Delta DVP power supplies

Delta DVP Power Supplies

Delta DVP power supplies are DVPPS switch-mode units that convert AC mains into a 24 V DC control supply. This group under Delta PLC accessories includes DVPPS01, DVPPS02 and DVPPS05. All three provide the same output voltage, with different maximum current and power capacities.

When selecting a supply for Delta DVP PLCs, verify the complete CPU model and required input voltage. DVPPS is a separate, wired AC/DC supply. It does not perform an I/O or communication function. Distinguish an AC-powered PLC from equipment requiring an external 24 V DC source.

DVPPS models and output capacities

Model Output voltage Maximum output current Rated power
DVPPS01 24 V DC 1 A 24 W
DVPPS02 24 V DC 2 A 48 W
DVPPS05 24 V DC 5 A 120 W

DVPPS01 serves smaller load budgets, DVPPS02 higher combined current requirements and DVPPS05 applications requiring a 5 A supply. A higher-current source does not force that current into the load; the circuit draws what it requires. Nevertheless, reassess wiring and branch protection against the selected source capacity.

AC input, DC output and terminals

The instruction sheet specifies 100–240 V AC, 50/60 Hz, −15%/+10% input tolerance and 24 V DC ±3% output. The catalogue’s 85–264 V AC range corresponds to those input tolerances. Connect AC mains to L and N, and the DC load to the labelled +24 V and DC return terminals.

Protective earth and DC return have different functions. Read terminal positions and labels for the complete model. Applying mains voltage to the 24 V output or PLC signal terminals damages equipment. Do not transfer the previous supply’s terminal order from memory.

Calculating PLC, panel and field loads

Include the CPU, suitable external modules, panels such as TP04P or TP70P, and field loads connected to the same supply. In TP panel and remote I/O installations, follow each device’s voltage and wiring requirements. Sharing a nominal 24 V rating does not establish suitability for every connection arrangement.

Add more than steady-state currents: consider startup demand, simultaneous coil operation and cabinet temperature. A PLC’s built-in sensor supply and an external DVPPS output are separate sources. Do not interconnect their outputs unless the manufacturer’s wiring instructions permit it.

Protection, mounting and heat

The manufacturer lists overcurrent/short-circuit protection with automatic recovery for all three models. DVPPS05 additionally lists overvoltage and overtemperature protection. Do not attribute these additional features to DVPPS01 or DVPPS02. Supply protection does not replace appropriate protection for field wiring and load branches.

Install the units inside a cabinet on 35 mm DIN rail or an appropriate direct-mount arrangement. The installation drawing specifies 50 mm clearance for cooling; follow that drawing when positioning the supply. Consider airflow, strain relief and access when reviewing HMI mounting and power connections and external terminals.

Route signals carried by DVP/AH I/O cables appropriately away from mains and power wiring. Conductor size, voltage drop and terminal tightness affect the loaded supply. Correct voltage at the power source does not establish the same voltage at a distant PLC input.

Comparing other Delta supplies

Assess Delta AS power supplies and Delta AH power supplies against their own electrical and mechanical systems. A supply used in an AS PLC or AH PLC installation is not automatically interchangeable with DVPPS because the brand or output voltage is similar. Compare terminals, voltages, current capacity and system power distribution together.

Editor's Note

A green power indicator is only the starting point. Check the output unloaded and then under a suitable load. If the PLC resets, measure at its supply terminals as well as at the source; a loose connection or undersized cable may be causing the voltage drop.

If the output collapses or cycles, do not immediately condemn the supply. Isolate power safely, disconnect field loads and then test branches individually under controlled conditions. A shorted sensor or damaged coil can put a healthy supply into protection.

When buying a used unit, verify its complete model, input voltage and output current from the nameplate. A 24 V marking alone is insufficient: 1 A, 2 A and 5 A represent substantially different capacities. Check stable operation on a suitable test load before accepting an unloaded voltage reading as proof of condition.

Investigate clicking, excessive heat, burnt odour, discoloured terminals or swollen capacitors. Disconnect mains and verify that capacitors are discharged before opening the unit. Replacement capacitors require appropriate voltage, temperature and ESR ratings as well as capacitance. Never bridge a fuse or protection circuit.

When fitting a higher-current model, reassess cabinet space, conductor sizes and branch fuses. Increasing source capacity does not repair damaged loads or undersized wiring. Label cables before removal so that the L/N and 24 V sides remain clearly identified.

Complete the final test under normal machine load, including coil switching and other consumers. Observe voltage stability and heating. If the fault occurs only in a hot cabinet, assess ventilation, installation clearances and continuous load together.

PDF and technical files

The document hub is Delta PLC accessories files. Further references are available through Delta PLC and HMI manuals and Delta user manuals. DVPPS supplies do not receive a downloaded program; read the installation sheet, terminal drawing and powered device’s hardware manual together.

Related topics

Delta DVP programming cables · Delta DVP communication cables · Delta DVP memory accessories · Delta DVP other accessories

Navigation: Delta PLC accessories · Delta PLC main group · Used Delta products

External references

Delta DVPPS01/02/05 instruction sheet — includes English · Delta DVP/TP catalogue — power supply selection table, English