Delta AS-F485
Delta AS-F485 RS-485 communication card
The Delta AS-F485 is a single-port RS-485 serial card in the Delta AS function card range. It adds an independent serial channel and can operate as a master or slave. When linking a compatible DOP-100 operator panel or Delta VFD-EL drive over serial Modbus, match the field device’s protocol and serial settings.
Compatible hardware and card slots
The card occupies one slot. It fits slot 1 or 2 of an AS300 CPU, such as the AS300N-A. Both slots are also supported on the AS00SCM-A with its mode switch set to COM. Modbus RTU remains available as a serial protocol in this position. AS200 CPUs have built-in RS-485 ports. Direct CPU mounting requires an AS300 function card slot.
RS-485 terminals and bus termination
The active terminals on the five-position connector are 3 = D+, 4 = D−, 5 = SG. Positions 1 and 2 are unused. Delta’s wiring example uses shielded cable and 120 Ω termination at both physical ends of the bus. Match each device’s D+, D− and signal reference to its wiring diagram. See Delta PLC cables and PLC accessories for cable options.
ISPSoft and Modbus settings
Use HWCONFIG in ISPSoft to configure the occupied card slot. Match the baud rate, data bits, parity, stop bits, RTU or ASCII mode and station address to the existing network. COMMGR handles the PC connection to the PLC. For software documentation, see Delta PLC software.
The corresponding ID and FORMAT knobs on the AS00SCM-A work independently. Setting a knob to 0 lets the software control that parameter. For example, FORMAT 4 selects 9600 bps, 8 data bits, no parity, 1 stop bit and Modbus RTU. Match the settings to the actual network.
Editor’s Note
For a used card, start by checking the label, the five-position terminal block and the rear connector contacts.
With power off, seat the card in the correct slot. If you have an AS00SCM-A, record the COM switch position and knob settings.
For the first test, read a register with a known value from one station over a short cable.
If there is no response, check the D+/D− mapping first, then the station address and serial format.
If the short test cable works but the installed line drops out, check termination at both ends and the shield connection.
PDFs and related topics
Delta PLC and HMI manuals · AS-F232 RS-232 · AS-F422 RS-422 · AS-FCOPM CANopen · AS-FEN02 Ethernet
More Delta pages · AS expansion modules · Delta AS PLC series · Delta PLC main page · Used Delta equipment
External references
AS-F485 installation and wiring sheet (PDF, EN and TR included) · AS Hardware and Operation Manual (PDF, EN)
AS00SCM-A wiring and serial settings sheet (PDF, EN and TR included) · Delta AS catalogue and card slot table (PDF, EN)