Delta AS-PS02 24 V DC 2 A PLC Power Supply

Delta AS-PS02 is a power supply module for the Delta AS PLC series, with 100–240 V AC, 50/60 Hz input and 24 V DC, 2 A / 48 W output. Its output capacity supplies the CPU and modules internally. It belongs to the Delta AS power supplies group.

Difference between AS-PS02 and AS-PS02A

AS-PS02 provides 2 A for internal supply. AS-PS02A divides its capacity into 1.5 A / 36 W internally and 0.5 A / 12 W externally. The A model's +24V and 24G external output terminals are absent on AS-PS02.

Before replacement, check the system's internal current requirement and external supply connections. Treat the A suffix as part of the complete ordering code.

Power connections and installation

L: AC line input; N: neutral; LG: line ground. Power reaches the AS CPU through the module's side power connection. Mount the module on a DIN rail and disconnect power before connecting or removing it.

The manufacturer's drawing shows dimensions including projections of 77.9 × 98.3 × 91.5 mm. Allow additional space for terminal access and ventilation. Install the module inside a suitable protective enclosure.

The 24 V DC output includes short-circuit and overcurrent protection. If protection operates, investigate the load and wiring rather than repeatedly cycling power.

CPU and expansion-module current budget

When building an AS200 or AS300 system, add the internal consumption of the CPU and installed modules. With CPUs such as AS332T-A, AS332P-A and AS324MT-A, select by complete equipment code and system load.

Check the applicable consumption tables for AS expansion modules, including digital modules, analogue / measurement modules, special modules and function cards. Module count alone does not establish an adequate power supply.

For I/O modules such as AS32AM10N-A and AS32AN02T-A, assess internal electronics and field-load supplies separately. Supply sensors, valves and other loads according to their own wiring diagrams.

Editor's Note

Compare the label and terminal arrangement first. AS-PS02 and AS-PS02A look similar. When buying used, request photographs of the front label, input terminal and side connection together.

A green indicator does not complete the test. Verify stable operation with the intended CPU and modules connected. Watch for resets during startup and load changes rather than relying solely on an unloaded test.

Investigate power before changing a repeatedly restarting CPU's program. Loose input wiring, poor side-connector contact and overload can produce similar symptoms. Check the supply arrangement first.

Recalculate consumption when adding modules. Total their internal requirements and examine field supplies separately. Do not attempt to resolve insufficient capacity by arbitrarily paralleling power supplies.

Inspect heat damage, capacitors and solder joints during workshop servicing. Disconnect power and measure to confirm that stored voltage has discharged before internal inspection. Capacitors can age without bulging; repairs require a subsequent stability test under load.

Separate supply faults from load faults when protection operates. Disconnect modules only with power removed, recording their connections. Repair burnt or loose connectors before installing another power supply.

PDF installation documents and software

Use our Delta PLC accessories PDF and software files page for documentation. Consult Power Supply Module Specifications in the AS Series Hardware and Operation Manual and the wiring drawings in the AS-PS02 / AS-PS02A Instruction Sheet.

For PLC programming and diagnosis, use a CPU-supported ISPSoft version. Back up the existing program and fault records while investigating power problems.