A shared brand or nominal output voltage does not establish identical connections, internal power delivery or mechanical installation.
Software and replacement preparation
AS-PS02 and AS-PS02A do not receive a downloaded PLC program. Before replacement, record the power budget, nameplate, terminal photographs and installed arrangement. Although replacing the supply does not itself require changing the PLC program, recommission the machine under controlled conditions. Check monitoring-capable power products against their own configuration documentation.
Editor's Note
Pay attention to the A suffix. Replacing AS-PS02 with AS-PS02A can change the available capacity when the internal load approaches 2 A. Check the internal supply and external 0.5 A output separately rather than relying on combined wattage.
An illuminated POWER indicator does not prove that every supply path is healthy. Observe voltage stability while the CPU and modules start, and while external loads switch. On AS-PS02A, a functioning external output alone does not establish a healthy internal power connection.
For resets or intermittent shutdowns, inspect loads and connections first. Loose terminals, contaminated contacts, excessive load and cabinet heat can produce similar symptoms. Isolate power safely before disconnecting modules, and change only one item at a time while recording the result.
When buying a used unit, request clear photographs of the complete nameplate, connectors and rail latch. Test both internal power delivery and any external output on a suitable setup. An unloaded 24 V measurement alone does not establish condition under load.
Investigate burn marks, hot terminals and capacitor deterioration separately. Disconnect mains and verify that capacitors are discharged before opening the unit. Never bridge fuses or protection circuits. After component replacement, check output stability again with a suitable load.
Label L, N, LG and external DC conductors before removal. Do not transfer wiring from memory. Complete the final test with the CPU, modules and field loads operating normally, including startup and simultaneous coil switching.
PDF and technical files
The document hub is Delta PLC accessories files. Further documents are available through Delta PLC and HMI manuals and Delta user manuals. Select the correct model column in the AS hardware manual’s power supply specifications and terminal profiles sections.
Related topics
Delta DVP programming cables · Delta DVP communication cables
Navigation: Delta AS PLC series · Delta PLC accessories · Delta PLC main group · Used Delta products
External references
Delta AS Series Hardware and Operation Manual — English · Delta AS catalogue — power supply selection table, English