Delta AS specialty modules

Delta AS specialty modules

Delta AS specialty modules add serial communications, DeviceNet, pulse-based positioning and IO-Link connectivity to AS PLC systems. For network stations, select the protocol and operating mode. For motion axes, match the output circuit and pulse frequency to the drive.

Communications and remote I/O

The AS00SCM-A is a communication module with two function-card slots. In COM mode, the AS-F232, AS-F422 or AS-F485 card provides the corresponding serial interface. RTU mode supports a remote I/O station. Check the supported protocol, slot and firmware for the installed card.

The AS01DNET-A is a DeviceNet communication module. It can operate as a master (scanner) or slave on the PLC, or as a remote I/O station in RTU mode. Check the EDS files and scan list in DeviceNet Builder.

Pulse-based positioning

The AS02PU-A provides 5 V differential pulse outputs for two axes at up to 200 kHz. It also has one A/B/Z differential encoder input.

The AS04PU-A provides NPN open-collector pulse outputs for four axes at up to 100 kHz. On feed, cutting or positioning axes, match the drive’s pulse input to the selected module’s output circuit.

IO-Link field devices

The AS04SIL-A is a four-port IO-Link master. It gives the PLC access to process data and diagnostics from compatible sensors and actuators. Ports can be configured for IO-Link or standard digital SIO operation. Match the IODD file to the exact device and revision.

Software and manuals

Check the exact AS200 or AS300 CPU code and firmware. Add the module in its physical position in ISPSoft HWCONFIG. Open the CPU connection through COMMGR for online checks. Delta AS PLC PDF files · Delta PLC and HMI manuals

Editor’s Note

For a used module, inspect photos of the label, terminal blocks and side expansion connector.

Save the PLC project, module order and addresses before replacement.

Record the communication module’s operating mode and network address. For DeviceNet, also save the scan list.

For positioning, verify the drive’s pulse input type and limit signals first.

Start IO-Link commissioning with one port and one device. Read its process data and diagnostics in the PLC.