Delta AS00SCM-A
Delta AS00SCM-A communication module
Delta AS00SCM-A is a Delta AS PLC communication extension module with two function card slots. The fitted card determines the interface. The module itself draws 0.6 W.
COM and RTU modes
COM: Fit the module to the right of a compatible CPU such as the AS300. The module bus supplies power. Fit AS-F232 / AS-F422 / AS-F485 in CARD 1 or CARD 2 for Modbus RTU/ASCII over RS-232 / RS-422 / RS-485 respectively. Fit AS-FCOPM in CARD 2 for CANopen slave operation.
RTU: The remote station uses a separate 24 V DC supply. Fit AS-FCOPM in CARD 2 for CANopen. AS-FEN02 provides EtherNet/IP and AS-FPFN02 provides PROFINET. Each occupies both slots. Fit compatible digital and analog I/O modules to the right of the station.
Configure the hardware in ISPSoft HWCONFIG. Use CANopen Builder or EIP Builder for the selected network. For PROFINET in COM mode, check CPU, SCM and card firmware in section 10.2.8 of the module manual.
Editor’s Note
Ask for the full card code when buying used.
Record the COM/RTU switch position.
Photograph the ID and FORMAT settings.
Check the supply and network settings against the manual.
On the bench, check the card LED first, then confirm data exchange.
PDFs and related topics
AS PLC PDF files · AS hardware manual (EN)
AS01DNET-A (DeviceNet) · AS04SIL-A (IO-Link)
More Delta pages AS specialty modules · AS expansion modules · Used Delta products
External references Installation sheet (TR/EN) · Module manual (EN, §9 and §10.2.8)