Delta AS-PS02A

Delta AS-PS02A is an AS-series PLC power supply converting 100–240 V AC, 50/60 Hz input to 24 V DC. Its output capacity is allocated as 1.5 A for the CPU and modules and 0.5 A for external use. Check these two current budgets separately when selecting the supply.

Internal and external power budgets

The internal section corresponds to 36 W, and the external section to 12 W. Do not treat their combined capacity as a single 2 A external output. Assess CPU and installed-module consumption against the internal budget, and sensors, auxiliary relays and other field devices against the external budget.

Include devices operating simultaneously and their starting behaviour in the external-load assessment. If another supply is required, arrange its connections according to the machine's electrical design. Compare options under Delta AS power supplies.

Difference from AS-PS02

The manufacturer specifies 2 A for internal use for Delta AS-PS02. AS-PS02A instead allocates capacity between internal and external use. During replacement, check the A suffix, any connected external load and total CPU/module consumption together. Total wattage alone does not establish interchangeability.

Assessing CPU and module consumption

For Delta AS200 and Delta AS300 projects within the Delta AS PLC series, calculate consumption using the complete CPU code. Do not assume identical field loads for CPUs with different output arrangements, such as AS228T-A, AS228P-A and AS228R-A. For projects using AS332T-A or AS332P-A, record CPU consumption separately from the supply path for output loads.

When adding Delta AS expansion modules, total the documented consumption of AS digital modules, AS analog / measurement modules, AS specialty modules and AS function cards. Keep internal and field-supply consumption separate. Update this calculation when investigating restarts or voltage drops appearing after a module has been added.

Terminal functions and connections

The manufacturer drawing identifies L/N: AC input, LG: line ground and +24V and 24G: external DC output. 24G is the DC return. Verify terminal order from the unit's own markings and distinguish the AC-input and DC-output functions.

Disconnect power and verify absence of voltage before making connections. Inspect the removable terminal block, the power connector to the AS system and mounting retainers. Prepare conductors appropriately and keep loose strands clear of adjacent terminals.

Installation, protection and field checks

Use the manufacturer outline drawing to allow for the housing, terminal projections and side power connection. Avoid crowded installation that obstructs ventilation or places the supply against heat sources. Output short-circuit and overcurrent protection does not replace a load calculation.

During commissioning, check the supply first and introduce loads in a planned sequence. Measure voltage with the CPU and field equipment operating as well as without load. Investigate intermittent shutdowns by checking input power, external loads and module connections together.

PDF and technical documentation

Start document selection at Delta PLC accessories files. In the 2018 AS Series Operation Manual, printed pages 2-68–2-70 / PDF pages 97–99 cover power ratings, the housing and terminals; printed page 4-5 / PDF page 114 shows supply wiring. Match document coverage to the complete hardware label.

Editor's Note

Read the A suffix on the label first. Photograph the old supply and record devices connected to its external output. Do not add internal and field capacity together and treat them as one freely available output.

A lit POWER indicator does not complete the test. Measure the DC output under load and observe voltage when the CPU restarts or relays operate. A supply that looks normal without load may behave differently in operation.

If the external output collapses, isolate field branches systematically. Disconnect branches with power off, then establish which branch triggers the fault when introduced. Distinguish a damaged sensor cable or faulty relay coil from a supply fault.

Do not increase a blown fuse rating as a repair. Check its type and rating against the device documentation. With power disconnected, inspect for input-stage shorts and burn damage. Replacing a fuse alone does not establish a completed repair.

Complete testing of a used supply with the machine load. Observe terminal looseness, excessive heating and intermittent shutdowns. Record the result together with the CPU, installed modules and external loads used during testing.